Veris V123 Installation Instructions

REL AY S
4.0"
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V123
V123
20A SPST Enclosed Relay With
Digital HOA Monitor
Installer’s Specifications
Wire Specications:
Lead Length 14”(356mm) min. Gauge UL1015; Coil: 18AWG; Contacts: 12AWG; HOA monitoring wires: 16AWG Insulation Class 277VAC RMS
Digital Monitor Maximums:
Dry Circuit Contact R ating (Max.) 24VAC/DC@100mA Agency Approvals UL 508 enclose d device listing, pollution degree 2
INSTALLATION
Disconnect and lock out all power sources before beginning the installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a knock out hole.
2. Secure with the conduit nut provided.
3. Connect coil wires:
• Choose the coil common lead (white with yellow stripe) and connect it to the common (-) source termination point.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
(103 mm)
3.8"
(97 mm)
Z203403-0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04123
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
3/4" NPT Nipple
2.3"
(59 mm)
2.0"
(52 mm)
2.5"
(64 mm)
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or high voltage (120VAC, white with black stripe) lead, depending on the application requirements, and connect it to the (+) source termination point.*
Note: When connecting the control side of this device (#18 wires) to power line circuits, provide currenting limiting at 7 amps max.
4. Connect relay contacts:
• Choose the relay common wire (yellow) and connect to the switched load.
• Choose the relay N.O. (orange) and/or* N.C. (blue) lead and connect to the
switched load.
5. Connect digital HOA monitor wires:
• Choose the solid brown and solid grey wires and connect them to two dierent digital inputs, referencing the violet wire as common.
6. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e. wire nut.
V123
24VAC/DC
120VAC
LOW
wht/blue
COMM
wht/yellow
HI
wht/black
CONTACT OUTPUTCONTROL SYSTEM INPUT
Common
To Load
To Controls
COIL
CONTACTS
To Load
To Controls
Wire Nut
C
O
I
L
CONTACTS
HAND
OFF
AUTO
Up position: contacts are closed.
Middle position: contacts are open.
Down position: control system actuates the contacts.
Coil Voltage 24VAC/DC, 120VAC
Voltage Coil Current AC DC
24V.................... 75mA.................... 32mA
120V.................... 22mA
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive..... 20A(r)@240VAC
8A@28VDC 14A@14VDC
Motor......... 250VAC, 1HP N.O. & N.C.
TM
INSTALLATION GUIDE
WIRING COLOR CODES
Digital HOA Position Monitor
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to a 2x or 4x electrical box
CONTACT AND COIL SPECIFICATIONS
Z203403-0B PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04123
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
HOA POSITIONS