Ventmaster H4-25 Installation Manual

Water Wash Control panels
C O N T R O L P A N E L S
I n s t a l l a t i o n ,
O p e r a t i o n ,
M a i n t e n a n c e
a n d S e r v i c e
I n s t r u c t i o n s
Enodis
C O N T R O L P A N E L C O M P O N E N T
F U N C T I O N S
Water Shut Off Valves: There are two water shut-off valves on both the hot and cold water* lines, so that the components in both hot and cold water lines can be isolated for easy removal.
Pressure Reducing Valves: These valves are located in the hot and cold water* lines to reduce the operating pressure to 25 PSI (172 kPa).
Solenoid Valves: There is a solenoid valve in both the hot and cold water* lines to automatically control the water flow.
Detergent Pump: This pump is used to inject a controlled amount of detergent into the hot water line when in wash mode.
Timer Relay: This relay energizes both the hot water solenoid and the detergent pump for the wash cycle; it determines the length of the wash cycle.
Fuse Block & Terminal Strip: To provide a 5 amp fuse to protect the electrical components in the control panel.
Selector Switch:
a) To activate the exhaust fan and cold water* spray. for the Cyclo Maze
ventilation, turn switch to the ‘RUN’ position.
V E N T I L A T O R C O M P O N E N T
F U N C T I O N S
tions over the length of the ventilator. They are also removable to provide access to the chamber.
Water Spray Nozzles: There are both hot and cold water* spray nozzles.
Fire Damper: To prevent fire from going up the duct; the damper is held open by one 286°F (141°C) fusible link.
Volume Control Damper: A n a d j u s t a bl e, hori zontal bl a d e - t y p e damper is provided at the exhaust collar allowing for velocity changes in the field (after hood installations).
b) To activate the hot water wash cycle for the Cyclo Maze ventilator, turn
switch to the “WASH‘ position.
Cold Water Pressure Gauge: This gauge is used to check the cold water* pressure on the outlet side of the pressure reducing valve. Should read 25 PSI (138 kPa) while in operation.
Plug-Hot Water Line: This plug can be removed and a pressure gauge or thermometer screwed into the hole for field temperature and pressure reading.
Cold Water* and Hot Water Strainers: The strainers located in the PRV valve are used to strain out dirt from the water flow and to protect the solenoid valves and water nozzles from plugging up.
Detergent Pump CheckValves: This valve stops the detergent in the pump and tube from draining back down into the detergent tank when the pump is not in operation, eliminating the need to continually prime the pump.
2
*H4-25 models are not provided with the cold water feature.
I N S TA L L A T I O N I N S T R U C T I O N S
Models: HC4-25 and H4-25
S T A R T U P A N D
O P E R A T I N G
I N S T R U C T I O N
Location of control panel is determined by the kitchen equipment contractor. The recommended mounting height above the finished floor and type (recessed suffix ‘R’ or surface suffix ‘S’ mount) is indicated on the ventilator shop drawing.
RECESSED CONTROL PANEL
Recessed mounted models.The panel can be shipped early to allow cabinet to be built into wall. Fastening as per surface mount units.
See Drawing 1.
Drawing 1
Sequence of Operation
1.Turn selector switch to ‘RUN’
- Exhaust fan energized
- Make-up air fan energized
- Cold water turns on (HC4-25 only)
2.Turn selector switch to ‘WASH’
- Exhaust fan de-energized
- Make-up air fan de-energized
- Cold water turns off (HC4-25 only)
- Wash begins after 60 second delay
- Wash ends after preset time
3. Fire condition
- Switch at fire panel closes
- Exhaust fan stops
- Make-up air fan stops
- Cold water turns off (HC4-25 only)
- Hot water turns on
- Dry contacts at 15 and 16 close
SURFACE MOUNT CONTROL PANEL
Surface mounted models are shipped as a complete unit.The installer must drill holes in the back of the cabinet and component plate to suit wall structure and securely fasten panel to wall with lag or butterfly bolts.
See Drawing 2.
Drawing 2
Fire condition sequence of operation to be confirmed to apply to local codes.
3
A U T O M A T I C
C L E A N I N G
P R E S S U R E R E D U C I N G V A L V E
During the day grease accumulates in the interior chamber of the extractor unit in the water wash hood, there­fore, a cleaning cycle is provided to properly clean all interior surfaces.
