HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INsTallaTION GUIDe
VST10 (-4), VST11 (-4)
VST10 (-4), VST11 (-4)
Track Mount 10 Amp SPDT Relay
Installer’s Specifications
Operating Temperature 0° to 60°C (32° to 140°F) Operating Humidity 10-90% RH, non-condensing Relay Status LED ON=energized Auxiliar y Supply for HOA 24VAC/DC (supplied from a Class 2 or LVLE source)* Expected Relay Life Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles Terminal Block Torque 0.5 to 3.5 in-lb (0.68 to 4.75 N-m) Insulation Class 600VAC RMS (coil to contact); 120VAC RMS (terminal to surface) Agency Approvals UL508 open device listing; Ins tallation Category III, pollution degree 2
*Class 2 source: A source that provides a Class 2 power supply as dene d by the NEC, NFPA-70. LVLE: Low voltage limited energy, not capable of p roviding more than 30VAC/42.4VDC, 8A or 100 VA
installation
Disconnect and lock out all power sources before beginning the installation.
1. Snap the VST into a mounted track of the appropriate size.
SNAP
SNAP
VSTxx: 2.75” (70 mm) VSTxx-4: 4” (102 mm)
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
2. Connect the coil terminals as indicated below. The status LED is closest to the load terminals. Use a single 24 VAC/DC Class 2 or low-voltage limited energy (LVLE), power source. Fusing is mandatory if the control voltage supply can provide > 4 A.
COIL COMMON
COIL Input 24VAC/DC
AUX Input 24VAC/DC
VST11s Only
3. Connect the contact terminals to the load(s), as required.
4. If using a VST11 or VST11-4, set the HOA switch to the correc t position for your application, Hand, Auto, or O. If using the Hand position, connect the 24 VAC/DC coil power to the AUX terminal to power the switch.
5. Secure the enclosure and reconnect power.
OFF AUTO HAND
Z204230-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
NC Contact
COMMON Contact
NO Contact
VsT10 (-4), VsT11 (-4)
TM
INsTallaTION GUIDe
dimEnsions
VST10 and VST11
2.75"
(70 mm)
VST10-4 and VST11-4
3.7"
(94 mm)
1.1"
(28 mm)
0.9"
(23 mm)
Wiring ExamplE
CONTROL PANEL
Relay
Contacts
24VAC/DC Coil Power
To Load
24VAC/DC Aux HOA Switch Power
(not available on all models)
24VAC/DC
POWER SUPPLY
DIGITAL
CONTROLLER
0.8"
(25 mm)
4Ø = 0.15”
(4 mm)
4.0"
(102 mm)
1.1"
(28 mm)
0.9"
(23 mm)
ContaCt and Coil spECifiCations
TYPICAL COIL PERFORMANCE
Coil Current VOLTAGE AC DC
24V..................................... 32mA 15mA
CONTACT RATINGS
Resistive...... 10A@250VAC
5A@30VDC
Motor......... 120VAC, 1/4HP N.O.
1/8 HP N.C.
Z204230-0C PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122