Veris VTD2P-F50 Installation Instructions

REL AYS
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
VTD2P -F50
VTD2P -F50
Time Delay, Multi-Function DPDT Relay
Installer’s Specifications
Operating Range 85% to 110% of nominal voltage Drop-Out Voltage Threshold 15% of nominal voltage Expected Relay Life Electrical (resistive @ rated current) 100,000 c ycles; Mechanical (unpowered) 10,000,000 cycles Dielectric Strength 1000VAC (RMS) Operating Temperature -20°C to 55°C (-4 to 131°F)
INSTALLATION
Disconnect and lock out all power sources before beginning the installation.
1. Connect relay contacts.
2. Secure the enclosure and reconnect power.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
RED LED LAMP INDICATOR
VERIS INDUSTRIES
1-800-354-8556
A-ON DELAY B-REPEAT C-INTERVAL
VTD2P-F50
Positive position thumb wheel adjustments
D-OFF DELAY E-ONE SHOT
TIME SET
A S0 0 0
1.87"
(47mm)
1.87"
TIME BASE
(47mm)
3.47"
(88mm)
1.80"
(45mm)
WIRING EXAMPLE
EXTERNAL CONTROL SWITCH
4 3
2
6
5
1
11
INPUT
7
8
9
10
ZL0008-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
PANEL CUTOUT
FOR PANEL MOUNTING
(45mm)
1.80"
VTD2P-F50
TM
INSTALLATION GUIDE
TIME DELAY FUNCTIONS
ON DELAY: When input voltage is applied, the output relay remains o for a programmed time inter val, then turns on. Applying control input has no eect on the timing or state of the relay. The LED ashes while the output relay is o and is on continuously when the output relay is on.
OFF DELAY: Input voltage is on continuously. When control voltage is applied, the output relay turns on. The time interval begins when the control input turns o. Reapplying the control input resets the time to zero and inhibits timing until removed. The LED is o while the control input is on, ashes during the time delay interval, and is on continuously when the output relay is o.
REPEAT: Input voltage is on continuously. When input voltage is rst applied, the output relay remains o for a programmed time interval, then turns on. Relay stays on for an equal time interval, then cycles on and o for this time interval until the input power is removed. Applying control input has no eect on the timing or state of the relay. The LED ashes when output relay is o and is on continuously when relay is on.
INTERVAL: When input voltage is applied, the output relay turns on for a programmed time inter val. The output relay only turns on once for each application of input voltage. Applying control input has no eect on the timing or state of the relay. The LED ashes when the output relay is on and is on continuously when the output relay is o.
ONE SHOT: Input voltage is on continuously. When the control voltage is applied, the output relay turns on for a programmed time interval, then turns o. The LED is on continuously when the output relay is o and ashes when the relay is on.
TIME DELAY SETTINGS
A-ON DELAY B-REPEAT C-INTERVAL D-OFF DELAY E-ONE SHOT
A S0 0 0
TIME
SET
TIME BASE
LED LAMP
.1S = 0.1-99.9 .1M = 0.1-99.9 .1H = 0.1-99.9 10H = 10-9,990 Hours
SELECT REQUIRED TIME (SEE TIME RANGES ABOVE)
SET FUNCTIONS A - ON DELAY B - REPEAT C - INTERVAL D - OFF DELAY E - ONE SHOT
S = 1-999 SEC M = 1-999 MIN H = 1-999 HOURS
CONTACT AND COIL SPECIFICATIONS
Function Timing Chart
ON D ELAY (Power On)
OFF DELAY (S Break)
REPEAT CYCLE (Star ting O )
INTERVAL (Power On)
ONE SHOT
U: Applied input voltage S: Control switch (open or closed) R: Relay contacts (on or o) T: Time delay
U
T T
R
U S
R
U
R
U
R
U S
R
T T
T
T
T
T T
T T T
T
T
TYPICAL COIL PERFORMANCE
Power Consumption
AC ...................................................... 2.5VA
DC...................................................... 2W
CONTACT RATINGS
T
T
T
Resistive ...........12A@240VAC, 30VDC
Pilot Duty..........B300
TIMING CHARACTERISTICS
Funtions Available 5
T
Time Ranges
0.1 sec 0-999 sec 0-999
0.1 min 0-999 min 0-999
0.1 hr 0-999 hr 0-999 10 hr 0-999
0.1 day --­ day --­Tolerance 0%
(mechanical setting)
Repeatability 0.1% Operate Time (max) 25 msec Reset Time (max) 150 msec Trigger Pulse Length
(min) ---
ZL0008-0C PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05122