When the selector switch is turned to the ‘WASH’ position at the control panel, the exhaust fan and cold water solenoid* are de-energized.After a 60 second delay (to allow the exhaust fan wheel to stop rotating), a pre-set wash timer energizes the hot water solenoid and detergent pump system for a short cleaning cycle. The hot water and detergent mixture is sprayed through a series of s t rategically placed nozzles to scour the interior of the unit.
CAUTION: If the cleaning cycle is not maintained, accumulated grease can constitute a fire hazard and impair the overall performance of the unit(s) and nozzles.
Hot and cold* water supply to the panel requires a minimum pressure of 40 PSI (276 kPa). Hot water requires a minimum temperature of 140°F (60°C). The pressure reducing valves are factory set for an outlet pressure of 25 PSI (172 kPa).The resulting pressure at the hood nozzle should be 20 PSI (138 kPa).If necessary, adjust the factory preset pressure reducing valve until the required pressure is obtained.
W A S H C Y C L E
Turn selector switch to the ‘WASH’position which will initiate the wash cycle and shut down fan and cold water spray. Check ventilator to see if hot water nozzles are functioning properly. After wash cycle has been completed, remove access door(s) and visually check to see if upper wash nozzles have a uniform spray pattern by observing water droplets on surface of upper chamber.
Remove and clean nozzle orifice if not spraying properly. Remove strainer enclosure on the pressure reducing valve in hot water line.Inspect and clean if necessary.
W A S H T I M E R
N OT E : After control panel and ventilator units have been installed, all hot and cold water* and drain connections made and electric connections completed and system has received factory authorized start­up, the system is ready to be put into operation.Refer to start-up check list.
R U N C Y C L E
Tu rn selector switch to the ‘ RU N ’ position, exhaust fan will start and cold water solenoid* will open. Check ventilators to see if cold water spray is functioning properl y. Place hand through slot opening in front of venti­lator. There should be an even flat, overlapping spray across the entire length of the ventilator.If nozzles are not spraying properly, remove and clean the ori f i c e. R e m ove access door in order to reach cold water n o z z l e. (See drawing 3). R e m ove strainer (enclosed on the pressure reducing va l ve in cold water line. Inspect and clean, if necessary.
*H4-25 models are not provided with the cold water feature.
A wash cycle of two minutes is preset at the factory. Under extreme conditions such as charcoal broiling or if hot water supply is located some distance from ventilators, it may be necessary to increase time cycle. It is suggested that this be done in one minute increments until proper time cycle is established.
Drawing 3
CYCLO MAZE WASH CHAMBER
4
P R I M I N G
D E T E R G E N T P U M P
C H E C K L I S T P R I O R T O S T A R T - U P
1. Loosen the plastic nut at the outlet of the detergent pump.
2. Cycle the detergent pump by t u rning the wing nut in a clock w i s e d i r e c t i o n .
3. Continue with step 2 until the detergent flows from the loosened nut, then tighten the nut.
D R A I N L I N E S
Ensure system is put through wash cycle at least daily with hot water and detergent. If detergent is not used or wash cycle ignored, drain line may become clogged.
NOTE: Before starting the control panel, the following should be checked:
Electrical
1. Connection to 120V, 60 cycle, 1 phase from main supply to the control panel, terminals #1 and #2.
2. Connection of 120V, 60 cycle, 1 phase from control panel, terminals #5 and #2, to exhaust fan magnetic starter coil.
3.Timer set for 2 minutes on HC4 models and 4 minutes on H4 models.
NOTE: Control panel wiring schematic located within control panel. Caution for proper system operation, the exhaust fan must be controlled by the water wash control panel.
Plumbing
1. Cold water (from supply) to the control panel.Note, not applicable to H4
models.
2. Hot water (from supply) to the control panel.
3. Connections for the above from the control panel to the ventilator(s).
4. Drain line and connections from the ventilator(s) to the drain.
5. Supply lines properly flushed before connection to control panel.
6. Strainers clean and free of foreign material.
7. Nozzles in hood properly oriented.
8. Nozzle orifice free of foreign material.
9. G-WIZ detergent bottle in place filled with detergent, complete with foot
valve inserted in bottle. Detergent bottle must be seated firmly on low liquid tray provided.
10. Detergent pump connected properly, primed and set for proper amount
of detergent.
11.Ventilator free of foreign material that would clog drain.
