The VT76xxA and VT76xxB Series PI thermostat family provides single stage and multi-stage control of heating/cooling equipment, including rooftop and self­contained units. The product features an intuitive, menu-driven, back-lit LCD display that walks users through the simple programming procedure, making installation extremely simple.
All models contain two user-controlled digital inputs that monitor lter status, change the occupancy status, and/or provide general purpose service indication. Some models oer up to three remote sensor inputs. All models contain a discharge air sensor input and SPST auxiliary switch, which can be used to control lighting or disable the economizer function. All devices are available with Echelon, BACnet, or wireless adapters.
APPLICATIONS
Single speed fans
setpoint devices
Supply air temperature sensor
Outdoor air temperature sensor
Dierential pressure switch
VT7600A5000
FEATURES
PI time proportioning algorithm...increased comfort, accuracy, and
energy savings
2 digital inputs...adds functionality
Smart fan...saves energy during night mode
Unique local conguration utility...minimizes parameter tampering
Lockable keypad...tamper proof, no need for thermostat guards
Freeze protection...prevents costly freeze damage
EEPROM memory...no loss of program
6 hour reserve time for clock...no need to reprogram day or time after
power outage
Remote room and outdoor temperature sensor...increased exibility
and functionality
Auxiliary output...can be used for lighting and/or economizer override
Discharge air sensor...can be used to monitor unit eciency
Intuitive, menu-driven programming...can be used for all types
of establishments
SPECIFICATIONS
Thermostat Power Requirements 19-30VAC; 50 or 60 Hz; 2 VA Class 2 Operating Conditions 0° to 50°C (32° to 122°F); 0 to 95% RH non-condensing Storage Conditions -30° to 50°C (-22° to 122°F); 0 to 95% RH non-condensing Temperature Sensor Local 10 K NTC thermis tor Resolution ± 0.1°C (± 0.2° F) Control Acc uracy Temp: ±0.5°C (±0.9°F ) @ 21°C (70°F) typical, calibrated Occupied and Unoccupied Setpoint Range Cooling 12° to 38°C (54° to 100°F) Occupied and Unoccupied Setpoint Range Heating 4.5° to 32°C (40° to 90°F) Room and Outdoor Air Temperature Display -40° to 50°C (-40° to 122°F) Proportional Band for Room Temperature Range Control Cooling & Heating: 1.8°C (3.2°F ) Binary Inputs Dry contact acros s terminal BI1, BI2 & UI3 to Scom Outputs Rating Triac output: 30VAC, 1A max., 3A in-rush; Analo g: 0 to 10VDC into 2k Ω resistance min. Economizer Analog Output Rating 0 to 10VDC into 2kΩ resis tance min. Economizer Analog Output Accuracy ±3% typical Wire Gauge 18 gauge maximum, 22 gauge recommended Dimensions 4.94” x 3.38” x 1.13” Approximate Shipping Weight 0.75 lb (0.34 kg)
UL: 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN , XAPX (US) and XAPX7 (Canada) FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US) Industry Canada: ICES- 003 (Canada) CE: EMC Directive 89/336/EEC (European Union) C-Tick: AS/NZS CISPR 22 Compliant (Australia / New Zealand); Supplier Code Number N10696
800.354.8556
Year
2
Warranty
+1 503.598.4564
www.veris.com
HQ0001866.B 01131
800.354.8556
10
AUX
1Y22Y13G4RC5
C
6RH7W18
W2
11
DI1
12
DI2
13RS14
S
COM
15OS16
MS
FAN
Y2
15 14
Y1 G RC C W1 W2
1 2 3 4 5 7 8
16 14
OA temp.
sensor
Differential
pressure
switch
Supply air
temp.
sensor
14 11
Filter
10
AUX
2Y13G4RC5
C
6RH7
W1
11
DI1
12
DI2
13RS14
S
COM
15OS16
MS
FAN
15 14
Y1 G RC C W 1
2 3 4 5 7
16 14
OA temp.
sensor
Differential
pressure
switch
Supply air
temp.
sensor
14 11
Filter
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
4.9”
(125mm)
1.1”
(28mm)
3.4”
(87mm)
ORDERING INFORMATION
APPLICATION/WIRING EXAMPLES
Typical 1H/1C Application
1.25”
(32mm)
1.5”
(37mm)
* Use for single speed fans, supply air tem perature sensors, outdoor air temperature sensors, and dierential pressure switch es.
Typical 2H/2C Application
MANUF. PART # ORDERING # DESCRIPTION COMM.
VT7600A5000 U010-0001
VT7600A5000B U010-0002 BACnet (MS/TP)
VT7600A5000E U010-0003 Echelon
VT7600A5000W U010-0004 Wireless (Zigbee)
VT7600B5000 U010-0005
VT7600B5000B U010-0006 BACnet (MS/TP)
VT7600B5000E U010-0007 Echelon
VT7600B5000W U010-0008 Wireless (Zigbee)
VT7652A5000 U010-0009
VT7652A5000B U010-0010 BACnet (MS/TP)
VT7652A5000E U010-0011 Echelon
VT7652A5000W U010-0012 Wireless (Zigbee)
VT7652B5000 U010-0013
VT7652B5000B U010-0014 BACnet (MS/TP)
VT7652B5000E U010-0015 Echelon
VT7652B5000W U010-0016 Wireless (Zigbee)
1H/1C thermostat, non­programmable; PIR Ready (PIR cover not included)
2H/2C thermostat, non­programmable; PIR Ready (PIR cover not included)
1H/1C thermostat, programmable; PIR Ready (PIR cover not included)
2H/2C thermostat, programmable; PIR Ready (PIR cover not included)
VT7600A5500 U010-0017
VT7600A5500B U010-0018 BACnet (MS/TP)
VT7600A5500E U010-0019 Echelon
VT7600A5500W U010-0020 Wireless (Zigbee)
1H/1C thermostat, non­programmable; PIR factory equipped
VT7600B5500 U010-0021
VT7600B5500B U010-0022 BACnet (MS/TP)
VT7600B5500E U010-0023 Echelon
2H/2C thermostat, non­programmable; PIR factory equipped
VT7600B5500W U010-0024 Wireless (Zigbee)
VT 7652A550 0 U010-0025
VT 7652A550 0B U010-0026 BACnet (MS/TP)
VT 7652A550 0E U010-0027 Echelon
VT 7652A550 0W U010-0028 Wireless (Zigbee)
1H/1C thermostat, programmable; PIR factory equipped
VT 7652B5500 U010-0029
VT 7652B5500 B U010-0030 BACnet (MS/TP)
VT 7652B5500 E U010-0031 Echelon
VT 7652B5500 W U010-0032 Wireless (Zigbee)
HQ0001866.B 01131
2H/2C thermostat, programmable; PIR factory equipped
Stand alone
Stand alone
Stand alone
Stand alone
Stand alone
Stand alone
Stand alone
Stand alone
setpoint devices
* Use for single speed fans, supply air temperature sensors, outdoor air temperature sensors, and dierential pressure switches.
Loading...