Vent-Axia 405215, Advance S, 405216, Advance SX, 476808 Installation Instructions

...
Page 1
Advance MVHR
PLEASE REFER TO ACCOMPANYING DOCUMENTATION FOR INFORMAT
PLEASE PRODUCT
Stock Ref. N°
405215 Advance S 405216 Advance SX 476 476
808 Advance Sp LH 809 Advance Sp RH
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE COMMENCING INSTALLATION O R OPERATION.
RETAIN THESE INSTRUCTIONS WITH THE
.
ION SPECIFIC TO YOUR UNIT.
Copyright © 2017 Vent-Axia. All rights reserved.
Page 2
Warnings and Safety Information
• Do not install this product in areas where the following may be present or occur:
• Excessive oil or a grease laden
atmosphere.
• Corrosive or flammable gases, liquids or vapours.
• Subject to direct water spray from hoses.
• Ambient temperatures higher than 40°C
and lower than -20°C.
• Possible obstructions that may hinder access to or removal of the unit.
• All wiring must be in accordance with the current IEE wiring regulations BS7671, or appropriate standards of your country. Installation should be inspected and tested by a suitably qualified person after completion.
• Ensure the mains supply (voltage, frequency and phase) complies with the rating label.
• The unit should be provided with a local double pole fused spur fitted with a 3A fuse having a
contact separation of at least 3mm. If a unit fitted with a preheater is being installed, a 13A fuse should be used.
• These units must be earthed.
• Precautions must be taken to avoid the back-flow of gases into the building from the open flue of
gas or other fuel-burning appliances.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
• Young children should be supervised to ensure that they do not play with the appliance.
• The installer is responsible for the installation and electrical connection of the sentinel system on
site. It is the responsibility of the installer to ensure that the equipment is safely and securely installed and left only when mechanically and electrically safe.
• All regulations and requirements must be strictly followed to prevent hazards to life and property, both during and after installation, and during any subsequent servicing and maintenance.
• The unit’s condensate drain must be connected to the building’s wastewater drainage system.
• Certain applications may require the installation of sound attenuation to achieve the sound levels
required.
• The unit must not be connected directly to a tumble drier.
• The supply and exhaust valves must be fully opened prior to commissioning.
• The intake air must be drawn from the exterior of the property.
• The unit should be allowed to stabilise during commissioning for a minimum period of 5 minutes
when changing between boost and normal speeds.
• Ensure that the unit’s external grilles are a minimum of 1500mm apart. The exhaust grille should be located at least 600mm away from any flue outlet. The inlet grille should be located 2000mm away from any flue outlet.
• This product and associated duct installation should be carried out in accordance with the Domestic Ventilation Compliance Guide.
UK Building Regulations (Part F) Declaration of Conformance
The unit conforms to the 2010 Building Regulation (Part F - Means of Ventilation, F1(1), F(2)) requirem ents for fixed systems for mechanical extract fans when installed in accordance with the instructions in this document and the Domestic Ventilation Compliance Guide
2 MVHR Installation and User Guide 476930
Page 3
Operation and Monitoring 4
Product Description ....................................................................... 4
Controlling the unit......................................................................... 5
Touch screen display..................................................................... 5
Control via WiFi ............................................................................. 5
User controls ................................................................................. 6
Settings and Performance ............................................................. 7
Control Unit Screens Summary ................................................... 12
Control Unit Screens Summary ................................................... 13
Maintenance 14
Filter Maintenance ....................................................................... 14
Periodic Maintenance .................................................................. 15
Spares ......................................................................................... 16
Troubleshooting 17
Diagnosing a Problem ................................................................. 17
Installation 19
Overview ...................................................................................... 19
Wall Mounting the Unit ................................................................ 20
Floor Mounting the Unit ............................................................... 21
Floor Mounting the Unit (Alternate Method) ................................ 22
Vertical Discharge Condensate Installation ................................. 23
Attaching the ducting ................................................................... 24
Electrical Installation .................................................................... 25
Connect Switches and Sensors................................................... 26
Connect the Power Supply .......................................................... 28
Contents
Commissioning 29
Powering up the Unit ................................................................... 29
Overview ...................................................................................... 29
Control Unit Touch Screen Display ............................................. 29
Modifying Settings ....................................................................... 30
Commissioning Screens Summary ............................................. 31
Modifying Commissioning Settings ............................................. 33
Commissioning the Unit via USB................................................. 42
Accessories 43
Accessories ................................................................................. 43
WiFi Controller ............................................................................. 44
Input Switch Accessory ............................................................... 47
Switched Live Expansion PCB Accessory .................................. 49
Analogue Input PCB Accessory .................................................. 51
Wired Remote docking Kit Accessory ......................................... 53
Connecting an Opto-coupler ....................................................... 55
Remote LED Indicator and Lead Accessory ............................... 55
Flow Rate settings ....................................................................... 57
Frost Protection ........................................................................... 57
Summer Bypass Mode ................................................................ 58
Product Dimensions .................................................................... 59
Spares ......................................................................................... 60
Default settings ............................................................................ 61
Disposal ....................................................................................... 64
MVHR Installation and User Guide 476930 3
Page 4
Operation and Monitoring
Left Hand
Right hand
atmosphere
dwelling
atmosphere
atmosphere
Fit condensate drain
Fit drain cap
Fit drain cap
Fit condensate

