• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
INSTALLATION GUIDE
Replacement CO Sensing Module
INSTALLATION
1. Disconnect power from the unit.
2. Unscrew the transmitter cover.
3. Carefully remove the old sensor module. Module may be hot! If necessary, allow
the unit to cool before proceeding.
4. Plug the new module rmly into the socket.
PRODUCT IDENTIFICATION
AA09 Replacement CO Sensor
OPERATION
To assure continued reliable operation of the G Series CO transmitter, replace the
AA09 sensor module ever y 5 years. The AA09 is factory calibrated. No eld calibration
is required or possible. Verify proper operation by observing LED indicators on the G
Series device (see the G Series installation guide for details).
DIMENSIONS
1.9”
(48 mm)
0.9”
(23 mm)
1.3”
(32 mm)
Ø 0.95”
(24 mm)
Plug
Socket
5. Replace cover, and reconnect power to the unit.
6. Allow 72 hours for the module to stabilize after initial power application.