TWS SERIES
Wall Mount Temperature
Transmier with
Thermostat Functions
Independent Heat/Cool Or
VERIS INDUSTRIES
Analog Setpoint Outputs
DESCRIPTION
All TWS Series institutional grade temperature transmitters are eld-programmable
and are designed to satisfy the demanding requirements of pharmaceutical labs,
hospitals, science labs, and other exacting applications. Internal jumpers control
access to a feature which allows eld adjustment of calibration osets. Tampering
can be prevented by setting a jumper to disable keypad program functions.
Analog Output
Analog output models feature a keypad to make adjusting temperature setpoint
values easy. They are unique in reporting the setpoint values back to a control system
by means of 4-20mA or 0-5/0-10VDC (output selected by slide-switch) signals.
Setpoint Relay
The TWS Series setpoint relay models measure temperature and oer thermostat
functionality. Two separate relays can be congured to control heat/cool in
thermostat mode.
setpoint devices
APPLICATIONS
● Hospitals and operating rooms, pharmaceutical labs
● Clean rooms
● Food processing plants
● Environmental testing facilities, and other institutional applications
TWS
FEATURES
● Independent heat/cool (TWS relay) or analog setpoint outputs (TWS analog)
provide application exibility
● LCD for local display of readings and setup values...easy visibility under any
lighting conditions
● Oset function adjusts calibration osets for temperature
● Switch selectable 4-20mA or 0-5/0-10VDC analog outputs
● Semiconductor temperature sensor can be eld calibrated
Year
5
SPECIFICATIONS
Input Power 15-30VDC/24VAC, 100mA max.
Outputs, Analog Switch-sele ctable 4-20mA (clipped and cap ped)/0-10V/0-5VDC (switch aect s all outputs)
Outputs, Relay (Relay models only) 2 Form C (SPDT), 1A 30VDC, resistive, 30W ma x.
Temperature:
Accuracy ±0. 5° C (±1° F)
Scaling 10° to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F), menu selectable
Calibration Oset Adjustable ±10° in 0.1° (C or F) increments
Setpoint Range Minimum to Full Scale in 1° (C or F) increment s
Hysteresis (Deadband) 1° to 10°F in 1°F increments
Physical UL 94-V-O re retardant ABS
800.354.8556
Warranty
+1 503.598.4564
www.veris.com
HQ0001873.B 01131
800.354.8556
POWER SOURCE
15 to 30VDC or 24 VAC
DIGITAL CONTROL
Temp IN
Temp Setpoint IN
Temp IN
-
-
-
+
GND
Temp Setpoint OUT
Temp Tr ansmitter OUT
RTD/Thermistor
RTD/Thermistor
RH
SENSOR
TEMP
SENSOR
AMP VOLT
YES
RUN
CAL
NO
TEMP
–
Minus PlusEnter
+
+1 503.598.4564
www.veris.com
APPLICATION/WIRING DIAGRAMS
Analog Models
Relay Models
Temp
Transmitter
OUT
Thermistor/
RTD
POWER SOURCE
15 to 30VDC or 24VAC
DIGITAL CONTROL
Temp IN
Thermistor/RTD
Thermistor/RTD
Heat alarm
COMM alarm
Cool alarm
+
GND
-
-
-
Heat alarm
COMM alarm
Cool alarm
CONFIGURATION
DIMENSIONAL DRAWING
Enter
-+
3.5"
(89 mm)
4.75"
(121 mm)
1.2"
(29 mm)
setpoint devices
ORDERING INFORMATION
TWS R S 1 C
TWS models include standard temperature transmitter
outputs. Optional RTDs and thermistors are available as
shown for TWSA models.
HQ0001873.B 01131
TWS
Setpoint
A = Analog
R = Relay
Exam ple:
S
= CE
(standard)
Cal Certificate
0 = None
1 = 1 point Cal Vali dation
2 = 2 point Cal Vali dation
Option
Blank = None
B = 100R Platinu m, RTD
C = 1k Platinum, RTD
D = 10k T2, Therm istor
E = 2.2k, Thermist or
F = 3k, Therm istor
G = 10k CPC, Th ermistor
H = 10k T3, Thermi stor
J = 10k Dale, Ther mistor
K = 10k w/11k shunt,Thermis tor
M = 20k NTC, Ther mistor
N = 1800 ohm TAC, Therm istor
Q = 1uA/C, Linitemp
R = 10k US, The rmistor
S = 10k 3A 221, Thermisto r
T = 100k, The rmistor
U = 20k “D”, Thermis tor
W = 10k T2 high acc uracy, Thermist or
Y = 10k T3 high acc uracy, Thermist or
Z = 10k E1, Thermisto r
ACCESSORIES
Replacement cover (AA53)
Replacement housing (AA55)
AA53 AA55