Veris V400 Installation Instructions

REL AY S
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V400
V400
10A DPDT Enclosed Relay
Installer’s Specifications
Operating Temperature -34°C to 60°C (-29 ° to 140°F) Operating Humidity 10-90% non condensing Expected Relay Life Electrical (at rated current): 100,000 cycles Mechanical (unpowered): 10,000,000 cycles Relay Status LED ON=energized
Wire Specications:
Lead Length 14” (356mm) min. Gauge UL1015; Coil: 18AWG; Contacts: 16AWG Insulation Class 600VAC RMS Agency Approvals UL508 enclosed device listing, pollution degree 2
INSTALLATION
Disconnect and lock out all power sources before beginning the installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a knock out hole.
2. Secure with the conduit nut provided.
3. Connect coil:
• Choose the coil common lead (white with yellow stripe) and connect it to the common (-) source termination point.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
2.9"
(74 mm)
2.8"
(71 mm)
1.6"
(41 mm)
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or high voltage (208-277VAC, white with brown stripe) lead, depending on the application requirements, and connect it to the (+) source termination point.*
4. Connect relay contacts:
• Choose the relay common wire (yellow) and connect to the switched load.
• Choose the relay N.O. (orange) and/or* N.C. (blue) lead and connect to the
switched load.
• Repeat with violet, brown, and grey wires, respectively, for the second set of contacts
5. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e. wire nut.
1.7"
Z202856-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
1/2" NPT Nipple
(43 mm)
1.8"
(46 mm)
V400
*Contact ratings are for single pole operation. When operating both poles simultaneousley, the total load cannot exceed the ratings above.
Pull in Voltage AC DC
20-30V..................................... 18 20
208-277V................................. 186
Drop Out Voltage AC DC
20-30V..................................... 4 5
208-277V................................. 44
Voltage Coil Current AC DC
24V.......................................... 43mA 25mA
30V.......................................... 54mA 31mA
208V........................................ 27mA -
277V........................................ 36mA -
TYPICAL COIL PERFORMANCE
CONTACT RATINGS*
Resistive.............. 10A@277VAC, 30VDC
Motor.................... 120VAC, 1/8HP
N.C.
Common
20-30VAC/DC
LOW
wht/blue
COMM
wht/yellow
Common
N.O.
CONTACT OUTPUTCONTROL SYSTEM INPUT
White
YELLOW
White
ORANGE
b
l
ue
b
l
ue
y
e
ll
o
w
y
e
ll
o
w
N.C.
Common
N.O.
208-277VAC
HI
wht/brown
White
br
o
w
n
br
o
w
n
TM
INSTALLATION GUIDE
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
WIRING EXAMPLE
Nipple mount directly to a panel
To Load A
N.C.
N.O.
To Load B
COM
To Power
To Controls
Nipple mount to a 2x or 4x electrical box
To Load B
To Power
CONTROL
PANEL
COIL
To Load A
CONTACTS
L
I
O
C
N.C.
Wire Nuts
N.O.
COM
Z202856-0C PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04121