Operation and Monitoring

Product Description

Mechanical Ventilation/Heat Recovery (MVHR). This heat recovery un it is designed for the energy
efficient ventilation of houses and s i milar dwellings, conforming to t he l atest requirements of the Building Regulations document F 2010.
The unit is designed for continuous 2 4 hour extract ventilation of stale moist air from bathrooms, toilets, utility rooms and kitchens. As the stale air is extracted, a heat exchang er within the unit transfers up to 93% of the extract air’s heat, into the supply air ent ering the bedrooms and lounge. This provides significant energy recovery, reducing household heat costs, and providing the optimum comfort conditions.
In addition, some models will have features that maintain a constant airflow independent of the blocked filters.
From
atmosphere
Extract from
To
Supply to
dwelling
Extract from
dwelling
From
Spigot
Filter drawers
Control panel
Supply to
dwelling
Spigot
Filter drawers
Control panel
To
drain with trap this
side.
Figure 1: MVHR with Left Hand and Right Hand spigot configuration.
Units with a preheater are preconfigur ed from the factory and the handing cannot be changed.
4 MVHR Installation and User Guide 476930
with trap this side.
Page 5
Operation and Monitoring
Controlling the unit
The unit can be controlled via t he Touch screen display, via WiFi, switche d i nputs, or via a third party building control system.
Touch screen display
The touch screen display can be located on the front of the unit or connected to the unit via a remote docking kit. The Control Unit provides the user interface for commissioning and monitoring purposes. The display is a resistive touchscreen with LED backlight, which will turn off to automatically after 5 minutes to minimise power consumption. To activate the backlight, touch the display.
User mode (Boost) button
Settings & Performance bar
Navigate through the functions by pressing the symbols, adjust settings using t he
buttons. A symbol indicates that there are further screens related to a menu option. Select the
option on the touchscreen to access the related screens.
Scroll Left
Status bar
Scroll Right

Control via WiFi

The MVHR WiFi control ler is a plug & play access ory that fits next to the control module. It allows the user instant access to commissioning, configuration, direct monitoring and control of the MVHR unit, using a smart phone or tablet with the app, available from the iTunes Store or on Google Play. See page 43 for App address.
MVHR Installation and User Guide 476930 5
Page 6
Operation and Monitoring

User controls

User Menu Home Screen
The user menu home screen, consists of a User Mode (BOOST) button, a Machine stat us bar, and a Settings / Performance bar.
The Machine status scrolls through Mode of operation, Summer bypass status and Frost protection status.
Press Settings / Performance to access these menus.
User Mode
Scroll through the pre-defined user modes (factory defaults are BOOST, LOW, and PURGE) using
the buttons either side of the User Mode button. Select the required func tion by pressing the centre button.
When a user mode is selected, selec t the duration by pressing the required button from the four options on the screen.
The button will appear white and the us er mode will flash. A countdown clock will also appear showing the time remaining for the selected User Mode.
Pressing the User mode button agai n will cancel the User Mode and the unit will default back to Normal mode.
6 MVHR Installation and User Guide 476930
Page 7
do not have editable parameters in this section.

