Veris H8026 Installation Instructions

TM
the user will be required to correct the interference at his own expense.
POWER MONITORING
ENERCEPT® H8025/8026
Networked (N2 BUS) Power Meters
Input Voltage 208 to 480 VAC Number of Phases Monitored 1 or 3 Frequency 50/60 H z Maximum Primary Current 100/300/400/800/1600/2400 A continuous per phase CT case isolation 600 VAC
US Patent No. 6,373,238
IND. CONT. EQ.
UL 508
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
Internal isolation 2000 VAC rms Operating temp. range 0° to 60°C (32° to 122°F) (<95%RH, non-condensing) Storage temp. range -40° to 70°C (-4 0° to 158°F) Accuracy ±1% of reading from 10% to 100% of the rated current* Output Type RS-485, 2-wire plus common Baud Rate 9600 Protocol N2
* Meter accuracy specied with conduc tors centered in the CT window.
QUICK INSTALL
Disconnect and lock out power before installation.
1. Set the address switches located on the bottom of the CT.
2. Connect the voltage leads to the source to be monitored.
3. Snap the CT onto the conductor (observe color matching).
INSTALLATION GUIDE
CAUTION
RISK OF EQUIPMENT DAMAGE
Enercept meters are rated for use at 50-60Hz. Do not connect this product to circuits with high harmonic energy, such as Variable Speed Drives (a.k.a. Variable Frequency Drives, Adjustable Frequency Drives) or similar sources, as these may permanently damage the product.
Failure to follow these instructions can result in overheating and permanent
equipment damage.
4. Connect the N2 BUS wires (observe polarity).
DIMENSIONS
F
B
C
D
A
E
SMALL
100/300 Amp
A = 3.8" (96 mm) B = 1.2" (30 mm) C = 1.3" (31 mm) D = 1.2" (30 mm) E = 4.0" (100 mm) F = 4.8" (121 mm)
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of Veris Industries nullify this statement.
For use in a Pollu tion Degree 2 or bet ter environment only. A Pollut ion Degree 2 environme nt must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, t he correct use of ven tilation, thermal pro perties of the equ ipment, and the relatio nship with the env ironment. Installat ion category: CAT II or C AT III
Z201640-0H PAGE 1 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 11101
B
C
A
B
C
A
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
F
MEDIUM
400/800 Amp
A = 4.9" (125 mm)
D
E
F
B = 2.9" (73 mm) C = 2.5" (62 mm) D = 1.2" (30 mm) E = 5.2" (132 mm) F = 5.9" (151 mm)
LARGE
800/1600/2400 Amp
A = 4.9" (125 mm) B = 5.5" (139 mm)
D
E
C = 2.5" (62 mm) D = 1.2" (30 mm) E = 7.9" (201 mm) F = 6.0" (151 mm)
TM
H8025/8026
INSTALLATION GUIDE
OPERATION
The H8025 and H8026 three-phase power transducers monitor energy parameters from aggregate kW (real power) and kWh (consumption) to power factor per phase. Integration of electronics lowers hardware and installation costs. The sensors automatically detect phase reversal, so CT load orientation is not a concern. The CTs and meters are calibrated as a set, so it is necessary to color-match the CTs and voltage leads when installing.
With two platforms to choose from (H8025 Energy Only or H8026 Enhanced Data Stream), the applications for these devices are diverse, including aggregate billing, tenant submetering, energy management, performance contracting, demand limiting and cooling plant optimization. The 1% total system accurac y conforms to ANSIC12.1 metering standards.
PRODUCT DIAGRAM
®
Enercept
5
4
3
6
INSTALLATION
Disconnect and lock out power before installation.
The Enercept meter, including the current transformers (CTs), voltage connection fuses, and fusepac, is permitted within electrical distribution equipment including but not limited to panelboards, switchboards, motor control centers, and transformers. Carefully review the equipment in which the Enercept meter will be installed. The following installation conditions should be considered during the installation process:
• Review the equipment enclosure for ventilation openings. Wires will cross many of these openings in a normal installation, however, do not install the Enercept where it will substantially block ventilation openings in the enclosure.
• The Enercept meter and the wiring installed within a wiring space or gutter should not exceed 75 percent cross sectional ll at the Enercept meter parts as addressed in the NEC. Improper installation of Enercept meter in the wire gut ter of equipment may aect the thermal performance of the equipment.
• The arrangement of CTs within the equipment must also be considered to ensure the bending radius of conductors is not adversely aected.
