Veris V100DC Installation Instructions

REL AYS
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V10 0D C
V10 0D C
10A SPDT Enclosed Relay
10-30 VDC Coil
Installer’s Specifications
Wire Specications:
Lead Length 14” (356mm) min. Gauge UL1015; Coil: 18 AWG; Contacts: 16 AWG Insulation Class 600 VAC RMS Agency Approvals UL508 enclosed device listing
INSTALLATION
Disconnect and lock out all power sources before beginning the installation.
1. Using the threaded nipple, connect the relay to the desired enclosure through a knock out hole.
2. Secure with the conduit nut provided.
3. Connect Coil:
• Choose the coil common lead (white with yellow stripe) and connect it to the (-) source termination point.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
2.9"
(74 mm)
2.8"
(71 mm)
1.6"
(41 mm)
• Choose the low voltage (10-30 VAC/DC, white with blue stripe) lead, and connect it to the (+) source termination point.*
4. Connect Relay Contacts:
• Choose the relay common wire (yellow) and connect to switched load.
• Choose the relay N.O. (orange) and/or* N.C. (blue) lead and connect to
switched load.
5. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e. wire nut.
1.7"
Z203521-0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 03121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
1/2" NPT Nipple
(43 mm)
1.8"
(46 mm)
V10 0DC
To Load
To Controls
COIL
CONTACTS
To Load
To Controls
Wire Nut
C
O
I
L
CONTACTS
Pull in Voltage DC
10-30V..................................... 9
Drop Out Voltage DC
10-30V..................................... 3
Voltage Coil Current DC
10V.......................................... 14mA
12V.......................................... 14mA
24V.......................................... 16mA
30V.......................................... 18mA
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive.............. 10A@277VAC, 28VDC
Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.
240VAC, 1/3HP N.O. & 1/6HP N.C. 277VAC, 1/4HP N.O. & 1/8HP N.C.
Pilot Duty............. 277VAC, (1.7A), 480VA N.O.
Ballast.................. 277VAC, 1.7A
Tungsten............... 120VAC, TV3 N.O. TV2 N.C.
Gold Flash............. Yes
TM
INSTALLATION GUIDE
WIRING COLOR CODES
CONTACT OUTPUTCONTROL SYSTEM INPUT
LOW
wht/blue
COMM
wht/yellow
b
y
e
ll
l
ue
White
10-30VDC
o
White
w
Common
b
l
ue
N.C.
YELLOW
Common
y
e
ll
o
w
ORANGE
N.O.
CONTACT AND COIL SPECIFICATIONS
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to any 2x or 4x electrical box
Z203521-0B PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 03121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Loading...