Settings and Performance

Operation and Monitoring
Settings
Scroll through the settings using the & buttons and select using where applicable to
access Language, Date, Time, Res et filter, Display settings, Summer Bypass, Mode Sch eduling, Service phone, Commissioner M enu & D iagnostics.
Days Run and Filter check are reporte d values and
Performance
The performance menu shows key performance indicators such as recovered Temperature and Estimated power consumption.
Scroll through the list using the & buttons and select the required parameter.
Each performance temperature can be shown in Celsius or Fahrenheit by pressing the required temperature.
Date
Change the date using the / buttons on the screen.
MVHR Installation and User Guide 476930 7
Page 8
Operation and Monitoring
Time
Change the time using the / buttons on the screen.
Note: The clock is 24 hour
Clean/Replace Filter
After maintenance or replacement of the filters, the filter timer can be reset by press i ng NOW.
Press LATER to return to the Settings Menu.
Display Settings
Change the brightness of the touch screen using the / buttons.
Summer Bypass
See page 9 for a full description of the S ummer Bypass modes and functions
Select the required bypass mode.
The indoor temperature setting is the maximum desired room temperature. This s hould be set to 3° above the central heating temperature.
Change the indoor temperature usin g the / buttons on the screen.
8 MVHR Installation and User Guide 476930
Page 9
Operation and Monitoring
The outdoor temperature is the minimum air temperature that the bypass will permit. This is to prevent cold draughts.
Change the outdoor temperature using the / buttons on the screen.
This is the mode the bypass will switch to when activated.
The suggested Mode for Evening fresh and Night time fresh setting is Boost.
Scroll through the settings using the & buttons and select the Go To mode.
Note: Number of available modes may differ from image shown depending on bypass s etting and the modes set in the commissioning proces s.
Mode Scheduling
Use a schedule to set a Mode (Airflo w setting) for a fixed, repeated period. For exampl e, set Boost Mode every morning between 7:00am and 8:00am while cooking breakfast.
Select the Schedule to view the settings
Scroll through the settings using the & buttons and select the Go To mode for each Schedule.
Scroll through the days of the week us ing the &
the Schedule program.
buttons and select each day to be included in
MVHR Installation and User Guide 476930 9
Page 10
Operation and Monitoring
Adjust the start and finish times f or each day using the / buttons.
Silent Hours
Silent Hours mode is useful to impose a speed/flow restriction on the unit to minimise unwanted noise during the night.
If Silent hours are enabled, the unit will not speed up above the set Maximum Mode. Silent Hours can be set to reoccur on specific da ys and times.
Service Phone
The service phone number can be ent ered by the installer and should be used if the unit displays a fault code, or to arrange routine servi cing for the unit.
Commissioning Menu
Enter the lock code using the / but tons to access the Commissioner Menu.
Note: the lock code is set by the installer and settings beyond this point should o nly be accessed and modified by a qualified install er .
10 MVHR Installation and User Guide 476930
Page 11
Operation and Monitoring
Diagnostics
Scroll through the Diagnostics l ist using the &
buttons to access the following infor mation. Machine Status, Days Run, Filter Check, Bypass, Energy Consumption, Air flows, Opti on boards. Input status, Output Status, WiFi Status, WiFi signal.
Note: Optional upgrades may be neces sary to view all information.
MVHR Installation and User Guide 476930 11
Page 12
Operation and Monitoring

Control Unit Screens Summary

The following Control Unit screens are available for daily operati on and monitoring of the unit. Colour and visual appearance may be different to the below depending on model version and region.
Refer to next page for an
expanded version of
available screens in this
section.
12 MVHR Installation and User Guide 476930
Page 13
Operation and Monitoring

Control Unit Screens Summary

The following Control Unit screens are available in the Settings / P erformance section. Colour, vis ual appearance, and some features may be different to the below depending on model version and region.
MVHR Installation and User Guide 476930 13
Page 14

Maintenance

Maintenance

Filter Maintenance

Heat recovery units require regul ar maintenance. This unit has been designed to facilitate access to enable maintenance to be carried out easily.
When the unit displays “Clean or repl ace filters”. This is a reminder to ensure t hat the filters are not so dirty that they are blocking the airflow or allowing di r t to pass through. The rate at which the filters become dirty will vary hugely depending on the environment and the activity within the property.
See page 61 for a list of spare filters.
1. Open the filter drawers by pressing the finger plate upwards and sliding t he drawer out.
2. Lift each filter out and clean gently by tapping or carefully using a vacuum cleaner if necessary.
3. Replace the filters
4. Close the filter drawers, ensuri ng the latches have clicked back into the locked position.
5. After maintenance of the filters, the filter timer can be reset by going to
Settings/Performance, Clean/Replace filter.
14 MVHR Installation and User Guide 476930
Page 15
Fan Filters