12. Cold water shut-off valve on and a setting of 25 PSI (172 kPa) on dial.
Note, not applicable to H4 models.
13. Hot water shut-off valve on and flow pressure setting of approximately 25
PSI (172 kPa) portable gauge check.
Other
1. Slot intake in hood open to proper width.
2. Exhaust duct connected properly.
3. Upper (wash) chamber doors properly closed. Note, applicable to Cyclo Wash series only.
4. Is hood hanging level and plumb?
5. Is fire damper fully open?
6. Is air volume control damper secured?
5
S T A R T - U P T E S T
1. Open stainless steel cover on control panel to expose plumbing.
2. Close both hot and cold water valves.
3. Turn selector switch to the ‘RUN’ position.
4. Check if ‘RUN’pilot light is on.
5. Is fan running?
6. Check velocity at slot opening (FPM). Note, refer to the ventilator shop
drawing for FPM slot velocities.
7. If within specified speed, turn hot and cold water valve on. (HC4-25
models only).
8. Adjust pressure reducing valve on cold water line to 25 PSI (172 kPa)
while water is running. (HC4-25 models only).
9. Check that all cold water nozzles are spraying properly by sliding hand
along slot area. (HC4-25 models only).
10.Turn selector switch to the ‘WASH’position.
11. Amber pilot light should come on.
12. Fan should shut off.
13. Cold water spray should shut off. Check again through slot areas. (HC4-
25 models only).
14. Insert gauge into hot water port provided. Hot water pressure gauge
should read 25 PSI (172 kPa) flow pressure while water running.
15.Visible hot water nozzles should be spraying in slot area.
16. Check detergent pump. Is it pumping detergent?
17. Is unit draining properly?
18. After wash cycle is complete, remove access panels.
19. Check upper hot water nozzles. They should still be dripping, if not,
remove nozzle and clean.
20. At end of wash cycle, did hot water shut off? All pilot lights are off.
6
M A I N T E N A N C E
A N D C A R E
I N S T R U C T I O N
HC4-25 with cold water spray and hot water wash cycle is 2 minutes average.
H4-25 with hot water wash cycle only is 4 minutes average.
N OT E : A clogged nozzle is an indicator that line strainers (located in the PRV) should be cleaned in control panel.
Quarterly
Clean interior and exterior of control panel. Clean all line strainers located in PRV valve.See Major Components drawings for exact location.
S E R V I C E I N S T R U C T I O N
The control panel consists of water shut-off valves, water pressure reducing valves, solenoid valves, detergent pump, relay timer, etc., as shown in Major Components drawings.
SOLENOID
The valves are two-way normally closed, internal pilot operated solenoid valve. The normally closed valve is closed when solenoid is de-energized and opens when solenoid is energized.
Coil Replacement
To replace the coil, turn off the electric power supply and close the water supply shut-off valve. Refer to Drawing 4. Proceed in the following manner:
1. Disconnect coil lead wires.
2. Remove retaining cap, name plate and cover. Caution:when retaining cap disengages, it will spring upwards.
Check detergent pump(s) for leaks or broken fittings during a wash cycle. ensure pump is primed and pumping.
Check solenoids for ‘click’when ‘RUN’ and ‘WASH’ switch is energized. See Major Components drawings fo r exact location.
3. Slip yoke containing coil, sleeves and insulating washers off the solenoid base sub-assembly.
4. Re-assemble in reverse order of disassembly, paying careful attention to exploded view in Drawing 4. The solenoid must be fully re-assembled as the housing and internal parts are part of, and complete the magnetic circuit.
5. Connect coil lead wires, open shut-off valves, turn on power and test valve.
Valve Disassembly
1. De-pressurize valve and turn off electrical power.
2. Disassemble valve in an orderly fashion.Pay careful attention to exploded view in Drawing 4 provided for identification and placement of parts.
3. Remove retaining cap and slip entire solenoid enclosure off the solenoid base sub-assembly. Caution: when retaining cap disengages, it will spring upwards.
4. Unscrew solenoid base sub-assembly, and remove bonnet gasket, core assembly and core spring.
5. Remove valve bonnet screws. Remove diaphragm assembly, diaphragm spring and damaged parts.
6. All parts are now accessible for cleaning or replacement. Replace worn or damaged parts.
7
Loading...
+ 15 hidden pages