REL AYS
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
DANGER
TM
INSTALLATION GUIDE
V10 0D
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
V10 0D
Dual 10A SPDT Enclosed Relays
10-30 VDC/AC or 120 VAC Coil
Installer’s Specifications
Operating Temperature -40°C to 55°C (- 40° to 131°F)
Operating Humidity 10-90% non condensing
Expected Relay Life Electrical (at rated cur rent): 10 0,000 cycles
Mechanical (unpowered): 10,000,000 cycles
Relay Status LED ON=energized
Wire Specications:
Lead Length 14” (356mm) min.
Gauge UL1015; Coil: 18 AWG; Contacts: 16 AWG
Insulation Class 600 VAC RMS
Agency Approvals UL508 enclosed device listing
INSTALLATION
Disconnect and lock out all power sources before beginning the
installation.
1. Using the threaded nipple connect the relay to the desired enclosure through a
knock out hole.
2. Secure with the conduit nut provided.
Relay #1
3. Connect Coil:
• Choose the coil common lead (white with yellow stripe) and connect it to
the (-) source termination point.
• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or
high voltage (120VAC, white with black stripe) lead, depending on the
application requirements, and connect it to the (+) source termination
point.*
NOTE: When connecting the control side of this device (#18 wires) to power
line circuits, provide current limiting at 7 amps max.
4. Connect Relay Contacts:
• Choose the relay common wire (yellow) and connect to switched load.
DIMENSIONS
4.0"
(103 mm)
3.8"
(97 mm)
2.0"
(52 mm)
2.3"
Z203399-0C PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 02122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
3/4" NPT Nipple
(59 mm)
2.5"
(64 mm)
Relay #2
5. Connect Coil:
• Choose the coil common lead (white with violet stripe) and connect it to
the (-) source termination point.
• Choose either the low voltage (10-30VAC/DC, grey with white stripe)
or high voltage (120VAC, white with red stripe) lead, depending on the
application requirements, and connect it to the (+) source termination
point.*
NOTE: When connecting the control side of this device (#18 wires) to power
line circuits, provide current limiting at 7 amps max.
6. Connect Relay Contacts:
• Choose the relay common wire (violet) and connect to switched load.
• Choose the relay N.O. (brown) and/or* N.C. (grey) lead and connect to
switched load.
7. Secure the enclosure and reconnect power.
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e.
wire nut.
V10 0 D
To Load
To Controls
COIL
CONTACTS
To Load
To Controls
Wire
Nut
C
O
I
L
CONTACTS
Pull in Voltage AC DC
10-30V..................................... 8 9
120V........................................ 78
Drop Out Voltage AC DC
10-30V..................................... 2 3
120V........................................ 18
Voltage Coil Current
AC DC
10V.......................................... 25mA 14mA
12V.......................................... 25mA 14mA
24V.......................................... 31mA 16mA
30V.......................................... 39mA 18mA
120V........................................ 22mA -
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive.............. 10A@277VAC, 28VDC
Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.
240VAC, 1/3HP N.O. & 1/6HP N.C.
277VAC, 1/4HP N.O. & 1/8HP N.C.
Pilot Duty............. 277VAC, (1.7A), 480VA N.O.
Ballast.................. 277VAC, 1.7A
Tungsten............... 120VAC, TV3 N.O. TV2 N.C.
Gold Flash............. Yes
RELAY 2
RELAY 1
Relay 2
Relay 1
TM
INSTALLATION GUIDE
WIRING COLOR CODES
Relay 1
b
l
a
HI
wht/black
b
LOW
wht/blue
y
COMM
wht/yellow
e
ll
CONTROL SYSTEM INPUT
HI
wht/red
LOW
grey/wht
c
White
k
120VAC
l
ue
White
10-30VAC/DC
o
White
w
Common
120VAC
10-30VAC/DC
b
bl
l
a
a
c
c
k
k
b
l
ue
y
e
ll
o
w
Relay 2
WIRING EXAMPLE
Nipple mount directly to a panel
CONTACT OUTPUTCONTROL SYSTEM INPUT
N.C.
YELLOW
Common
ORANGE
N.O.
Nipple mount to any 2x or 4x electrical box
CONTACT OUTPUT
N.C.
Common
COMM
wht/violet
COMMON
CONTACT AND COIL SPECIFICATIONS
N.O.
LED CONFIGURATION
Z203399-0C PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 02122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.