Periodic Maintenance

THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING MAINTENANCE.
Maintenance
WARNING
Check fan filters as described on the previous page.
Heat Exchanger Cell
Step 1: Remove the outer cover by
pressing the tabs either side of t he c ontrol module and lifting the cover outwards from the bottom edge.
Step 2: Remove the inner door by undoing the 4 retaining screws.
Step 3: Slide the heat exchanger out from the unit.
Step 4: Wash the outer cover and heat
exchanger in warm water using a mild detergent (such as Milton Fluid) and dry thoroughly.
NOTE: Keep water away from all electrical components and wiring within the unit.
Motors
Inspect the motors for build-up of dus t and dirt on the impeller blades, which co ul d cause imbalance and increased noise levels. Vacuum or clean if necessar y.
Condensate Drain
Check the condensate drain tube is secure and clear of debris. Clean if necessary. Ensure the trap is fully charged with water.
Fastenings
Check that all unit and wall-mount fastenings are sufficiently tig ht and have not become loose. Re-tighten if necess ary.
MVHR Installation and User Guide 476930 15
Page 16
Maintenance

Spares

The following spare parts may be ordered from Vent-Axia:
Part No Description
472663 Main Power Board 472665 Control Module
472667 Filters G3, 2 per pack 472669 Filters M5, 1 per pack 472671 Filters F7, 1 per pack 472673 Motor Scroll Assembly 472675 Summer Bypass Motor Assembly
472685 Temperature/Humidity Sensor T1 (Right) 472679 Temperature Sensor T2 (Left) 472687 Temperature/Humidity Sensor T3 (Left) 472683 Temperature Sensor T4 (Right) 478335 Constant Volume + Clean Filter Pressure Sensors PCBA
Table 3: Spare parts
16 MVHR Installation and User Guide 476930
Page 17

Troubleshooting

Code
Problem

Diagnosing a Problem

In the event of a problem, always troubl es hoot the unit according to:
Warning code displayed on the control unit.
A warning code is advisory and will not i m mediately stop the function of t he unit.
Fault code displayed on the Control Unit. Fault LED if connected.
If no indications are displayed, then troubleshoot problem according to the fault symptom as described in the following tables.

Service/Fault Code Screens

Troubleshooting
The Fault Code notification is displayed, when a fault has occurred. Take note of the faul t code when reporting a fault.
For assistance contact the servic e pr ovider and quote the fault code number and the product serial number which can be found behind the front cover.
Note that the fault code is not displayed until the fault has been present f or 3 minutes.
The following fault codes numbers may be displayed.
Code numbers are added together if more than one fault is detected.
For example: Code 03 indicates that both left and right fans are not running.
01 Left Fan Fault 02 Right fan Fault 04 Left Thermistor Fault 08 Right Thermistor Fault 16 Left Centre Thermistor Fault 32 Right Centre Thermistor Fault 64 Left Centre Temp/Humidity Sensor Fault 128 Right Centre Temp/Humidity Sensor Fault
Table 4: Fault Codes
MVHR Installation and User Guide 476930 17
Page 18
Troubleshooting
Room Too Cold Screen
The Room Too Cold screen displays the status of the fan. If the heating system i n the building fails or is switched off and the internal temperature drops below 5°C, the unit will stop runnin g so as to not bring cold air into an already cold house. The unit will start up every hour and will run for a short tim e to measure the temperature of the property. When the temperature rises, e.g. the heating system is switched back on, the unit will restart and continue normal operation.
Bottom line of display may be (Fan Off, Fan Restarting).
18 MVHR Installation and User Guide 476930
Page 19

Installation

Installation

Overview

Before installation of the unit
We advise installers to fix all mains and sensor wiring along with any inter nal accessories prior to fixing the MVHR unit in position, leaving approximately 500mm tails to allow for internal routing.

Inspect the Unit

When taking delivery of the unit, check the items delivered against the enc l os ed delivery note. Inspect the unit for damage in transit. If in doubt, contact Customer Services. Each box cont ai ns a heat recovery unit, a wall brack et and accessory pack containing miscellaneous fixings and product documentation.
Unit Installation
Installation should be carried out by a suitably qualified and competent person. If the unit is wall mounted, the wall sh ould have sufficient strength to support the unit The unit may also be floor mounted, either directly to the floor or using standard kitchen cabinet feet (not supplied).
Ensure that the unit is mounted upright. Do not use this unit as a support for any other equipment.
Service Void

Clearance must be left around the unit to allow for cleaning and servicing, the dimensions below are the minim um requirements. The condensate drain trap used will dictate the necessary clearance below the unit which may be larger than the minimums.

