POWER MONITORING
ENERCEPT® H804x SERiES
4-20mA Output kW Transducers
Installer’s Specifications
Input Voltage 208 to 480 VAC
Number of Phases Monitored 1 or 3
Frequency 50/60 H z
Maximum Primary Current 2400 A continuous per phase
CT case isolation 600 VAC
US Patent No. 6,373,238
IND. CONT. EQ.
UL 508
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
Internal isolation 2000 VAC rms
Operating temp. range 0° to 60°C (32 ° to 122°F) (<95%RH, non-condensing)
Storage temp. range -40° to 70°C (-4 0° to 158 °F)
Accuracy ±1% of reading from 10% to 100% of the rated current*
Output Type 4-20mA
Supply Power (loop) 9-30VDC; 30mA max.
CT 100A to 2400A
* Meter accuracy specied with conduc tors centered in the CT window.
QUICK INSTALL
Disconnect and lock out power before installation.
1. Connect the voltage leads to the phase conductors.
2. Snap the CT onto the conductor (observe color matching).
3. Connect the 4-20mA output wires (observe polarity).
INSTALLATION GUIDE
CAUTION
RISK OF EQUIPMENT DAMAGE
• Enercept meters are rated for use at 50-60Hz. Do not connect this product to circuits with
high harmonic energy, such as Variable Speed Drives (a.k.a. Variable Frequency Drives,
Adjustable Frequency Drives) or similar sources, as these may permanently damage the
product.
Failure to follow these instructions can result in overheating and permanent
equipment damage.
DIMENSIONS
B
A
F
C
D
E
100/300 Amp
A = 3.8" (96 mm)
B = 1.2" (30 mm)
C = 1.3" (31 mm)
D = 1.2" (30 mm)
E = 4.0" (100 mm)
F = 4.8" (121 mm)
SMALL
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
For use in a Pollu tion Degree 2 or bet ter environment only. A Pollut ion Degree 2 environme nt must
control conductive pollution and the possibility of condensation or high humidity. Consider the
enclosure, t he correct use of ven tilation, thermal pro perties of the equ ipment, and the relatio nship
with the env ironment. Installat ion category: CAT II or C AT III
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
F
MEDIUM
400/800 Amp
A = 4.9" (125 mm)
D
E
F
B = 2.9" (73 mm)
C = 2.5" (62 mm)
D = 1.2" (30 mm)
E = 5.2" (132 mm)
F = 5.9" (151 mm)
LARGE
800/1600/2400 Amp
A = 4.9" (125 mm)
B = 5.5" (139 mm)
D
E
C = 2.5" (62 mm)
D = 1.2" (30 mm)
E = 7.9" (201 mm)
F = 6.0" (151 mm)
TM
SHIELD
S
(+)(+)
External
Power (24 VDC)
PS-24
PANEL
(-)
Common
4-20mA Inpu
t
(-)
(s)
H804x SERIES
INSTALLATION GUIDE
OPERATION
The H8040 Series devices combine microprocessor-based kW transducers and
high-accuracy split-core instrument grade current transformers (CTs) in a single
unit. Integration of elec tronics lowers hardware and installation costs. The sensors
automatically detect phase reversal, so CT load orientation is not a concern. The
CTs and meters are calibrated as a set, so it is necessary to color-match the CTs and
voltage leads when installing.
The H8041 and H8042 are for single-phase or balanced-load applications at 208V and
480V, respectively. The H8043 and H8044 are the three-CT versions of the product for
use on 208V and 480V with unbalanced loads.
These devices are used in chiller optimization, performance contracting, and energy
management. The 1% total system accuracy conforms to ANSIC12.1 metering
standards.
PRODUCT DIAGRAM
®
Enercept
INSTALLATION
Disconnect and lock out power before installation.
The Enercept meter, including the current transformers (CTs), voltage connection
fuses, and fusepac, is permitted within electrical distribution equipment including
but not limited to panelboards, switchboards, motor control centers, and
transformers. Carefully review the equipment in which the Enercept meter will be
installed. The following installation conditions should be considered during the
installation process:
• Review the equipment enclosure for ventilation openings. Wires will cross
many of these openings in a normal installation, however, do not install
the Enercept where it will substantially block ventilation openings in the
enclosure.
• The Enercept meter and the wiring installed within a wiring space
or gutter should not exceed 75 percent cross sectional ll at the
Enercept meter parts as addressed in the NEC. Improper installation of
Enercept meter in the wire gut ter of equipment may aect the thermal
performance of the equipment.
• The arrangement of CTs within the equipment must also be considered to
ensure the bending radius of conductors is not adversely aected.
