Veris 380 Datasheet

380 SERIES
Tee Meter, BTU System
Measures Temperature And Flow Rate And Calculates Energy
meter &
temperature
sensors all
in one
piece!
VERIS INDUSTRIES
380 Series
DESCRIPTION
Series 380 BTU System provides a low-cost system for metering cold or hot systems. The 380 measures ow and temperature dierential to accurately calculate energy. With BACnet, Modbus RS-485, or scaled pulse output, it can interface with many existing control systems.
The rugged design incorporates an impeller ow sensor and two temperature probes, one mounted in the ow sensor tee and the other on either the supply or return line, depending on the application.
Commissioning can be done in the eld via a computer connection or set up at the factory. Setup includes energy measurement units, measurement method, communication protocol, pulse output control, uid density, and specic heat parameters (requires re-usable programming cable and software, see Ordering Information).
APPLICATIONS
Energy management and data systems
flow
FEATURES
Rugged, compact design with two temperature probes
316 SS impeller with tungsten carbide shaft
PEEK housing
Cast bronze tee
Minimal connections...simplify installation, saving time and cost
Integration of ow and temperature sensors with metering components...
single solution for metering
BACnet and Modbus protocols are standard features...compatibilit y with
existing control systems
Multiple size options...installation exibility
Yea r
1
SPECIFICATIONS
Input Power 12-35 VDC/ 12-28VAC , 200 mA Communication Modbus RTU, BACnet MSTP Output Scaled puls e, open drain Flow Calculation Accuracy ±2% of ow rate within range; ±5% repeatabilit y Temperature Sensors Meets IEC751 Class B Flow Range 1 to 15 FPS
Materials:
Housing Polycarbonate Flow Sensor PEEK Potting Material Polyurethane Tee Material Bronze
Environmental:
Fluid Temperature Chilled: -20° to 60°C (-4° to 140°F); Hot: 4° to 125°C (39° to 257°F) Ambient Temperature -20° to 65°C (-4° to 149°F)
800.354.8556
Warranty
+1 503.598.4564
www.veris.com
HQ00 01783.C 01131
800.354.8556
TEE/NP T Size A B C D E
2” (51 mm) 7.9” (201 mm) 8.5” (216 mm) 7.8” (197 mm) 3.3” (84 mm) 3.5” (89 mm)
1.5” (38 mm) 7.3” (185 mm) 8.3” (209 mm) 6.7” (170 mm) 2.75” (70 mm) 3.5” (89 mm)
1.25” (32 mm) 7.1” (180 mm) 8.1” (204 mm) 6.2” (158 m m) 2.4” (60 mm) 3. 5” (89 mm)
1” (25.4 mm) 6.7” (170 mm) 7.9” (201 mm) 5.4” (137 mm) 2” (51 mm) 3.5” (89 mm)
0.75” (19 mm) 6.7” (170 mm) 7.9” (201 mm) 5.4” (137 mm) 2” (51 mm) 3.5” (89 mm)
+1 503.598.4564
DIMENSIONAL DRAWINGS
www.veris.com
B
Overall Height
1/8” NPT
C
Tee Length
A
Overall Length
Side View
T1
RTD Fitting
D
Hex
T2
Length
6.6’ (2m)
Ø 0.2 “
(6 mm)
PG-7
Top View
E
Width
PG-9
Ø 8”
360˚ pivot area case
from center of tee
ORDERING INFORMATION
MODEL MANUF. PART # DESCRIPTION MAX. GAL/MIN (GPM)
U001-0098 380007000-1200*,** BTU system, cold service, ¾" tee NPT, with pulse, Modbus and BACNet outputs 25
U001-0099 380010000-1200*,** BTU system, cold service, 1” tee NPT, with pulse, Modbus and BACNet outputs 40
U001-0100 380012000-1200*,** BTU system, cold service, 1 ¼” tee NPT, with pulse, Modbus and BACNet outputs 70
U001-0101 380015000-1200*,** BTU system, cold service, 1 ½” tee NPT, with pulse, Modbus and BACNet outputs 95
U001-0102 380020000-1200*,** BTU system, cold service, 2” tee NPT, with pulse, Modbus and BACNet outputs 150
U001-0103 380107000-2202** BTU system, hot service, ¾” tee NPT, with pulse, Modbus and BACNet outputs 25
U001-0104 380110000-2202** BTU system, hot service, 1” tee NPT, with pulse, Modbus and BACNet outputs 40
U001-0105 380112000-2202** BTU system, hot service, 1 ¼” tee NPT, with pulse, Modbus and BACNet outputs 70
U001-0106 380115000-2202** BTU system, hot service, 1 ½” tee NPT, with pulse, Modbus and BACNet outputs 95
U001-0107 380120000-2202** BTU system, hot service, 2” tee NPT, with pulse, Modbus and BACNet outputs 150
U001-0114 A304-1M*** Programming Cable with CD for 380 Series n/a
* Consult factory for availability information. ** Requires programming accessory. *** Required to program 380 Series BTU meters (reusable). Standard USB type A to mini-B cable included. Software available from manufacturer’s website, www.badgermeter.com
HQ00 01783.C 01131
flow
Loading...