POWER MONITORING
ENERCEPT® H804x SERiES
4-20mA Output kW Transducers
Input Voltage 208 to 480 VAC Number of Phases Monitored 1 or 3 Frequency 50/60 H z Maximum Primary Current 2400 A continuous per phase CT case isolation 600 VAC
US Patent No. 6,373,238
IND. CONT. EQ.
UL 508
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
Internal isolation 2000 VAC rms Operating temp. range 0° to 60°C (32 ° to 122°F) (<95%RH, non-condensing) Storage temp. range -40° to 70°C (-4 0° to 158 °F) Accuracy ±1% of reading from 10% to 100% of the rated current* Output Type 4-20mA Supply Power (loop) 9-30VDC; 30mA max. CT 100A to 2400A
* Meter accuracy specied with conduc tors centered in the CT window.
QUICK INSTALL
Disconnect and lock out power before installation.
1. Connect the voltage leads to the phase conductors.
2. Snap the CT onto the conductor (observe color matching).
3. Connect the 4-20mA output wires (observe polarity).
INSTALLATION GUIDE
CAUTION
RISK OF EQUIPMENT DAMAGE
Enercept meters are rated for use at 50-60Hz. Do not connect this product to circuits with high harmonic energy, such as Variable Speed Drives (a.k.a. Variable Frequency Drives, Adjustable Frequency Drives) or similar sources, as these may permanently damage the product.
Failure to follow these instructions can result in overheating and permanent
equipment damage.
DIMENSIONS
B
A
F
C
D
E
100/300 Amp
A = 3.8" (96 mm) B = 1.2" (30 mm) C = 1.3" (31 mm) D = 1.2" (30 mm) E = 4.0" (100 mm) F = 4.8" (121 mm)
SMALL
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of Veris Industries nullify this statement.
For use in a Pollu tion Degree 2 or bet ter environment only. A Pollut ion Degree 2 environme nt must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, t he correct use of ven tilation, thermal pro perties of the equ ipment, and the relatio nship with the env ironment. Installat ion category: CAT II or C AT III
Z20170 0-0F PAGE 1 ©2008 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10101
B
C
A
B
C
A
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
F
MEDIUM
400/800 Amp
A = 4.9" (125 mm)
D
E
F
B = 2.9" (73 mm) C = 2.5" (62 mm) D = 1.2" (30 mm) E = 5.2" (132 mm) F = 5.9" (151 mm)
LARGE
800/1600/2400 Amp
A = 4.9" (125 mm) B = 5.5" (139 mm)
D
E
C = 2.5" (62 mm) D = 1.2" (30 mm) E = 7.9" (201 mm) F = 6.0" (151 mm)
TM
SHIELD
S
(+) (+)
External
Power (24 VDC)
PS-24
PANEL
(-)
Common
4-20mA Inpu
t
(-)
(s)
H804x SERIES
INSTALLATION GUIDE
OPERATION
The H8040 Series devices combine microprocessor-based kW transducers and high-accuracy split-core instrument grade current transformers (CTs) in a single unit. Integration of elec tronics lowers hardware and installation costs. The sensors automatically detect phase reversal, so CT load orientation is not a concern. The CTs and meters are calibrated as a set, so it is necessary to color-match the CTs and voltage leads when installing.
The H8041 and H8042 are for single-phase or balanced-load applications at 208V and 480V, respectively. The H8043 and H8044 are the three-CT versions of the product for use on 208V and 480V with unbalanced loads.
These devices are used in chiller optimization, performance contracting, and energy management. The 1% total system accuracy conforms to ANSIC12.1 metering standards.
PRODUCT DIAGRAM
®
Enercept
INSTALLATION
Disconnect and lock out power before installation.
The Enercept meter, including the current transformers (CTs), voltage connection fuses, and fusepac, is permitted within electrical distribution equipment including but not limited to panelboards, switchboards, motor control centers, and transformers. Carefully review the equipment in which the Enercept meter will be installed. The following installation conditions should be considered during the installation process:
• Review the equipment enclosure for ventilation openings. Wires will cross many of these openings in a normal installation, however, do not install the Enercept where it will substantially block ventilation openings in the enclosure.
• The Enercept meter and the wiring installed within a wiring space or gutter should not exceed 75 percent cross sectional ll at the Enercept meter parts as addressed in the NEC. Improper installation of Enercept meter in the wire gut ter of equipment may aect the thermal performance of the equipment.
• The arrangement of CTs within the equipment must also be considered to ensure the bending radius of conductors is not adversely aected.
• Review the arrangement and location of the CTs within the equipment. The CT must not create undue strain on the conductor. A CT may require appropriate support in order to address such a condition.
2
3
4
Fuse Pack
2
5
1
2
2
1. Voltage Leads: input range is 208 to 480V, 50/60Hz.
2. Fuses: maximum current draw 60mA. Fuses provided by the factory are rated 1/2A, 600VAC, 200 KAIC. Replace only with fuses of the same type and rating.
3. 4-20mA Output connector
4. Status LED: blink codes: slow green for normal operation; slow red for incorrect wiring or low power factor (less than 0.5); fast red for max. current exceedance.
5. External CTs (3-phase version only): permanently attached; do not disconnect or use with other power meters.
Color match CTs and voltage leads! Example: clamp the red labeled CT around the power conductor connected to the red voltage wire.
1. Connect the voltage leads to the 3 phase conductors, at a location that is not normally turned o. Connect voltage leads on the Line side of the conductor to ensure constant power to the meter. Connect the red lead rst to the conductor most conveniently located to the output connector. See the Wiring section on the following page.
2. Snap the CT onto the conductor. Observe color matching. If the application can exceed 20 times the rated CT current, use wire ties to secure the I-bar to the CT housing. This CT automatically detects phase reversal, so CT load orientation is not important.
3. Attach the 4-20mA output wires as shown. Observe (+), (-), and Shield polarity. Insulate any exposed wiring.
Wire tie
4. Check power reading (these calculations are approximations only).
Expected power: 4-20mA response: kW = Volts x Amps x 1.732 x PF / 1000 kW demand = kW x (mA out - 4) / 16 kW = Horsepower x 0.746
Z20170 0-0F PAGE 2 ©2008 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10101