Veris E30 series, E30A, E30C, E30B Installation Manual

TM
the user will be required to correct the interference at his own expense.
Power MoNITorING
INSTALLATIoN GUIDe
E30
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
E30
Panelboard Monitoring System
Installer’s Specifications
Inputs:
Accurac y:
Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008 Volt age ±0.5% of reading 90-277V line-to-neutral
Operation:
Sampling Frequency 2560 Hz Update Rate 1.8 seconds (both panels) Overload Capability 22 kAIC
Outputs:
Type Modbus RTU Connection DIP switch-select able 2-wire or 4-wire, RS-485 Address DIP switch-select able address 1 to 247 (in pairs of 2)* Baud Rate DIP switch-select able 9600, 19200, 38400 Parity DIP switch-selectable NONE, ODD, EVEN Communication Format 8-data-bits, 1-start-bit, 1-stop-bit Termination 5-position depluggable connector (TX+ TX- SHIELD TX+/RX+ TX-/RX-)
Mechanical:
Ribbon Cable Suppor t 4 ft. (0.9 m) at ribbon cable ships standard;
up to 20 ft. (6 m) available
Environmental:
* See Conguration section for de tails.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of Veris Industries nullify this statement.
Product IdentIfIcatIon
Description
E30
A = Advanced B = Interme diate C = Basic
CT Option
0 = 100A, 3/4" spacing 1 = 100A, 1" spacing
# of CTs
42 = 2 strips* 84 = 4 stri ps*
table of contents
Quick Install 2
Operation 2
Dimensions 2
Product Diagram 3
Data Output 3
Blink Codes for Status LED 3
Solid-Core CT Accuracy 3
Installation 4
Wiring 7
Conguration 8
Default DIP Switch Settings 8
Address Setup 9
Commissioning 10
Recommended Accessories 10
Safety 10
Troubleshooting 11
China RoHS Compliance Information IEFUP Table) 11
*Each strip contains 21 current sensors.
Z204998-0M PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
e30
TM
INSTALLATIoN GUIDe
quIck Install
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
1. Disconnect and lock out power. Use a properly rated voltage sensing device to conrm power is o.
2. Mount current sensor strips adjacent to breaker terminations.
3. Verify that the serial numbers on the CT strips match the serial number
on main circuit board (Data Acquisition Board).
4. Congure communication and addressing parameters using DIP switches.
5. Mount the main acquisition board in the electrical enclosure.
6. Connect current sensor strip cables to the main board, observing the 2-strip or 4-strip setup and their orientation (A or B) within the panel.
7. Wire RS-485 communications.
8. Connect CTs to the auxiliary inputs and connec t them onto the main conductors in the enclosure (optional).
9. Wire control power and voltage taps (E30A and E30B only).
10. Download the free E3x conguration tool from www.veris.com to commission the device for operation.
oPeratIon
The E30 Series Branch Current Monitor is a device designed to measure the current, voltage, and energy consumption of up to 92 circuits (84 branch circuits, 2 3-phase mains, 2 neutrals) on a single board. It increases the board’s current monitoring capability by combining the functions of two boards into one device.
The E30 consists of a data acquisition board and up to four 21-unit current sensor strips, with eight auxiliary inputs. The strips are mounted on each side of the panel board along the termination points of each breaker. The conductor passes through the appropriate current sensor before terminating at the breaker. Each strip transmits the current data to the data acquisition board.
dImensIons
Circuit Board and Mounting Bracket
3.9”
(100 mm)
Ø = 0.2”
(5 mm)
1.3”
(33mm)
3/4” opti on
2.0”
(50mm)
1.2”
1” opt ion
(30mm)
2.0”
(50mm)
8.3”
(211 mm)
7.3”
(184 mm)
8.9”
(288 mm)
7.9”
(200 mm)
Solid-Core CT Strips
20.3” (516mm)
0.4” (10mm) opening
25.0” (635mm)
0.4” (10mm) opening
slot: 0.25” x 0.5”
(7 x 13mm)
0.75” (19mm) on center
slot: 0.25” x 0.5”
(7 x 13mm)
1.0” (26mm) on center
1.75”
(45 mm)
4.8”
(122 mm)
(28mm)
0.8”
(20mm)
1.2”
(31mm)
1.1”
5.8”
(146 mm)
Data is transmitted using an RS-485 Modbus protocol. Each data acquisition board requires two addresses, one for each set of two current sensor strips and four auxiliary inputs. Data is updated roughly every two seconds. As a circuit approaches the user-dened threshold, the E30 activates the alarm indicators.
The E30A measures both current and power for the mains and branch circuits. The E30B measures both current and power for the mains, and current only in each circuit. The E30C measures current only for the mains and branch circuits.
Z204998-0M PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
e30
TM
INSTALLATIoN GUIDe
Product dIagram
A A
1
B B
8
2
3
4
5
6
1. 50-Pin Ribbon Cable Connectors (Data Acquisition Board): 48-inch (1220
mm) ribbon cables are provided for easy connection of current sensor strips to this point of the data acquisition board. The two connectors on the left are for panelboard 1; the two on the right are for panelboard 2.
Note: Connect CT strips to the correct ribbon cable connectors for each panel. The top connector is for Strip A, and the bottom conector is for Strip B.
