Veris VST121 Installation Instructions

RELAYS
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V S T1 20 (- 4), V S T121(-4)
V S T1 20 (- 4), V S T121(-4)
Track Mount 20 Amp SPDT Relay
Installer’s Specifications
Operating Temperature 0° to 60°C (32° to 140°F) Operating Humidity 10-90% RH, non-condensing Relay Status LED ON=energized Auxiliar y Supply for HOA 24VAC/DC (supplied from a Class 2 or LVLE source)* Expected Relay Life Electrical (@ rated current) 100,00 0 cycles; Mechanical (unpowered) 10,000,000 cycles Terminal Block Torque 0.5 to 3.5 in-lb (0.68 to 4.75 N-m) Insulation Class 600VAC RMS (coil to contact); 120VAC RMS (terminal to surf ace) Agency Approvals UL508 open device listing; Installation Categor y III, pollution degree 2
*Class 2 source: A source that provides a Class 2 power supply as dene d by the NEC, NFPA70. LVLE: Low voltage limited energy, not capable of p roviding more than 30VAC/42.4VDC, 8A or 100 VA
INSTALLATION
Disconnect and lock out all power sources before beginning the installation.
1. Snap the VST into a mounted track of the appropriate size.
SNAP
SNAP
VSTxx: 2.75” (70 mm) VSTxx-4: 4” (102 mm)
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Z204232-0A PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05123
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
2. Connect the coil wires as shown. Use either 24 VAC/DC for the Auto Low Voltage input or 120 VAC for the Auto High Voltage input. Do not use both the Auto Low Voltage and Auto High Voltage inputs at the same time.
COMMON Input
COIL 24AC/DC Input
COIL120VAC Input
3. Connect the contact terminals to the load(s), as required.
4. If using a VST121 or VST121-4, set the HOA switch to the correct position for your application, Hand, Auto or O. If using the Hand position, connect 24 VAC/DC to the AUX terminal to power the device.
OFF AUTO HAND
COMMON Input
COIL 24AC/DC Input
COIL 120VAC Input
AUX 24VAC/DC Input
5. Secure the enclosure and reconnect power.
COMMON Contact
NO Contact
NC Contact
COMMON Contact
NO Contact
NC Contact
VST120(-4), VST121(-4)
TM
INSTALLATION GUIDE
DIMENSIONS
1.45"
(37 mm)
VST120 and VST121
2.75"
(70 mm)
VST120-4 and VST121-4
3.7"
(94 mm)
1.8"
(46 mm)
0.9"
(23 mm)
1.8"
(46 mm)
WIRING EXAMPLE
CONTROL PANEL
Relay
Contacts
24VAC/DC Coil Power
To Load
24VAC/DC Aux HOA Switch Power
(not available on all models)
24VAC/DC
POWER SUPPLY
DIGITAL
CONTROLLER
CONTACT AND COIL SPECIFICATIONS
TYPICAL COIL PERFORMANCE
Voltage Coil Current AC DC
24V.......................................... 75mA 32mA
120V........................................ 42mA -
CONTACT RATINGS
Ø .15”
(4 mm)
4.0"
(102 mm)
0.9"
(23 mm)
Resistive....... 20A@250VAC
10A@28VDC
Motor........... 120VAC, 1HP
Z204232-0A PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05123
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.