REL AYS
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V200
V200
10A SPDT Enclosed Relay
10-30 VDC/AC or 208-277 VAC Coil
Installer’s Specifications
Operating Temperature -34°C to 60°C (-29 ° to 140°F)
Operating Humidity 10-90% non condensing
Expected Relay Life Electrical (at rated current): 100,000 cycles
Mechanical (unpowered): 10,000,000 cycles
Relay Status LED ON=energized
Wire Specications:
Lead Length 14” (356mm) min.
Gauge UL1015; Coil: 18AWG; Contacts: 16AWG
Insulation Class 600VAC RMS
Agency Approvals UL508 enclosed device listing
INSTALLATION
Disconnect and lock out all power sources before beginning the
installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a
knock out hole.
2. Secure with the conduit nut provided.
3. Connect Coil:
• Choose the coil common lead (white with yellow stripe) and connect it to
the (-) source termination point.
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
2.9"
(74 mm)
2.8"
(71 mm)
1.6"
(41 mm)
4. Connect Relay Contacts:
5. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e.
wire nut.
high voltage (208-277VAC, white with brown stripe) lead, depending
on the application requirements, and connect it to the (+) source
termination point.*
• Choose the relay common wire (yellow) and connect to switched load.
• Choose the relay N.O. (orange) and/or* N.C. (blue) lead and connect to
switched load.
1.7"
Z202853-0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 02122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
1/2" NPT Nipple
(43 mm)
1.8"
(46 mm)
V200
To Load
To Controls
COIL
CONTACTS
To Load
To Controls
Wire
Nut
C
O
I
L
CONTACTS
Pull in Voltage AC DC
10-30V..................................... 8 9
208-277V................................. 154
Drop Out Voltage AC DC
10-30V..................................... 2 3
208-277V................................. 36
Voltage Coil Current
AC DC
10V.......................................... 25mA 14mA
12V.......................................... 25mA 14mA
24V.......................................... 31mA 16mA
30V.......................................... 39mA 18mA
208V........................................ 19mA -
277V........................................ 25mA -
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive.............. 10A@277VAC, 28VDC
Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.
240VAC, 1/3HP N.O. & 1/6HP N.C.
277VAC, 1/4HP N.O. & 1/8HP N.C.
Pilot Duty............. 277VAC, (1.7A), 480VA N.O.
Ballast.................. 277VAC, 1.7A
Tungsten............... 120VAC, TV3 N.O. TV2 N.C.
Gold Flash............. Yes
TM
INSTALLATION GUIDE
WIRING COLOR CODES
CONTACT OUTPUTCONTROL SYSTEM INPUT
wht/brown
LOW
wht/blue
COMM
wht/yellow
HI
br
o
208-277VAC
b
y
e
ll
w
White
n
l
ue
White
10-30VAC/DC
o
White
w
Common
br
o
w
n
N.C.
b
l
ue
YELLOW
Common
y
e
ll
o
w
ORANGE
N.O.
CONTACT AND COIL SPECIFICATIONS
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to any 2x or 4x electrical box
Z202853-0B PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 02122