• Review the arrangement and location of the CTs within the equipment. The CT must not create undue strain on the conductor. A CT may require appropriate support in order to address such a condition.
Fuse Pack
2
1. Voltage Leads: input range is 208 to 480V.
2. Fuses: maximum current draw 60mA. Fuses provided by the factory are rated 1/2A, 600VAC, 200 KAIC. Replace only with fuses of the same type and rating.
3. Pulse Output connector
4. Status LED: blink codes: slow green for normal operation; slow red for incorrect wiring or low power factor (less than 0.5); fast red for max. current exceedance.
5. Pulse Rate Switches: used to set the pulse output rate.
6. External CTs: permanently attached; do not disconnect or use with other power meters.
Color match CTs and voltage leads! Example: clamp the
red labeled CT around the power conductor connected to the red voltage wire.
1. Choose a unique address and set the switches for that address as shown in the Address Selection Switches section. Only addresses 1 to 63 can be used.
1
2. Connect the voltage leads to the phase conductors, at a location that is not normally turned o. Connect voltage leads on the Line side of the conductor to ensure constant power to the meter. For a 3-phase system, connect the red lead to phase A, black to phase B, and yellow to phase C. See the Wiring section on the
following page.
3. Snap the CT onto the conductor. Connect CTs to the correspondingly colored voltage lead. If the application can exceed 20 times the rated CT current, use wire ties to secure the I-bar to the CT housing. This CT automatically detects phase reversal, so CT load orientation is not important.
4. Remove the terminal block and attach the N2 BUS. Observe (+), (-), and Ref polarity. Insulate any exposed wiring. When installing multiple meters, attach all N2 Bus connectors to the network trunk cable, and then connect individual meters
Wire tie
Z201640-0H PAGE 2 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 11101
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
TM
N2 BUS
ØA
ØB
ØC
120
Neutral
120
N2 bus
Black CT
Red CT
ØA
ØB
Neutral
277
N2 bus
Black CT
Red CT
Yellow C
T
ØA
H8025/8026
INSTALLATION GUIDE
5. Set up Metasys (see Metasys Setup section).
6. Check power reading (these calculations are approximations only).
Expected power: kW = Volts x Amps x 1.732 x PF / 1000 kW = Horsepower x 0.746
WIRING
Typical 208/480 VAC 3Ø, 3, 4 Wire Installation
Typical 240/120 VAC 1Ø, 3 Wire Installation
(Cap yellow voltage lead)
Typical 277 VAC 1Ø, 2 Wire Installation
NOTES
1. DO NOT GROUND THE N2 BUS REFERENCE INSIDE THE ELECTRICAL PANEL. All N2 lines, including the shield, should be insulated to prevent accidental contact with high voltage conductors.
2. The N2 BUS cable should be mechanically secured where it enters the electrical panel.
3. All N2 BUS devices should be connected together in a daisy-chain fashion.
4. The N2 BUS cable should be shielded twisted pair wire BELDEN 1120A or similar.
WARNING: After wiring the N2 BUS cable, remove all scraps of wire or foil shield from the electrical panel. This could be DANGEROUS if wire scraps come into contact with high voltage wires!
OUTPUT
H8025 AC-1: kWh, consumption BO-1: Reset kWh AI-1: kW, real power
H8026 AC-1: kWh, consumption BO-1: Reset kWh BO-2: Reset min./max./avg. AI-1: kWh, consumption AI-2: kW, real power AI-3: VAR, reactive power AI-4: VA, apparent power AI-5: Power factor AI-6: Average real power AI-7: Minimum real power AI-8: Maximum real power AI-9: Voltage, line-to-line AI-10: Voltage, line-to-neutral AI-11: Amps, average current AI-12: kW, real power ØA AI-13: kW, real power ØB AI-14: kW, real power ØC AI-15: Power factor ØA AI-16: Power factor ØB AI-17: Power factor ØC AI-18: Voltage, ØA to ØB AI-19: Voltage, ØB to ØC AI-20: Voltage, ØAto ØC AI-21: Voltage, ØA to Neutral AI-22: Voltage, ØB to Neutral AI-23: Voltage, ØC to Neutral AI-24: Amps, Current ØA AI-25: Amps, Current ØB AI-26: Amps, Current ØC
Note: The meter cannot communicate on the N2 bus without po wer. Therefore, it is best to connect the voltage leads ahead of switching devi ces.
Z201640-0H PAGE 3 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 11101
(Cap yellow voltage lead)
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
Loading...
+ 6 hidden pages