Veris AA04 Installation Instructions

TM
2.5"
62 mm
1.2"
28 mm
3.9"
98 mm
4.3"
109 mm
POWER SUPPLY
12 to 24 VDC Veris #PS-24
DIGITAL CONTROL
4-20mA Return
+
+
RED
BLK
+
1888
POWER SUPPLY
12 to 24 VDC Veris #PS-24
+
+
+ -
0
RED
BLK
1888
ENVIRONMENTAL SENSORS
AA04 AA04
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
INSTALLATION GUIDE
Remote Display, 4-20mA
Installer's Specifications
Repeatability ±2% full scale Analog Output 4-20mA, scaled 0 -100%; polarity sensitive Input power Loop powered, 12-30 VDC, 30mA max.
INSTALLATION
1. Mount indoors using the screws provided.
2. Wire the device. See the Wiring section for diagrams. Observe polarity.
PRODUCT IDENTIFICATION
AA04 Remote display for use with 4-20 mA output devices
OPERATION
The AA04 remote display converts a standard 4-20 mA output from an environmental sensor into a convenient digital readout.
DIMENSIONS
SPAN ZERO
4. Connect a 4-20mA loop calibrator to the black and red wires.
5. Set the loop calibrator to 4mA and adjust the “ZERO” pot until the display shows an output of 0%.
6. Set the loop calibrator to 20mA and adjust the “SPAN” pot until the display shows an output of 100% (scaling to less than 100% is also permitted).
7. Repeat steps 5 and 6 until the scaling is stable at 0 and 100%.
8. Replace housing cover.
WIRING
2-Wire, Loop powered, Sinking Transmitter
Z201241- 0K PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 04121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
3-Wire, Sourcing Transmitter
Loading...