H804x & H805x SERIES
Enercept® kW/kWh Transducers
(4-20mA or Pulse Output)
VERIS INDUSTRIES
Integral Submetering Solution
Eliminates the Need for
Separate Enclosures
DESCRIPTION
The Enercept H804x and H805x Series kW (real power)/kWh (consumption)
transducers combine processing electronics and industrial grade CTs in an easy-toinstall split-core package. These devices continuously measure voltage and current
values for the monitored conductors and update calculations to provide highly
accurate true RMS power readings. Models designed for balanced loads include one
CT only, while models for unbalanced loads have three CTs.
The unique design of the H804x/H805x Series transducers reduces the number
of installed components, making them ideal for monitoring electrical power in
commercial and industrial facilities The H804x provides industry-standard 4-20mA
output, and the H805x provides a pulse output.
power/energy monitoring
Installation is simple. The H804x/H805x eliminates the need to mount and wire a
transducer and enclosure. CTs and voltage leads are color-matched, and the meters
are designed to detect and automatically compensate for phase reversal. No more
worries about CT load orientation.
APPLICATIONS
● Optimize chillers, pumps & cooling towers
● Energy management & performance contracting
● Control processes
● Activity-based costing in commercial and industrial facilities
● Monitor real-time power
● Load shedding
H804x/H805x
Pat ent #6,373 ,238
FEATURES
● Revenue Grade measurements
● Fast split-core installation eliminates the need to remove conductors...
perfect for retrots
● Precision meter electronics and current transformers in a single package...
reduces the number of installed components...creating signicant labor savings
● Smart electronics eliminate the need to be concerned with CT orientation...
fast trouble-free installation
Year
SPECIFICATIONS
Inputs:
Voltage Input 208/240 or 480VAC, 50/60 Hz RMS ¹ ² ³
Current Input Up to 2400A continuous per phase ² ³
Accuracy:
System Accuracy ±1% of reading from 10% to 100% of the rated c urrent of the CTs, accomplished by matc hing the CTs with electronics and calibrating them as a system
Outputs:
H804x
Output 4-2 0mA
Supply Power (current loop) 9-30VDC, 30mA max.
H805x
Pulsed Output Field selectable; 1, 0.5, 0.25, 0.1kWh/pulse
Pulsed Output Type Normally Open, Opto-FET, 100mA@24VDC
Environmental:
Operating Temperature Range 0° to 60°C (32° F to 140°F), 50°C (122°F) for 2400A
Humidity Range 0 - 95% noncondensing
Agency Approvals UL508
¹ Do not install on the line or load side of a VFD unit, or on any other equipment generating harmonics. For line side applications, use the E5x Series meters.
² Contact factory to interface with voltages above 480VAC or current above 2400 Amps.
³ Do not apply 600V Class current transformers to circuits having a phase-to-phase voltage greater than 600V, unless adequate additional insulation is applied between the primary conductor and the current transformers.
Veris assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings.
Count must be multiplied by the number of phases when using single CT models to monitor balanced multiphase systems.
800.354.8556
5
Warranty
+1 503.598.4564
www.veris.com
HQ00 01811.C 01131
800.354.8556
120
Yellow Voltage
Lead capped
N
120
Yellow CT*
4-20 mA Output
Red CT
B
A
B
E
F
C
D
B
E
F
C
D
A
A
B
E
C
F
D
SMALL
100/300 Amp
MEDIUM
400/800 Amp
LARGE
800/1600/2400 Amp
A = 3.8" (96 mm)
B = 1.2" (30 mm)
C = 1.3" (31 mm)
D = 1.2" (30 mm)
E = 4.0" (100 mm)
F = 4.8" (121 mm)
A = 4.9" (125 mm)
B = 2.9" (73 mm)
C = 2.5" (62 mm)
D = 1.2" (30 mm)
E = 5.2" (132 mm)
F = 6.0" (151 mm)
A = 4.9" (125 mm)
B = 5.5" (139 mm)
C = 2.5" (62 mm)
D = 1.2" (30 mm)
E = 7.9" (201 mm)
F = 6.0" (151 mm)
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWINGS
APPLICATION/WIRING EXAMPLES
H804x/H805x 208 or 480VAC 3Ø, 3/4 Wire
ØB
ØA
Black
Red
ØC
Yellow
H804x 240VAC 1Ø, 3-Wire
4-20mA or Pulse Output
Black CT*
Red CT
Yellow CT*
ORDERING INFORMATION
4-20 mA Output Power Transducers
Single CT Models for Use with Balanced 3Ø Loads
Three CT Models for Use with Unbalanced 3Ø Loads
MODEL VOLTAGE MAX. AMPS OUTPUT CT SIZE CT TYPE
H8041-0100-2
H8041-0300 -2 300 SMALL
H8041-0400-3 400 MEDIUM
H80 41-080 0-3 800 MEDIUM
208 /240
H8041-0800-4 800 LARGE
H8 041 -160 0- 4 160 0 LARGE
H8041-2400-4 2400 LARGE
H80 42-0100-2
H8042-030 0-2 300 SMALL
H8042-0400-3 400 MEDIUM
H8042-0800-3 800 MEDIUM
H8042-0800-4 800 LARGE
H8 04 2-160 0- 4 160 0 LARGE
H8042-2400-4 2400 LARGE
H8043-0100-2
H8043- 0300-2 300 SMALL
H8043-0400-3 400 MEDIUM
H8043-0800-3 800 MEDIUM
208 /240
H8043-0800-4 800 LARGE
H8 04 3-16 00 -4 160 0 LARGE
H8043-2400-4 2400 LARGE
H8044-0100-2
H804 4-0300-2 300 SMALL
H8044-0400-3 400 MEDIUM
H8044-0800-3 800 MEDIUM
H8044-0800-4 800 LARGE
H8044-1600-4 1600 LARGE
H8044-2400-4 240 0 LARGE
HQ00 01811.C 01131
100
100 SMALL
480
100 SMALL
100
480
4-2 0mA
4-2 0mA
SMALL
SMALL
Single CT
Model
Single CT
Model
Three C T
Model
Three C T
Model
H805x 208 or 480VAC 3Ø, 3/4-Wire
Pulse Output
ØB
ØA
ØC
Pulse Output Power Transducers
Single CT Models for Use with Balanced 3Ø Loads
Three CT Models for Use with Unbalanced 3Ø Loads
MODEL VOLTAGE MAX. AMPS OUTPUT CT SIZE CT TYPE
H8051-0100-2
H8051-0300 -2 300 SMALL
H8051-0400-3 400 MEDIUM
H8051-0800-3 800 MEDIUM
H8051-0800-4 800 LARGE
H8 051 -160 0- 4 160 0 LARGE
H8 051-240 0-4 2400 LARGE
H8053-0100-2 100 SMALL
208 /480
H8053-0300 -2 300 SMALL
H8053-0400-3 400 MEDIUM
H8053-0800-3 800 MEDIUM
H8053-0800-4 800 LARGE
H8 053 -160 0- 4 160 0 LARGE
H8 053-24 00- 4 24 00 LARGE
100
SMALL
Single CT Model
Pulse
Three CT Model
ACCESSORIES
CT Mounting brackets (AH06)
AH06
power/energy monitoring