RELAYS
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V120
V120
20A SPDT Enclosed Relay
Installer’s Specifications
Operating Temperature -34°C to 55°C (-29° to 131°F)
Operating Humidity 10-90% non condensing
Expected Relay Life Electrical (at rated current): 100,000 cycles
Mechanical (unpowered): 10,000,000 cycles
Relay Status LED ON=energized
Wire Specications:
Lead Length 14” (356mm) min.
Gauge UL1015; Coil: 18 AWG; Contacts: 12 AWG
Insulation Class 600 VAC RMS
Agency Approvals UL508 enclosed dev ice listing, pollution degree 2
INSTALLATION
Disconnect and lock out all power sources before beginning the
installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a
knock out hole.
2. Secure with the conduit nut provided.
3. Connect coil wires:
• Choose the coil common lead (white with yellow stripe) and connect it to
the (-) source termination point.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
(74 mm)
2.8"
(71 mm)
1.6"
(41 mm)
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or
high voltage (120VAC, white with black stripe) lead, depending on the
application requirements, and connect it to the (+) source termination
point.*
4. Connect relay contacts:
• Choose the relay common wire (yellow) and connect to the switched load.
• Choose the relay N.O. (orange) and/or* N.C. (blue) lead and connect to the
switched load.
5. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e.
wire nut.
Z203094-0D PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
1/2" NPT Nipple
1.7"
(43 mm)
1.8"
(46 mm)
V120
To Load
To Controls
COIL
CONTACTS
Voltage Coil Current
AC DC
24V.......................................... 75mA 32mA
120V........................................ 42mA -
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive.............. 20A@277VAC, 28VDC
Motor.................... 120VAC, 1HP
277VAC, 2HP
Pilot Duty............. A300
Ballast.................. 277VAC, 20A N.O.
277VAC, 10A N.C.
Tungsten............... 120VAC, 10A N.O.
120VAC, 2A N.C.
N.C.
Common
24VAC/DC
120VAC
HI
wht/black
LOW
wht/blue
COMM
wht/yellow
Common
N.O.
CONTACT OUTPUTCONTROL SYSTEM INPUT
White
YELLOW
White
White
ORANGE
b
l
a
c
k
b
l
a
c
k
b
l
ue
b
l
ue
y
e
ll
o
w
y
e
ll
o
w
bl
a
c
k
TM
INSTALLATION GUIDE
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to 4x electrical box
POWER
SOURCE
To Controls
Fractional
HP Motor
Z203094-0D PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.