Veris H8036 Installation Instructions

TM
the user will be required to correct the interference at his own expense.
ENERCEPT ™ H8035/H8036
Networked Power Transducer (Modbus RTU)
Installer’s Specifications
Measurement A ccuracy:
Syste m Accuracy ±1% of reading from 10% to 100% of the rated current * Type of Measurement One or three phase AC system
Input Voltage Characteristics:
Measured AC Voltage 208-480 VAC
POWER MONITORING
US Patent No. 6,373,238
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material.
CAUTION
RISK OF EQUIPMENT DAMAGE
Enercept meters are rated for use at 50-60Hz. Do not connect this product to circuits with high harmonic energy, such as Variable Speed Drives (a.k.a. Variable Frequency Drives, Adjustable Frequency Drives) or similar sources, as these may permanently damage the product.
Failure to follow these instructions can result in overheating and permanent
equipment damage.
Frequency Range 50/60 Hz Fuses 1/2A, 600VAC, 200 kAIC
Input Current Characteristics:
Maximum Primary Current 100, 300, 400, 800, 1600, or 2400 A, continuous p er phase**
Meter Current Draw:
Maximum 60 mA AC
Output:
Modbus RTU Protocol RS-485, 2-wire plus common Baud Rate 9600
Mechanical Conditions:
CT Case Iso lation 600 VAC Internal Isolation 2000 VAC RMS Terminal Block Screw Torque 0.37 ft-lb (0.5 N·m) min.; 0.44 ft-lb (0.6 N·m) max.
Environmental Conditions:
Operating Temperature Range 2400 A model only: 0° to 50°C (32° to 122°F) all other models: 0° to 60°C (32° to 140°F) Storage Temperature Range -40° to 70°C (-40° to 15 8°F) Operating Humidity Range <95% RH non-condensing
Agency Approvals:
US and Canada (cULus) UL508 (open ty pe device)
* Meter accuracy specied with conduc tors centered in the CT window. ** For amperages greater than 2400A, see App Note VN19, www.veris.com/applicationnotes.aspx
Disconnect and lock out power before installation.
1. Set the address switches located on the bottom of the CT.
2. Connect the voltage leads to the source to be monitored.
3. Snap the CT onto the conductor (observe color matching).
4. Connect the Modbus wires (observe polarity).
INSTALLATION GUIDE
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of Veris Industries nullify this statement.
For use in a Pollu tion Degree 2 or bet ter environment only. A Pollut ion Degree 2 environme nt must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, t he correct use of ven tilation, thermal pro perties of the equ ipment, and the relatio nship with the env ironment. Installat ion category: CAT II or C AT III
Z201686-0N PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TABLE OF CONTENTS
Quick Install 1
Operation 2
Product Identication 2
Dimensions 2
Product Diagram 2
Installation 3
Wiring 4
Data Outputs 4
Address Setup 5
Modbus Register Addressing 6
Using Integer Data Types 8
Notes 10
Troubleshooting 10
H8035/H8036
TM
INSTALLATION GUIDE
OPERATION
The H8035 and H8036 three-phase power transducers monitor energy parameters from aggregate kW (real power) and kWh (consumption) to power factor per phase. Integration of electronics lowers hardware and installation costs. The sensors automatically detect phase reversal, so CT load orientation is not a concern. The CTs and electronics are calibrated as a set, so it is necessary to color-match the CTs and voltage leads when installing. These devices monitor up to 63 loads at a time on a single RS-485 drop.
With two platforms to choose from (H8035 Basic/Energy Only or H8036 Enhanced Data Stream), the applications for these devices are diverse, including aggregate billing, tenant monitoring, energy management, performance contracting, demand limiting and cooling plant optimization.
