TM
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
CURRENT MONITORING
INSTALLATION GUIDE
H738
TM
738
Solid-Core Current Switch, Adjustable Trip Point
With Command Relay
Installer’s Specifications
Amperage Range 1-135 A continuous
Sensor Power Induced from monitored current
Insulation Class 600 VAC RMS
Frequency Range 50/60 Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% of setpoint, typical
Terminal Block Maximum WIre Size 14 AWG
Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
Status Output N.O. 1.0 A@30 VAC/DC
Relay Coil 24 VAC/DC, 10 mA
Relay Contac t Resistive: 10 A@250 VAC, 30 VDC; Induc tive: 5 A@250 VAC, 30 VDC
Agency Approvals UL508 E150462
Do not use the LED status indicators as evidence of ap plied voltage.
The product design provi des for basic insulation only.
INSTALLATION
Disconnect and lock out power to the enclosure containing the
conductor to be monitored.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
CONTROLLER
DI
(Status)
DO
(Relay
Coil)
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
2. Route the conductor through the sensor’s center window and slip the assembly
into the mounting bracket. Terminate the conductor. See Notes (page 2) for
currents under 1 Amp or above 135 Amps.
3. Wire the output connections to the DDC controller or switched load (solid state
contact).
4. Secure enclosure and reconnect power.
5. Calibrate the sensor (see Calibration section).
DIMENSIONS
Removable/Adjustable Mounting Bracket
0.9"
0.7"
(19 mm)
(23 mm)
3.0"
(75 mm)
Z201487-0A PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.
CONTROL
POWER
CONTACTOR
Fan or Pump
Motor
0.2” x 0.15”
slot (2x)
2.8"
(68 mm)
(95 mm)
4.2"
(106 mm)
3.8"
1.1"
(27 mm)
TM
H738
INSTALLATION GUIDE
OPERATION
The H738 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in the conductor’s amperage that crosses
the adjustable switch threshold plus the hysteresis value causes the resistance of
the FET status output to change state, similar to the action of a mechanical switch.
In this model, the setpoint is adjustable through the action of a twenty (20) turn
potentiometer (see the CALIBRATION section). An integrated relay allows start/
stop control. The status output is suitable for connection to building controllers or
other appropriate data acquisition equipment operating at up to 30 volts. The H738
requires no external power supply to generate its output.
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.
240A
> 135 A (Sensor max.)
5A
300A:
CALIBRATION
Before beginning calibration, establish normal load conditions.
OK!
A
Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
!
OK!
A
1. Turn setpoint screw
clockwise until Status OPEN
LED turns ON.
2. Slowly turn the screw counter-clockwise until the Status CLOSED LED just
turns ON.
Setpoint
Status
Closed
OK!
STOP
+
Status
Open
Setpoint
1/4
STATUS
OK!
Setpoint
STOP
3.Turn the screw an
additional 1/4 turn
counter-clockwise for
operational margin.
H68xx-5A CT
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.
< 1 A (Sensor Min.)
0.5A
4x
B. To monitor over-current (mechanical problems, seized impeller)
1/4
STATUS
OK!
STOP
3. Turn the setpoint
screw an additional
1/4 turn clockwise for
operational margin.
!
OK!
A
1. Turn setpoint screw
counter-clockwise until Status
Setpoint
Status
Closed
CLOSED LED turns ON.
2. Slowly turn the setpoint screw clockwise until the Status OPEN LED just turns ON.
Status
Setpoint
Open
Setpoint
+
STOP
TROUBLESHOOTING
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control voltage at sensor (< 30 V)
• Check for amperage in monitored conductor (>1 A)
Setpoint screw has no
stops
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.
The setpoint screw has a slip-clutch at both ends of its travel to
avoid damage. Twenty turns CCW will reset the sensor to be
most sensitive. Repeat calibration above.
Z201487-0A PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.