Veris V400S Installation Instructions

Verabar V400S (Single Rod)
1.0 SCOPE
These instructions provide procedures for installing the V400 (Single Rod) Verabar flow sensor. Procedures are given for all industrial flow measurement applications including liquid, steam and gas service for both horizontal and vertical piping configurations.
2.0 RECEIVING INSPECTION
The following tasks should be performed as part of the receiving inspection procedure:
Check items received against the packing list.
Check sensor nameplate for proper model number,
serial number and customer number.
Verify that the actual pipe diameter matches the ID stated on the sensor nameplate.
Check the bullet shaped sensor tube for any signs of damage. Damage to the sensor tube may result in erroneous flow readings.
Check the round cover tube for any damage, especially axial gouges or scratches. Damage to the cover tube may prevent the packing from sealing properly.
3.0 SAFETY PRECAUTIONS
Prior to installation of the Verabar flow sensor, check maximum operating conditions on the flow sensor nameplate and verify that they exceed the maximum conditions of the installation. If any pressure, temperature or flow limits will be exceeded, consult the factory before proceeding.
INSTALLATION INSTRUCTIONS
4.0 INSTALLATION PREPARATIONS
4.1 Location
For the most accurate flow measurement, a minimum straight run of pipe is required. Table 1 shows the minimum straight run requirements. If longer straight runs are available, position the Verabar such that the ratio of upstream straight run to downstream straight run is approximately 4 to 1. If straight run lengths are less than the values stated in Table 1, consult the factory for additional accuracy and location information. For additional piping configurations, see Drawing SUB -4521.
Position straightening vanes such that the end closest to the Verabar is half way between the Verabar and the closest upstream configuration. For elbow installations, mount the Verabar in the same plane as the closest upstream elbow.
4.2 Orientation
Verify the proper sensor orientation by checking for an “­H” (horizontal piping) or a “-V” (vertical piping) in the model number on the Verabar name plate. Verify that the flow arrow stamped on the instrument head is pointing downstream in the direction of flow.
4.2.1 Horizontal Piping
For air or gas installations, mount the Verabar in the upper 160° of the pipe to allow any condensate to drain into the pipe (Figure 1). For liquid or steam installations, mount the Verabar in the lower 160° of the pipe. This allows any entrained air to bleed back into the pipe for liquid applications and allows condensate to collect in the instrument piping for steam applications.
Piping Configuration
Table 1. Straight Run Requirements
4.2.2 Vertical Piping
The Verabar may be mounted in any location around the circumference of the pipe for vertical piping applications (Figure 1).
Figure 1. Verabar Orientation in Horizontal Pipe
4.3 DP Transmitter/Local Indicator Location
When choosing a Verabar location, consider the DP transmitter/local indicator location:
The transmitter must be mounted below the Verabar for liquid and steam applications.
The transmitter must be mounted above the Verabar for air and gas applications.
4.4 Installation Drawings and Bill of Materials
Additional information is available in the Installation Drawings and Bill of Materials VB-7061 (also on the VeraData CD). It contains standard and alternate transmitter locations and a complete bill of materials based on the fluid type and sensor orientation on the pipe.
4.5 Piping Support
For sensors that extend more than 36” (915mm) beyond the pipe wall or for sensors mounted in thin-walled pipes, external support of the Verabar is recommended. This will reduc e stresses on the pipe wall.
5.0 INSTALLATION PROCEDURE
5.1 Assemble the Verabar
Your Verabar is shipped loosely assembled and is not properly tightened for proper pressure retention. Follow all assembly steps to ensure a safe installation (see Figure 2).
5.2 Install Instrument Valves or Manifold
5.2.1 Valves
If the Verabar does not have a valve head, install instrument valves using proper thread sealant. Be sure instrument shut-off valves are installed and shut prior to repressurizing the pipe.
5.2.2 Manifold
If the Verabar has a direct or integral manifold, be sure the high and low pressure block valves are shut off prior to repressurizing the pipe.
Figure 2. Verabar Model V400S (Single Rod)
Loading...
+ 2 hidden pages