HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V300
V300
10A DPDT Enclosed Relay
Installer’s Specifications
Operating Temperature -34°C to 60°C (-29 ° to 140°F)
Operating Humidity 10-90% non condensing
Expected Relay Life Electrical (at rated current): 100,000 cycles
Mechanical (unpowered): 10,000,000 cycles
Relay Status LED ON=energized
Wire Specications:
Lead Length 14” (356mm) min.
Gauge UL1015; Coil: 18AWG; Contacts: 16AWG
Insulation Class 600VAC RMS
Agency Approvals UL508 enclosed device listing, pollution degree 2
INSTALLATION
Disconnect and lock out all power sources before beginning the
installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a
knock out hole.
2. Secure with the conduit nut provided.
3. Connect coil:
• Choose the coil common lead (white with yellow stripe) and connect it to
the common (-) source termination point.
• Choose either the low voltage (20-30VAC/DC, white with blue stripe) or
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
2.9"
(74 mm)
2.8"
(71 mm)
Z202855-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
1/2" NPT Nipple
1.7"
(43 mm)
1.6"
(41 mm)
1.8"
(46 mm)
4. Connect relay contacts:
5. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e.
wire nut.
high voltage (120VAC, white with black stripe) lead, depending on the
application requirements, and connect it to the (+) source termination
point.*
• Choose the relay common wire (yellow) and connect to the switched load.
• Choose the relay N.O. (orange) and/or* N.C. (blue) lead and connect to the
switched load.
V300
N.C.
Common
20-30VAC/DC
120VAC
HI
wht/black
LOW
wht/blue
COMM
wht/yellow
Common
N.O.
CONTACT OUTPUTCONTROL SYSTEM INPUT
White
YELLOW
White
White
ORANGE
b
l
a
c
k
b
l
a
c
k
b
l
ue
b
l
ue
y
e
ll
o
w
y
e
ll
o
w
bl
a
c
k
N.C.
Common
N.O.
*Contact ratings are for single pole operation. When
operating both poles simultaneousley, the total load
cannot exceed the ratings above.
Pull in Voltage AC DC
20-30V..................................... 18 20
120V........................................ 104
Drop Out Voltage AC DC
20-30V..................................... 4 5
120V........................................ 26
Voltage Coil Current
AC DC
24V.......................................... 43mA 25mA
30V.......................................... 54mA 31mA
120V........................................ 29mA -
TYPICAL COIL PERFORMANCE
CONTACT RATINGS*
Resistive.............. 10A@277VAC, 30VDC
Motor.................... 120VAC, 1/8HP
TM
INSTALLATION GUIDE
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
WIRING EXAMPLE
Nipple mount directly to a panel
To Load A
N.C.
N.O.
To Load B
COM
To Power
To Controls
Nipple mount to a 2x or 4x electrical box
To Load B
To Power
CONTROL
PANEL
COIL
To Load A
CONTACTS
L
I
O
C
N.C.
Wire
Nuts
N.O.
COM
To Control
* Isolate any unused wires, e.g. wire nut.