Veris V221 Installation Instructions

Rel ays
4.0"
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INsTallaTION GUIDe
V2 21
V2 21
20A SPST Enclosed Relay With HOA Switch
Installer’s Specifications
Operating Temperature -40° to 60°C (-40° to 131°F) Operating Humidity 10-90% RH, non-condensing Expected Relay Life Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles Relay Status LED ON=energized
Wire Specications:
installation
Disconnect and lock out all power sources before beginning the installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a knock out hole.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Dimensions
(103 mm)
3.8"
(97 mm)
2.0"
(52 mm)
2. Secure with the conduit nut provided.
3. Connect coil wires:
• Choose the coil common lead (white with yellow stripe) and connect it to the common (-) source termination point.
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or high voltage (208-277VAC, white with brown stripe) lead, depending on the application requirements, and connect it to the (+) source termination point.*
Note: When connecting the control side of this device (#18 wires) to power line circuits, provide currenting limiting at 7 amps max.
4. Connect relay contacts:
• Choose the two solid orange wires (N.O. contact) and connect to the switched load.
5. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e. wire nut.
Z203430-0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
3/4" NPT Nipple
2.3"
(59 mm)
2.5"
(64 mm)
V221
To Load
To Controls
COIL
CONTACTS
To Load
To Controls
Wire Nut
C
O
I
L
CONTACTS
HAND
OFF
AUTO
Up position: contacts are closed.
Middle position: contacts are open.
Down position: control system actuates the contacts.
Voltage Coil Current AC DC
24V.................... 75mA.................... 32mA
208V.................... 36mA
277V.................... 49mA
Resistive..... 20A@240VAC
8A@28VDC 14A@14VDC
Motor......... 120VAC, 1HP N.O. & N.C.
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Coil Voltage 24VAC/DC, 208-277VAC
TM
INsTallaTION GUIDe
Wiring Color CoDes
208-277VAC
24VAC/DC
Common
ContaCt anD Coil sPeCifiCations
Wiring examPle
Nipple mount directly to a panel
Nipple mount to a 2x or 4x electrical box
Hoa Positions
Z203430-0B PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04122