• Review the arrangement and location of the CTs within the equipment.
The CT must not create undue strain on the conductor. A CT may require
appropriate support in order to address such a condition.
2
3
4
Fuse Pack
2
5
1
2
2
1. Voltage Leads: input range is 208 to 480V, 50/60Hz.
2. Fuses: maximum current draw 60mA. Fuses provided by the factory are rated
1/2A, 600VAC, 200 KAIC. Replace only with fuses of the same type and rating.
3. 4-20mA Output connector
4. Status LED: blink codes: slow green for normal operation; slow red for incorrect
wiring or low power factor (less than 0.5); fast red for max. current exceedance.
5. External CTs (3-phase version only): permanently attached; do not disconnect or
use with other power meters.
Color match CTs and voltage leads! Example: clamp the red
labeled CT around the power conductor connected to the
red voltage wire.
1. Connect the voltage leads to the 3 phase conductors, at a location that is not
normally turned o. Connect voltage leads on the Line side of the conductor to
ensure constant power to the meter. Connect the red lead rst to the conductor
most conveniently located to the output connector. See the Wiring section on the
following page.
2. Snap the CT onto the conductor.
Observe color matching. If the
application can exceed 20 times the
rated CT current, use wire ties to
secure the I-bar to the CT housing.
This CT automatically detects phase
reversal, so CT load orientation is
not important.
3. Attach the 4-20mA output wires as shown. Observe (+), (-), and Shield polarity.
Insulate any exposed wiring.
Wire tie
4. Check power reading (these calculations are approximations only).
Expected power: 4-20mA response:
kW = Volts x Amps x 1.732 x PF / 1000 kW demand = kW x (mA out - 4) / 16
kW = Horsepower x 0.746
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
WIRING
TM
H804x SERIES
INSTALLATION GUIDE
Typical 208/480 VAC 3Ø, 3- or 4-Wire Installation
Model 8043/44Model 8041/42 (Use on balanced loads only)
4-20mA Output
NOTE: Multiply output by
3 for proper kW indication
4-20mA OUTPUT LINE
120
Neutral
120
Neutral
277
Model 8043
Model 8044
Typical 240/120 VAC 1Ø, 3-Wire Installation
4-20mA OUTPUT LINE
Typical 277 VAC 1Ø, 2-Wire Installation
4-20mA OUTPUT LINE
120V
Neutral
120V
Neutral
277V
Model 8041
Black
Red
Yellow
Model 8042
Black
Red
Yellow
NOTE: Multiply output by
2 for proper kW indication
NOTE: Multiply output by
2 for proper kW indication
Alternative 277 VAC 1Ø, 2-Wire Installation
277V
Model 8042
Neutral
Black
Red
Yellow
4-20mA OUTPUT LINE
NOTE: Wires are crossed through
the CT, each entering from
the opposite direction. Th is
arrangement does not require
multiplying the output data.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
TM
H804x SERIES
INSTALLATION GUIDE
TROUBLESHOOTING
ProblemSolution
Status LED does not blink
Readings seem highly
inaccurate.
Meter goes oine when load
is switched o.
Status LED blinks red.•IftheLEDblinksquickly(i.e.,about5blinksin
Check fuses and voltage connections. Status
LED should blink regardless of CTs or output
connections.
with the corresponding color voltage input
lead attached. In most cases, incorrect wiring
will cause the STATUS LED to blink RED (slowly).
However, a power factor lower than 0.5 could
cause the LED to blink this way, even if the unit is
installed properly.
•ItdoesnotmatterwhichsideoftheCTfaces
towards the load.
•Ifcurrentisbelow7%offullscalemaximum
for the CT, use a smaller CT or wrap each wire
through the CT multiple times
•Ifusingthesingle-phaseH8042,useanamp-
clamp to ensure that all three phases are passing
the same approximate current. If phases are
unbalanced, try the H8043/H8044 models.
Voltage leads must be connected on the Line
side of the conductor. The power meter cannot
communicate without voltage.
two seconds) the CTs are not installed on the
correct conductors, or the power factor is less
than 0.5. The meter can accurately measure
these low PFs, but few loads operate normally at
such a low power factor.
NOTES
1. DO NOT GROUND THE SHIELD INSIDE THE ELECTRICAL PANEL. All wires, including
the shield should be insulated to prevent accidental contact to high voltage
conductors.
2. The cable should be mechanically secured where it enters the electrical panel.
3. The cable should be shielded twisted pair wire BELDEN 1120A or similar.
WARNING: After wiring the cable, remove all scraps of
wire or foil shield from the electrical panel. This could
be DANGEROUS if wire scraps come into contact with high
voltage wires!