Veris V550 Installation Instructions

1.0 SCOPE

2.0 RECEIVING INSPECTION

The following tasks should be performed as part of the receiving inspection procedure:
Check items received against the packing list.
Check sensor nameplate for proper model num-
ber, serial number and customer number.
Verify that the actual pipe diameter matches the ID stated on the sensor nameplate.
Check the bullet shaped sensor tube for any signs of damage. Damage to the sensor tube may result in erroneous flow readings.
Check the round cover tube for any damage, especially axial gouges or scratches. Damage to the cover tube may prevent the ferrule from sealing properly.
3.0 SAFETY PRECAUTIONS
The following tasks should be conducted prior to install­ing the Verabar flow sensor:
Check maximum operating conditions on the flow sensor nameplate and verify that they exceed the maximum conditions of the installation. If any pressure, temperature or flow limits will be exceeded, consult the factory before proceeding.
Check that the pipe is depressurized and drained prior to installation.
Piping Configuration
Table 1. Straight Run Requirements
Verabar V550 (Flanged Spring-Lock)

INSTALLATION INSTRUCTIONS

The Flanged Spring-Lock Model V550 is designed for carbon and stainless steel pipes with a schedule 10 or heavier wall thickness. The V550 should not be used with PVC, copper, aluminum, cast iron or thin-walled pipes or ducts. If there is any question as to the proper application for a model V550, consult the factory.
4.0 INSTALLATION PREPARATIONS
4.1 Location
For the most accurate flow measurement, a minimum straight run of pipe is required. Table 1 shows the minimum straight run requirements.
If longer straight runs are available, position the Verabar such that the ratio of upstream straight run to downstream straight run is approximately 4 to 1. If straight run lengths are less than the values stated in Table 1, consult the factory for additional accuracy and location information.
Position straightening vanes such that the end closest to the Verabar is half way between the Verabar and the closest upstream configuration. For elbow installations, mount the Verabar in the same plane as the closest upstream elbow.
4.2 Orientation
Verify the proper sensor orientation by checking for an “-H” (horizontal piping) or a “-V” (vertical piping) in the model number on the Verabar nameplate.
4.2.1 Horizontal Piping
For air or gas installations, mount the Verabar in the upper 160° of the pipe to allow any condensate to drain into the pipe (Figure 1). For liquid or steam installations, mount the Verabar in the lower 160° of the pipe. This allows any entrained air to bleed back into the pipe for liquid applications and allows condensate to collect in the instrument piping for steam applications.
4.2.2 Vertical Piping
The Verabar may be mounted in any location around the circumference of the pipe for any vertical piping applications.
Figure 1. Verabar Orientation in Horizontal Pipe
4.3 DP Transmitter/Local Indicator Location
When choosing a Verabar location, consider the DP transmitter/local indicator location:
The transmitter must be mounted below the Verabar for liquid and steam applications.
The transmitter must be mounted above the Verabar for air and gas applications.
4.4 Installation Drawings and Bill of Materials
Additional information is available in the Installation Drawings and Bill of Materials VB-7061 (also on the VeraData CD). It contains standard and alternate transmitter locations and a complete bill of materials based on the fluid type and sensor orientation on the pipe.
5.0 INSTALLATION PROCEDURE

5.1 Drill Hole in Pipe

Completely depressurize and drain pipe prior to installation of the Verabar.
Mark the location of the hole through which the Verabar will be mounted. Use a center punch to mark the hole to prevent the drill bit from walking on the pipe.
Drill the pipe with the proper sized hole per the following table:
Sensor Size Hole Dia
V550-05 1/2" (13mm) V550-10 1” (25mm) V550-15 1-1/2” (38mm)

Deburr the hole on the inside of the pipe.

5.2 Weld Mounting Flange to Pipe

With the follower and packing rings already in
place (factory assembled), insert the sensor into the Spring-Lock body (Figure 3). Loosely bolt together (hand tight) the sensor, gasket and mounting flange. Insert the assembly until the tip of the sensor hits the opposite side of the pipe. Align the head of the sensor so that the arrow labeled “flow” on the head is in the direction of the flow to within 3°. The contour of the weld coupling should match the contour of the pipe. Check that the bottom of the weld coupling is in contact with the pipe wall.
Loading...
+ 2 hidden pages