HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INsTallaTION GUIDe
V222
V222
20A SPST Enclosed Relay With
Resistive HOA Monitor
Installer’s Specifications
Operating Temperature -40° to 60°C (-40° to 131°F)
Operating Humidity 10-90% RH, non-condensing
Expected Relay Life Electrical (@ rated current) 100,000 cycles;
Mechanical (unpowered) 10,000,000 cycles
Relay Status LED ON=energized
Wire Specications:
Lead Length 14”(356mm) min.
Gauge UL1015; Coil: 18AWG; Contacts: 12AWG; HOA monitor wires: 16AWG
Insulation Class 277VAC RMS
Resistive Monitor Maximums:
Volt age Max. 13.4VAC/DC
Current Max. 4mA AC/DC
Agency Approvals UL 508 enclose d device listing, pollution degree 2
installation
Disconnect and lock out all power sources before beginning the
installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a
knock out hole.
2. Secure with the conduit nut provided.
3. Connect coil wires:
• Choose the coil common lead (white with yellow stripe) and connect it to
the common (-) source termination point.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Dimensions
(103 mm)
3.8"
(97 mm)
Z203431-0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
3/4" NPT Nipple
2.3"
(59 mm)
2.0"
(52 mm)
2.5"
(64 mm)
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or
high voltage (208-277VAC, white with brown stripe) lead, depending
on the application requirements, and connect it to the (+) source
termination point.*
Note: When connecting the control side of this device (#18 wires) to power
line circuits, provide currenting limiting at 7 amps max.
4. Connect relay contacts:
• Choose the two solid orange wires (N.O. contact) and connec t to the
switched load.
5. Connect resistive HOA monitor wires:
• Choose the two solid grey wires and connect them to a resistive (0-10kΩ)
input in the control system.
6. Secure the enclosure and reconnect power.
7. Program the resistive input to the ranges listed.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e.
wire nut.
V222
208-277VAC
24VAC/DC
Common
To Load
To Controls
COIL
CONTACTS
To Load
To Controls
Wire
Nut
C
O
I
L
CONTACTS
HAND
OFF
AUTO
Up position: contacts are closed.
Middle position: contacts are open.
Down position: control system actuates the contacts.
Coil Voltage 24VAC/DC, 208-277VAC
Voltage Coil Current
AC DC
24V.................... 75mA 32mA
208V.................. 36mA –
277V.................. 49mA –
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive..... 20A(r)@240VAC
8A@28VDC
14A@14VDC
Motor......... 250VAC, 1HP N.O. & N.C.
TM
INsTallaTION GUIDe
Wiring Color CoDes
Resistive HOA Position Monitor
Wiring example
Nipple mount directly to a panel Nipple mount to a 2x or 4x electri-
cal box
Hoa positions
ContaCt anD Coil speCifiCations
programming tHe resistive
monitor
The resistive monitor is a 0-10 kΩ analog output for monitoring the HOA switch
position. Please use the following ranges for the DDC scaling.
Condition Range (Ω)* Nominal Values without Wire
Resistance (Ω)*
Line Open Greater than 8630 n/a
HOA O 5290 to 8630 6190
Z203431-0B PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
HOA Auto 2880 to 5289 3391
HOA On 1200 to 2879 1406
Line Shorted Less than 1200 n/a
* Ranges based on the presence of 0 -1000Ω of resistance due to wire. Average # of feet for 1000Ω
by wire AWG listed below.
Wire Type (AWG)
26 12,189
22 30,864
18 78,296
† All 2-wire runs
†
Distance Allowed (ft.)