Veris H800 Installation Instructions

TM
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
DANGER
CURRENT MONITORING
TM
800
Solid-Core On/O Current Switch, Fixed Trip Point
RoHS
Compliant
INSTALLATION GUIDE
SPECIFICATIONS
Sensor Power Induced from monitored conductor Amperage Range 0.25 to 200 A Continuous Status Output Ratings N.O. 1.0 A@30 VAC/DC, not polarity sensitive Insulation Class 600 VAC RMS (UL); 300 VAC (CE), insulated conductor s only Setpoint Fixed at 0.25 A max . Frequency 50/60 H z Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH non-condensing O State Resis tance Open switch represent s 1+ MΩ On State Resistance Closed switch represents <200 mΩ Terminal Block Wire Size 0.2 to 2.1 mm2(24 to14 AWG) Terminal Block Torque 0.4 to 0.5 N-m(3.5 to 4.4 in-lb) Agency Approvals UL508 E150462, CE:EN61010-1:2001 Installation Categor y Cat. III, pollution degree 2
For CE compliance, conductor shall be insul ated according to IEC 61010‑1:2010. The product design provides for basic insulation only.
INSTALLATION
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
POWER SOURCE
Insulated Conductor Only
BUILDING AUTOMATION
CONTROLLER
DI
DI
Disconnect and lock out power to the enclosure containing the conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow the monitored conductor to pass through the center window when it is installed and that will keep the device at least ½” (13 mm) from any uninsulated conductors. Determine cable routing for the controller connection, allowing wiring to reach the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections and relay between the sensor and the controller (solid-state contact).
4. Route the conductor through the sensor’s center window and slip the assembly into the mounting bracket.
5. Secure enclosure and reconnect power.
DIMENSIONS
Removable/Adjustable Mounting Bracket
 0.7" (18 mm)
0.9"
(23 mm)
2.8"
(71 mm)
Z20198 4-0G PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 12121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.
POWER SOURCE
UNIT VENT HEATER
0.4” x 0.2” Slot (x2)
1.7
(43 mm)
2.3"
(58 mm)
1.1"
(27 mm)
TM
H800
INSTALLATION GUIDE
PRODUCT OVERVIEW
The H800 is a current-sensitive switching device that monitors current (amperage) in the conductor passing through it. A change in amperage in the monitored conducter that crosses the switch threshold will cause the resistance of the status output to change state, similar to the action of a mechanical switch. The threshold is xed at
0.2 A or less. The status output is suitable for connection to building controllers or other appropriate data acquisition equipment operating at up to 30 volts. The H800 requires no external power supply to generate its output.
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be combined with wrapping (see below) to add range for a low current load on a high current source.
> 200 A (Sensor max.)
300A:5A
H68xx‑5A CT
4A
4.2 A
240A
250 A
TROUBLESHOOTING
Problem Solution
No Reading at Controller • Check for control voltage at sensor (<30 V)
• Check for amperage in monitored conductor (>0.25 A)
DANGER: 5A CTs can present hazardous voltages. Install CTs in accordance with manufacturer's instructions. Terminate the CT secondary before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases the current measured by the transducer.
Program the controller to account for the extra turns, e.g., if four turns pass through the sensor (as shown), then divide the normal controller reading by 4.
< 0.25 A (Sensor Min.)
0.1A
0.5A
4x
Z20198 4-0G PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 12121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.