REL AYS
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
VTD2P -F50
VTD2P -F50
Time Delay, Multi-Function DPDT Relay
Installer’s Specifications
Operating Range 85% to 110% of nominal voltage
Drop-Out Voltage Threshold 15% of nominal voltage
Expected Relay Life Electrical (resistive @ rated current) 100,000 c ycles;
Mechanical (unpowered) 10,000,000 cycles
Dielectric Strength 1000VAC (RMS)
Operating Temperature -20°C to 55°C (-4 to 131°F)
INSTALLATION
Disconnect and lock out all power sources before beginning the
installation.
1. Connect relay contacts.
2. Secure the enclosure and reconnect power.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
RED LED
LAMP INDICATOR
VERIS INDUSTRIES
1-800-354-8556
A-ON DELAY
B-REPEAT
C-INTERVAL
VTD2P-F50
Positive position
thumb wheel adjustments
D-OFF DELAY
E-ONE SHOT
TIME SET
A S0 0 0
1.87"
(47mm)
1.87"
TIME
BASE
(47mm)
3.47"
(88mm)
1.80"
(45mm)
WIRING EXAMPLE
EXTERNAL CONTROL SWITCH
4
3
2
6
5
1
11
INPUT
7
8
9
10
ZL0008-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
PANEL CUTOUT
FOR PANEL MOUNTING
(45mm)
1.80"
VTD2P-F50
TM
INSTALLATION GUIDE
TIME DELAY FUNCTIONS
ON DELAY: When input voltage is applied, the output relay remains o for a
programmed time inter val, then turns on. Applying control input has no eect on
the timing or state of the relay. The LED ashes while the output relay is o and is on
continuously when the output relay is on.
OFF DELAY: Input voltage is on continuously. When control voltage is applied,
the output relay turns on. The time interval begins when the control input turns
o. Reapplying the control input resets the time to zero and inhibits timing until
removed. The LED is o while the control input is on, ashes during the time delay
interval, and is on continuously when the output relay is o.
REPEAT: Input voltage is on continuously. When input voltage is rst applied, the
output relay remains o for a programmed time interval, then turns on. Relay stays
on for an equal time interval, then cycles on and o for this time interval until the
input power is removed. Applying control input has no eect on the timing or state of
the relay. The LED ashes when output relay is o and is on continuously when relay
is on.
INTERVAL: When input voltage is applied, the output relay turns on for a
programmed time inter val. The output relay only turns on once for each application
of input voltage. Applying control input has no eect on the timing or state of the
relay. The LED ashes when the output relay is on and is on continuously when the
output relay is o.
ONE SHOT: Input voltage is on continuously. When the control voltage is applied, the
output relay turns on for a programmed time interval, then turns o. The LED is on
continuously when the output relay is o and ashes when the relay is on.
TIME DELAY SETTINGS
A-ON DELAY
B-REPEAT
C-INTERVAL
D-OFF DELAY
E-ONE SHOT
A S0 0 0
TIME
SET
TIME
BASE
LED
LAMP
.1S = 0.1-99.9
.1M = 0.1-99.9
.1H = 0.1-99.9
10H = 10-9,990 Hours
SELECT REQUIRED TIME
(SEE TIME RANGES ABOVE)
SET FUNCTIONS
A - ON DELAY
B - REPEAT
C - INTERVAL
D - OFF DELAY
E - ONE SHOT
S = 1-999 SEC
M = 1-999 MIN
H = 1-999 HOURS
CONTACT AND COIL SPECIFICATIONS
Function Timing Chart
ON D ELAY
(Power On)
OFF DELAY
(S Break)
REPEAT CYCLE
(Star ting O )
INTERVAL
(Power On)
ONE SHOT
U: Applied input voltage
S: Control switch (open or closed)
R: Relay contacts (on or o)
T: Time delay
U
T T
R
U
S
R
U
R
U
R
U
S
R
T T
T
T
T
T T
T T T
T
T
TYPICAL COIL PERFORMANCE
Power Consumption
AC ...................................................... 2.5VA
DC...................................................... 2W
CONTACT RATINGS
T
T
T
Resistive ...........12A@240VAC, 30VDC
Pilot Duty..........B300
TIMING CHARACTERISTICS
Funtions Available 5
T
Time Ranges
0.1 sec 0-999
sec 0-999
0.1 min 0-999
min 0-999
0.1 hr 0-999
hr 0-999
10 hr 0-999
0.1 day -- day --Tolerance 0%
(mechanical setting)
Repeatability 0.1%
Operate Time (max) 25 msec
Reset Time (max) 150 msec
Trigger Pulse Length
(min) ---
ZL0008-0C PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.