PRODUCT IDENTIFICATION
Modbus Enhanced Data Stream Power Transducers*
MODEL MAX. AMPS CT SIZE
H8036-0100-2 100 SMALL
H8036-0300-2 300 SMALL
H8036-0400-3 400 MEDIUM
H8036-0800-3 800 MEDIUM
H8036-0800-4 800 LARGE
H8036-1600-4 1600 LARGE
H8036-2400-4 2400 LARGE
DIMENSIONS
B
C
A
B
C
A
B
C
A
F
SMALL
100/300 Amp
A = 3.8" (96 mm)
D
E
F
B = 1.2" (30 mm) C = 1.3" (31 mm) D = 1.2" (30 mm) E = 4.0" (100 mm) F = 4.8" (121 mm)
MEDIUM
400/800 Amp
A = 4.9" (125 mm)
D
E
F
B = 2.9" (73 mm) C = 2.5" (62 mm) D = 1.2" (30 mm) E = 5.2" (132 mm) F = 6.0" (151 mm)
LARGE
800/1600/2400 Amp
A = 4.9" (125 mm)
D
E
B = 5.5" (139 mm) C = 2.5" (62 mm) D = 1.2" (30 mm) E = 7.9" (201 mm) F = 6.0" (151 mm)
*H8036 models work with H8920-1 LON nodes
Modbus Basic Power Transducers*
MODEL MAX. AMPS CT SIZE
H8035-0100-2 100 SMALL
H8035-0300-2 300 SMALL
H8035-0400-3 400 MEDIUM
H8035-0800-3 800 MEDIUM
H8035-0800-4 800 LARGE
H8035-1600-4 1600 LARGE
H8035-2400-4 2400 LARGE
*H8035 models work with H8920-5 LON nodes
PRODUCT DIAGRAM
®
Enercept
5
4
3
1. Voltage leads
2. Fuses
3. Modbus connector
4. Status LED: Blink codes: slow green for normal operation; slow red for incorrect wiring or low power factor (less than 0.5); fast red for maximum current exceeded.
5. Modbus address switches
6
2
1
6. External CTs: Permanently attached; do not disconnect or use with other power transducers.
Color match CTs and voltage leads! Example: clamp the red labeled CT around the power conductor connected to the red voltage wire.
Z201686-0N PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
H8035/H8036
Wire tie
SHIELD
SHIELD
S
S
SHIELD
120
Terminator
TM
INSTALLATION
Disconnect and lock out power before installation.
The Enercept meter, including the current transformers (CTs), voltage connection fuses, and fuse pack, is permitted within electrical distribution equipment including but not limited to panelboards, switchboards, motor control centers, and transformers. Carefully review the equipment in which the Enercept meter will be installed. Consider the following installation conditions during the installation process:
• Review the equipment enclosure for ventilation openings. Wires will cross many of these openings in a normal installation, however, do not install the Enercept where it will substantially block ventilation openings in the enclosure.
• The Enercept meter and the wiring installed within a wiring space or gutter should not exceed 75 percent cross sectional ll at the Enercept meter parts as addressed in the NEC. Improper installation of Enercept meter in the wire gut ter of equipment may aect the thermal performance of the equipment.
• Consider the arrangement of CTs within the equipment to ensure the correct bending radius of conductors.
• Review the arrangement and location of the CTs within the equipment. Use appropriate support for the CT to prevent undue strain on the conductor.
ADDRESS
1. Choose a unique address and set the switches for that address as shown in the Address Selec tion Switches section. Only addresses 1 to 63 can be used.
2. Connect the voltage leads to the phase conductors at a location that is not normally turned o. Connect voltage leads on the Line side of the conductor to ensure constant power to the Enercept. For a 3-phase system, connect the red lead to phase A, black to phase B, and yellow to phase C. See the Wiring section on the following page.
1 2 4
8 16 32
INSTALLATION GUIDE
4. Remove the terminal block and attach the RS-485 wires. Observe (+), (-), and Shield polarity. Insulate any exposed wiring.
5. For information regarding software setup, see the Modbus protocol specications available at www.veris.com/Modbus/.
6. Check power reading (these calculations are approximations only).
Expected power:
kW = Volts x Amps x 1.732 x PF / 1000
kW = Horsepower x 0.746
3. Snap the CT onto the conductor. Connect CTs to the correspondingly colored voltage leads. If the application can exceed 20 times the rated CT current, use wire ties to secure the I-bar to the CT housing. This CT automatically detects phase reversal, so CT load orientation is not important.
Z201686-0N PAGE 3 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 08122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Loading...
+ 7 hidden pages