Verify that the serial numbers on the CT strips match the serial number on the main circuit board (Data Acquisition Board).
2. Auxiliary Inputs: These 0.333 VAC inputs are used for monitoring the main
breaker or other high amperage source. Inputs on the lef t are for panelboard 1; inputs on the right are for panelboard 2.
3. Control (Mains) Power Connection: Easy 2-wire 90-277 VAC 50/60 Hz
connection.
4. Control Power Fuse: 600 VAC, 500 mA time lag, factory-replaceable.
5. Alive LED: Red/green/amber LEDs. Blink codes are on page 3.
7
2
12
11
10
9
13
data outPut
Monitoring at Mains E30A E30B E30C
Current per phase
Max. current per phase
Current demand per phase
Max. current demand per phase
Energy (kWh) per phase
Real Power (kW) per phase
Apparent Power (kVA)
Power factor total *
Power factor per phase
Voltage - L-L and average
Voltage - L-N and average
Frequency (phase A)
Monitoring at Branch Circuit
Current
Max. current
Current demand
Max. current demand
Real power (kW)
Real power (kW) demand
Real power (kW) demand max.
Energy (kWh) per circuit
Power factor
Apparent Power (kVA)
Modbus Alarms
Voltage over/under
Current over/under
6. Voltage Taps: 1, 2, or 3 phase plus neutral connections. For voltage sensing and
power calculations (no voltage taps on the E30C).
7. Communications Address DIP Switches: Each Modbus device must have a
unique address. Switches are binary weighted. Lef t-most switch has a value of 1; right-most switch has a value of 128. Note: the 4-strip model uses 2 addresses.
8. Communications Settings DIP Switch: Congures baud rate, parity, 2/4 wire
communications.
9. RS-485 2 Connection: Used for Modbus serial communications. The Universal
plug accomodates 2 or 4 wire connec tions.
10. RS-485 LEDs: The RX LED (closest to DIP switches) indicates the RS-485
is receiving information; the TX LED (farthest from DIP switches) indicates transmission of information.
11. Power LED: Indicates power to main board
12. Current Sensors: Each current sensor is capable of monitoring conductors rated
up to a maximum of 100 amps.
13. 50 Pin Ribbon Cable Connectors (Current Sensor Strips): Connects current
signal from the sensor strip to the main board via the ribbon connectors.
Z204998-0M PAGE 3 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
* Based on a 3-phase breaker rotation.
blInk codes for status led
Color and Pattern Status Description
Green, once per second Normal operation
Amber, once per second Volts or Amps clipping
Amber, twice per second Invalid rmware image
Amber, three per second Incorrect strips or strip order
Red, solid or blink Diagnostic event detected
solId-core ct accuracy
100A Solid-Core CT
Voltage Rating 300 VAC
Accuracy ±0.5%
Temperature 0° to 60°C
Agency UL508 recognized, EN61010
e30
TM
INSTALLATIoN GUIDe
InstallatIon
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
Disconnect power to the electrical panel and lock it out.
1. Install the current sensor strips in the panel (Figure 1).
2. Arrange the sensor strips in one of the four congurations shown in Figure 2. Adjust orientation of the circuit numbers in the eld during commissioning by writing to Modbus Register 6 or use free conguration software at www.veris. com.
Top Feed Bottom Feed
Register 6 Value = 0
(Default)
Panel 2
A
2
1
A
B
3
6
5
7
10
9
11
14
13
15
18
17
19
22
21
23
26
25
27
30
29
31
34
33
35
38
37
39
42
41
Figure 2
B
A
2
1
3
6
5
7
10
9
11
14
13
15
18
17
19
22
21
23
26
25
27
30
29
31
34
33
35
38
37
39
42
41
Panel 1
A
4
8
B
12
16
20
24
28
32
36
40
20
Figure 1
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
2020202020202020
20
20202020202020202020
CTs accept a maximum #2 AWG (0.384” O.D.)
wire with THHN insulation.
Use this gauge wire or smaller for 100 A circuits .
Register 6 Value = 1
Panel 2
B
A
B
3
7
11
15
19
23
27
31
35
39
B
B
4
8
12
16
20
24
28
32
36
40
A
1
4
3
5
8
7
9
12
11
13
16
15
17
20
19
21
24
23
25
28
27
29
32
31
33
36
35
37
40
39
41
Panel 1
A
B
2
6
10
14
18
22
26
30
34
38
42
20
A
2
1
4
6
5
8
10
9
12
14
13
16
18
17
20
22
21
24
26
25
28
30
29
32
34
33
36
38
37
40
42
41
Single Row: Sequential Single Row: Odd/Even
A
2
4
6
8
10
12
14
16
18
20
22
B
24
26
28
30
32
34
36
38
40
42
Panel 1
A
1
B
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
Z204998-0M PAGE 4 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Panel 2
Register 6 Value = 2
A
A
B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
B
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
A
3
7
11
15
19
23
27
31
35
39
2
B
6
10
14
18
22
26
30
34
38
42
Panel 1
A
1
B
5
9
13
17
21
25
29
33
37
41
4
8
12
16
20
24
28
32
36
40
Register 6 Value = 3
Panel 2
A
A
B
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
B
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42