Veris VWG-40 Installation Instructions

VWG-40
Viconics Wireless Gateway
Hardware Installation Guide
(Issue Date September 24, 2008 – 028-0179 R8)
Product overview
The VWG-40 and related wireless thermostats are targeted to retrofit applications where the addition of communicating field bus wiring within the building space is prohibitive. The Gateway and Communicating Thermostats with wireless field bus encourages the use of existing wiring utilized by existing electronic thermostat type controls.
The VWG-40 when utilized in conjunction with the VT7xxxXxxxxW series wireless thermostats will offer the integrator simple BACnet IP or BACnet MS/TP objects to integrate over standard building automation systems using familiar integration toolsets.
A maximum of 30 wireless thermostats can be wirelessly attached to a single VWG The following additional documentation is available on www.viconics.com
Gateway BACnet integration guide (VWG-40-IP & VWG-40-MSTP), is available in document ITG-VWG-40-BAC-E xx
Information on design consideration of wireless mesh networ ks and VWG set-up / diagnostics is available in document LIT-
VWG-40-SETUP-Exx
Part available
Part number Description
VWG-40-IP-1000 Viconics BACnet over IP wireless gateway. Includes:
- Supports up to 30 wireless thermostats
- Factory mounted wireless adapter
- 24 Vac panel mounted power supply
- Gateway mounted antenna
VWG-40-MSTP-1000 Viconics BACnet RS485 MS-TP wireless gateway. Includes:
- Supports up to 30 wireless thermostats
- Factory mounted wireless adapter
- 24 Vac panel mounted power supply
- Gateway mounted antenna
VWG-40-LON-1000
(Upcoming)
Viconics LON wireless gateway. Includes:
- Supports up to 30 wireless thermostats
- Factory mounted wireless adapter
- 24 Vac panel mounted power supply
- Gateway mounted antenna
VWG-APP
Interface software for VWG configuration and set-up. Operates under Windows XP ™. Uses a LAN crossover IP connection for initial set-up.
VWG-RA
Remote antenna for gateway when the gateway is installed inside a metal cabinet or
when remote antennal mounting is required by physical installation VWG-WA Replacement antenna for gateway mounted antenna setup VWG-PS-DC 24 Vac to 15 Vdc panel mounted power supply for VWG VWG-PS-AC 120 Vac to 15 Vdc power supply for VWG with cord VWG-BB Replacement battery backup pack for the VWG
Trademarks
Niagara, Niagara AX is a registered trademark of Tridium, Inc. LON, LonWorks and LonTalk are registered trademarks of Echelon Corporation BACnet is a registered trademark of ASHRAE
1
Disclaimers
NO WARRANTY. Viconics, Inc. ( herein after referred to as “Viconics” ) makes no warranty as to the accuracy of or use of this technical documentation. Any use of the technical documentation or the information contained therein is solely at the risk of the user.
Documentation may include technical or other inaccuracies or typographical errors. Viconics reserves the right to make changes to this document without prior notice, and the reader should in all cases consult Viconics to determine whether any such changes have been made. The information in this publication does not represent a commitment on the part of Viconics. Viconics shall not be liable for incidental or consequential damages resulting from the furnishing, performance, or use of this material.
This guide contains links and references to third-party websites that are not under the control of Viconics, and Viconics is not responsible for the content of any reference material or linked websites. If you access a third party website mentioned in this guide, then you do so at your own risk. Viconics provides these links only as a convenience, and the inclusion of the link does not imply that Viconics endorses or accepts any responsibility for the content on those third­party sites.
Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and installing the Viconics wireless gateway.
All Viconics wireless gateways and related wireless thermostats are to be used only as operating controls. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety devices and/or alarm system to protect against such catastrophic failures.
All VT7000 series wireless thermostats and associated VWG (Viconics Wireless Gateway) have been rigorously tested to ensure reliable operation in most building applications using the latest 2.4 ZigBee technologies. Viconics cannot guarantee against potential network interference should additional wireless systems be deployed sharing close proximity.
Best practices covered in this manual and all related Viconics VWG documents should be considered as a guide to apply Viconics Wireless Network devices only. The instructions included in this manual are based upon Viconics in house testing and should be referred to as a guide only.
Viconics Inc. may not be held liable for continued reliable, or robust operation of any and all wireless based devices. Although Viconics has taken many precautions in assuring the robustness of the VT7000 series wireless thermostat product line and associated network access point (VWG-40-XXXX-1000) Please note; future application of additional wireless devices utilizing the same or similar channels and / or frequencies may degrade performance of overall system and / or reliability.
Non-approved modifications or changes made to the VWG or wireless thermostats may void the FCC compliance of the VWG and wireless thermostats.
