Veris V101 Installation Instructions

REL AYS
4.0"
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V10 1
V10 1
10A SPST Enclosed Relay With HOA Switch
Installer’s Specifications
Operating Temperature -40° to 55°C (-40 ° to 131°F) Operating Humidity 10-90% RH, non-condensing Expected Relay Life Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles Relay Status LED ON=energized
Wire Specications:
Lead Length 14” (356mm) min. Gauge UL1015; Coil: 18AWG; Contacts: 16AWG Insulation Class 600VAC RMS Agency Approvals UL508 enclosed device listing, pollution degree 2
INSTALLATION
Disconnect and lock out all power sources before beginning the installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a knock out hole.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
(103 mm)
3.8"
(97 mm)
2.0"
(52 mm)
2. Secure with the conduit nut provided.
3. Connect coil wires:
• Choose the coil common lead (white with yellow stripe) and connect it to the common (-) source termination point.
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or high voltage (120VAC, white with black stripe) lead, depending on the application requirements, and connect it to the (+) source termination point.*
NOTE: When connecting the control side of this device (#18 wires) to power line circuits, provide current limiting at 7 amps max.
4. Connect relay contacts:
• Choose the two orange wires (N.O. contact) and connect to the switched load.
5. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e. wire nut.
Z203391-0D PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
3/4" NPT Nipple
2.3"
(59 mm)
2.5"
(64 mm)
V10 1
To Load
To Controls
COIL
CONTACTS
To Load
To Controls
Wire Nut
C
O
I
L
CONTACTS
Pull in Voltage AC DC
10-30V..................................... 8 9
120V........................................ 78
Drop Out Voltage AC DC
10-30V..................................... 2 3
120V........................................ 18
Voltage Coil Current AC DC
10V.......................................... 25mA 14mA
24V.......................................... 31mA 16mA
30V.......................................... 39mA 18mA
120V........................................ 22mA -
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive.............. 10A@250VAC
Motor.................... 1/3HP@120VAC
Gold Flash............. Yes
HAND
OFF
AUTO
Up position: contacts are closed.
Middle position: contacts are open.
Down position: control system actuates the contacts.
TM
INSTALLATION GUIDE
WIRING COLOR CODES
CONTACT OUTPUTCONTROL SYSTEM INPUT
HI
wht/black
LOW
wht/blue
COMM
wht/yellow
120VAC
10-30VAC/DC
Common
CONTACT AND COIL SPECIFICATIONS
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to a 2x or 4x electrical box
HOA POSITIONS
Z203391-0D PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.