HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INsTallaTION GUIDe
VST10 (-4), VST11 (-4)
VST10 (-4), VST11 (-4)
Track Mount 10 Amp SPDT Relay
Installer’s Specifications
Operating Temperature 0° to 60°C (32° to 140°F)
Operating Humidity 10-90% RH, non-condensing
Relay Status LED ON=energized
Auxiliar y Supply for HOA 24VAC/DC (supplied from a Class 2 or LVLE source)*
Expected Relay Life Electrical (@ rated current) 100,000 cycles;
Mechanical (unpowered) 10,000,000 cycles
Terminal Block Torque 0.5 to 3.5 in-lb (0.68 to 4.75 N-m)
Insulation Class 600VAC RMS (coil to contact); 120VAC RMS (terminal to surface)
Agency Approvals UL508 open device listing; Ins tallation Category III, pollution degree 2
*Class 2 source: A source that provides a Class 2 power supply as dene d by the NEC, NFPA-70.
LVLE: Low voltage limited energy, not capable of p roviding more than 30VAC/42.4VDC, 8A or
100 VA
installation
Disconnect and lock out all power sources before beginning the
installation.
1. Snap the VST into a mounted
track of the appropriate size.
SNAP
SNAP
VSTxx: 2.75” (70 mm)
VSTxx-4: 4” (102 mm)
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
2. Connect the coil terminals as indicated below. The status LED is closest to the load
terminals. Use a single 24 VAC/DC Class 2 or low-voltage limited energy (LVLE),
power source. Fusing is mandatory if the control voltage supply can provide > 4 A.
COIL COMMON
COIL Input 24VAC/DC
AUX Input 24VAC/DC
VST11s
Only
3. Connect the contact terminals to the load(s), as required.
4. If using a VST11 or VST11-4, set the HOA switch to the correc t position for your
application, Hand, Auto, or O. If using the Hand position, connect the 24 VAC/DC
coil power to the AUX terminal to power the switch.
5. Secure the enclosure and reconnect power.
OFF
AUTO
HAND
Z204230-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
NC Contact
COMMON Contact
NO Contact
VsT10 (-4), VsT11 (-4)
TM
INsTallaTION GUIDe
dimEnsions
VST10 and VST11
2.75"
(70 mm)
VST10-4 and VST11-4
3.7"
(94 mm)
1.1"
(28 mm)
0.9"
(23 mm)
Wiring ExamplE
CONTROL PANEL
Relay
Contacts
24VAC/DC
Coil Power
To
Load
24VAC/DC Aux HOA Switch Power
(not available on all models)
24VAC/DC
POWER
SUPPLY
DIGITAL
CONTROLLER
0.8"
(25 mm)
4Ø = 0.15”
(4 mm)
4.0"
(102 mm)
1.1"
(28 mm)
0.9"
(23 mm)
ContaCt and Coil spECifiCations
TYPICAL COIL PERFORMANCE
Coil Current
VOLTAGE AC DC
24V..................................... 32mA 15mA
CONTACT RATINGS
Resistive...... 10A@250VAC
5A@30VDC
Motor......... 120VAC, 1/4HP N.O.
1/8 HP N.C.
Z204230-0C PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122