HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V203
V203
10A SPDT Enclosed Relay With
Digital HOA Monitor
Installer’s Specifications
Operating Temperature -40° to 55°C (-40 ° to 131°F)
Operating Humidity 10-90% RH, non-condensing
Expected Relay Life Electrical (@ rated current) 100,000 cycles;
Mechanical (unpowered) 10,000,000 cycles
Relay Status LED ON=energized
Wire Specications:
Lead Length 14” (356mm) min.
Gauge UL1015; Coil: 18AWG; Contacts: 16AWG; HOA monitor wires: 16AWG
Insulation Class 600VAC RMS
Digital Monitor Maximum:
Dry Circuit Contact Rating (Max.) 24VAC/DC@100mA
Agency Approvals UL508 enclosed device listing, pollution degree 2
INSTALLATION
Disconnect and lock out all power sources before beginning the
installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a
knock out hole.
2. Secure with the conduit nut provided.
3. Connect coil wires:
• Choose the coil common lead (white with yellow stripe) and connect it to
the common (-) source termination point.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
(103 mm)
3.8"
(97 mm)
2.0"
(52 mm)
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or
high voltage (208-277VAC, white with brown stripe) lead, depending
on the application requirements, and connect it to the (+) source
termination point.*
NOTE: When connecting the control side of this device (#18 wires) to power
line circuits, provide current limiting at 7 amps max.
4. Connect relay contacts:
• Choose the two solid orange wires (N.O. contact) and connect to the
switched load.
5. Connect digital HOA monitor wires:
• Choose the solid brown and solid grey wires and connec t them to two
dierent digital inputs, referencing the violet wire as common.
6. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e.
wire nut.
Z203396-0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
3/4" NPT Nipple
2.3"
(59 mm)
2.5"
(64 mm)
V203
To Load
To Controls
COIL
CONTACTS
To Load
To Controls
Wire
Nut
C
O
I
L
CONTACTS
Pull in Voltage AC DC
10-30V..................................... 8 9
207-277V................................. 154
Drop Out Voltage AC DC
10-30V..................................... 2 3
208-277V................................. 36
Voltage Coil Current
AC DC
10V.......................................... 25mA 14mA
24V.......................................... 31mA 16mA
30V.......................................... 39mA 18mA
208V........................................ 19mA -
277V........................................ 25mA -
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive.............. 10A@277VAC
Motor.................... 1/3HP@120VAC
Gold Flash............. Yes
HAND
OFF
AUTO
Up position: contacts are closed.
Middle position: contacts are open.
Down position: control system actuates the contacts.
TM
INSTALLATION GUIDE
WIRING COLOR CODES
Digital HOA Position Monitor
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to a 2x or 4x electrical box
CONTACT AND COIL SPECIFICATIONS
HOA POSITIONS
Z203396-0B PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04121