Ferrites supplied with the power supply and VWG MUST be installed according to instructions. Failure to do so may void the FCC compliance of the VWG and wireless thermostats.
Only VWG-PS-DC and VWG-PS-AC power supply can be used with the VWG. The usage of another non -approved power supply may void the FCC compliance of the VWG and wireless thermostats.
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
2
Overview
This document covers the mounting and wiring of the Viconics VWG-40 series product. It assumes that you are an engineer, technician, or service person who is performing control system installation. Instructions in this document apply to the following products:
Models Description
VWG-40-IP-1000 Viconics BACnet over IP wireless gateway. VWG-40-MSTP-1000 Viconics BACnet RS485 MS-TP wireless gateway. VWG-40-LON-1000 Viconics LON wireless gateway. (Upcoming)
Note Not covered in this document is the configuration appliance software required for fully setup the gateway . This includes setting host IP address, passwords, database, and other ther mostat and network utilities. Refer to the document LIT-VWG-40-SETUP-Exx for more information.
Table of contents
These are the main topics included in this document:
Preparation
Precautions
Mounting
Board Layout
About Expansion Options
Wiring Details
Power Up and Initial Checkout
Also included in this document are several appendixes, as follows:
Using Status LEDs
Maintaining the VWG
Replacement and accessory
Certifications
Declaration of Conformity
Information and specifications published here are current as of the date of publication of this document. Viconics, Inc. reserves the right to change or modify speci fications without prior notice. One or more U.S. or foreign patents may cover products or features contained herein.
Preparation
Unpack the VWG and power module (either VWG-PS-DC or VWG-PS-AC) and inspect the contents of the packages for damaged or missing components. Be sure the factory-installed ferrite is on the cord of the power supply unit. If damaged, notify the appropriate carrier at once and return any damaged components for immediate repair or replacement.
Included in this Package
Included in this package you should find the following items:
VWG-40-XX-1000 base controller.
Local antenna for the VWG
This VWG-40-XX-1000 Hardware installation guide
Configuration tool on a mini-CD
Power module required for operation, are ordered and sold separately. The power module can be one of the
following: – VWG-PS-DC: 24Vac in-line (DIN-mount capable), or – VWG-PS-AC: External 120 Vac wall-mount power adapter
3
f
Material and Tools Required
The following tools and supplies may be required for installation:
DIN rail, type NS35/7.5 (35mm x 7.5mm), recommended for panel mount installation. Length of DIN rail should be minimum 6.5 “ ( 165 mm ).
If using an VWG-PS-DC power supply, use UL listed, Class 2, 24Vac transformer, supplying a minimum of 5VA to the VWG. Note that the VWG-PS-DC power supply provides isolation — a dedicated transformer is not required.
Suitable screws and screwdriver for mounting DIN rail, or if DIN rail not used, for mounting bases of VWG controller and VWG-PS-DC power supply (if used).
Precautions
This document uses the following warning and caution conventions:
Cautions remind the reader to be c areful. They alert readers to situations where the re is a chance that the reader might perform an action that cannot be undone, might receive unexpected results, or might lose data. Cautions contain an explanation of why the action is potentially problematic.
Warnings alert the reader to proceed with extreme care. They alert readers to situations where there is a cha nce that the reader might do something that can result in personal injur y or equipment damage. Warnings contain an explanation o why the action is potentially dangerous.
Safety Precautions
The following items are warnings of a general nature relating to the installation and start-up of the VWG controller. Be sure to heed these warnings to prevent personal injury or equipment dama ge.
Depending on power module used, the circuit powering the VWG is 24Vac at 50/60 Hz (if using the VWG-PS-DC power
supply or 120 Vac at 50/60 Hz (if using the VWG-PS-AC power supply). Disconnect power before installation or servicing to prevent electrical shock or equipment damage.
Make all connections in accordance with national and local electrical codes. Use copper conductor s o nl y.
To reduce the risk of fire or electrical shock, install in a controlled environment relatively free of contam i n an ts .
This device is only intended for use as a moni toring and cont rol device . To p revent d ata loss o r equipm ent dam age, do
not use it for any other pu rpose.
All Viconics wireless gateways and related wireless thermostats are to be used only as operating controls. Whenever a control
failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety devices and/or alarm system to protect against such catastrophic failures.
Static Discharge Precautio ns
Static charges produce voltages high enough to damage electronic components. The microprocessors and associated circuitry within a VWG controller are sensitive to static discharge. Follow these precautions when installing, servicing, or operating the system:
Work in a static-free area.
Discharge any static electricity you may have accumulated . Discharge static ele ctricity by touching a k nown,
securely grounded object.
Do not handle the printed circuit board (PCB) without proper protection against static discharge. Use a wrist strap when
handling PCBs. The wrist strap clamp must be secured to earth ground.
4