Installation Guide
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
DANGER
Current Monitoring
Product Overview
The H808 is a current-sensitive switching device that monitors current (amperage) in the conductor passing
through it. A change in amperage in the monitored conducter that crosses the switch threshold plus the hysteresis
value will cause the resistance of the status output to change state, similar to the action of a mechanical switch.
The setpoint is adjustable through the action of a 20-turn potentiometer (see Calibration section). The status
RoHS
Compliant
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
output is suitable for connection to building controllers or other appropriate data acquisition equipment operating
at up to 30 volts. The H808 requires no external power supply to generate its output.
Specifications
TM
H808
Solid-Core Current Switch, Adjustable Trip Point
Sensor Power
Amperage Range
Status Output Ratings
Insulation Class
Setpoint
Frequency Range
Temperature Range
Humidity Range
Hysteresis
Off State Resistance
On State Resistance
Terminal Block Wire Size
Terminal Block Torque
Agency Approvals
Installation Category
Induced from the monitored conductor
0.75 to 50 A continuous*
N.O. 1.0 A@ 30 VAC/DC, not polarit y sensitive
600 VAC RMS (UL); 30 0 VAC (CE )
Adjustable, 0.75 A or less
50 /60 Hz
-15° to 60°C ( 5° to 140°F)
10-9 0% RH non-condensing
10% t ypic al
Open switch represents >1 MΩ
Closed switch represents < 200 mΩ
24 to 14 AWG (0.2 to 2.1 mm2)
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
COMPLIANCE INFORMATION
UL508 open divice listing, CE: EN61010 -1
Cat. III, pollution degree 2
TM
Z201763-0F Page 1 of 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010-1:2010
The product design provides basic insulation only.
Do not use the LED indicators as evidence of applied voltage.
* When operating at 50 Hz, low threshold may be 0.9 A.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide
Current Monitoring
H808
TM
Dimensions
Installation
Removable/Adjustable Mounting Bracket
0.9"
(23 mm)
2.8"
(71 mm)
1.1"
(27 mm)
0.4” x 0.2”
Slot (x2)
0.7"
(18 mm)
1.7
(43 mm)
2.3"
(58 mm)
Disconnect and lock out power to the enclosure containing the conductor to be
monitored.
1. Locate a mounting surface for the removable mounting bracket
that will allow the monitored conduc tor to pass through the center
window when it is installed and that will keep the device at least ½”
(13 mm) from any uninsulated conductors. Determine cable routing
for the controller connection, allowing wiring to reach the mounting
location.
CONTACTOR
Insulated Conductor Only
DDC CONTROLLER
2. Drill holes to mount the bracket to the chosen surface using the
included screws.
3. Wire the output connections and relay between the sensor and the
controller (solid-state contact).
4. Route the conductor through the sensor’s center window and slip the
assembly into the mounting bracket.
5. Secure the enclosure and reconnect power.
6. Calibrate the sensor with the load running normally.
DI
Fan or Pump
Motor
Z201763-0F Page 2 of 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide
Current Monitoring
H808
TM
Notes
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) current transformer (CT) as shown. This technique can be combined with wrapping (see below) to add
range for a low current load on a high current source.
> 50 A (Sensor max.)
240A
DANGER: 5A CTs can present
hazardous voltages. Install
CTs in accordance with
4A
300A:5A
H68xx-5A CT
manufacturer's instructions.
Terminate the CT secondary
before applying current.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases
the current measured by the transducer. Program the controller to account for the extra turns (e.g., if four turns pass through the
sensor (as shown) divide the normal reading by 4).
< 0.75 A (Sensor Min.)
0.5A
4x
CAUTION
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
RISK OF EQUIPMENT DAMAGE
Z201763-0F Page 3 of 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide
Current Monitoring
H808
TM
Calibration
Before beginning calibration, establish normal load conditions. Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
Status
1. Turn setpoint screw clockwise
until Status Open LED turns
on.
2. Slowly turn the screw counter
clockwise until the Status
Closed LED turns on.
Closed
Status
Open
Status
Closed
Status
Open
Setpoint
Setpoint
3. Turn the screw an additional
¼ turn counter clockwise for
operational margin.
Setpoint
¼
B. To monitor over-current (mechanical problems, seized impeller)
Status
1. Turn setpoint screw counter
clockwise until Status Closed
LED turns on.
Closed
Status
Open
Setpoint
Troubleshooting
Status
2. Slowly turn the setpoint screw
clockwise until the Status
Open LED just turns on.
Closed
Status
Open
Setpoint
3. Turn the setpoint screw an
additional ¼ turn clockwise
for operational margin.
Setpoint
¼
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control power at sensor (<30VDC)
• Check for amperage in monitored conductor (>0.75A)
Setpoint screw has no stops • The setpoint screw has a slip-clutch at both ends of its travel to avoid damage. Twenty turns CCW will reset
Both LEDs are lit Unit is out of calibration. Turn screw 20 turns CCW and recalibrate.
the sensor to be most sensitive. Repeat calibration above.
Z201763-0F Page 4 of 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07131