Select Unit Configuration

The unit is configurable as either Left or Right Handed (Default), see page 4 for the spigot configuratio n. Use the left hand condensate drain for the Left Hand configuration, the right hand dr ain for the Right Hand configuration. If the unit is fitted with a preheater, the configuration is factory set and c annot be altered.
MVHR Installation and User Guide 476930 19
Page 20
Installation
Top of unit

Wall Mounting the Unit

Step 1: Mark the wall bracket position
using the dimensions shown. Note t he position of the top of the unit in relation to the wall bracket. Ensure the br ac ket position is horizontal.
Step 2: Attach the wall bracket to the wall using appropriate fixings.
Step 3: Lift the unit and locate the two hooks on the rear onto the wall bracket.
Step 4: Make sure the unit is level or leaning slightly backwards; this is to ensure the condensate drain functio ns correctly.
The mounting feet at the base of t he uni t are adjustable. From the factory, the mounting feet are set to compensate for the standoff caused by the mounting bracket. Adjust the feet in or out to level the unit as necessary.
20 MVHR Installation and User Guide 476930
If mounting on uneven walls, the spacers (A) may need to be removed before the feet can be screwed further into the unit.
Lock the mounting feet into their final position using the M6 nuts (B).
Page 21
Base fixing holes 11 x 4
7
Top of unit

Floor Mounting the Unit

Step 1: The unit has 44 x 12mm deep
fixing holes on the underside suitable for a No.6 screw. Pre drill a board using the dimensions shown, and cut 2 x 105mm minimum diameter holes for t he condensate drain access.
Step 2: Mount the board to the underside of the unit using appropriate fixings.
Installation
Note: Ensure any other cabling requirements (e.g. sensor, control cables etc) are routed through the two cable channels as required prior to attaching the board.
The board may then be attached to joists, flooring, or equivalent.
Vent-Axia recommend that where possible, the wall bracket is used in conjunction with any floor mount solution to prevent the unit from t ippi ng.
Step 3: Mark the wall bracket position using the dimensions shown. Note the position of the top of the unit in relation to the wall bracket. Ensure the bracket position is parallel to the floor.
Step 4: Attach the wall bracket to the wall or batten using appropriate fixings. (As shown on page 19)
Step 5: Lift the unit and locate the two hooks on the rear onto the wall bracket prior to fixing the unit to the floor. (As shown on page 19)
MVHR Installation and User Guide 476930 21
Page 22
Installation
7
Base fixing holes 11 x 4
Top of unit

Floor Mounting the Unit (Alternate Method)

Step 1: The unit has 44 x 12mm deep
fixing holes on the underside suitable for a No.6 screw. The holes are configured to allow fitment of most standard kitchen foot types (not supplied).
Step 2: Mount your chosen foot type to the underside of the unit using appropriate fixings.
Step 3: Adjust your chosen foot type to ensure the base of the unit is horizontal in both axis.
It is recommended that where possible, the wall bracket is used in conjunction with any floor mount solution to prevent the unit from tipping.
Step 4: Mark the wall bracket position using the dimensions shown. Note t he position of the top of the unit in relation to the wall bracket. Ensure the bracket position is parallel to the floor.
Step 5: Attach the wall bracket to the wall or batten using appropriate fixi ngs. (As shown on page 19)
Step 6: Lift the unit and locate the two hooks on the rear onto the wall bracket prior to fixing the unit to the floor. (As shown on page 19)
22 MVHR Installation and User Guide 476930
Page 23

Vertical Discharge Condensate Installation

Note
A trap must be fitted between the condensate drain of the unit and the rest of th e waste system. A waterless trap is recommended, as they are not susceptible to drying out during warmer periods
when no condensate is formed. An example of a suitable waterless trap i s t he Osma HepVo waterless trap.
If a conventional trap is used, a t rap with a minimum water seal of 60mm must be selected.
The condensate outlet is compatible with standard 22 mm plastic solvent weld fittings and 32mm threaded waste pipe fittings. Wastepipes must have a 3 degree minimum angle to allow the water to drain away from the unit naturally.
In areas where freezing weather cond i tions occur, outlet pipes must be insulated to avoid blockage by ice, which may cause damage to the unit and surroundings.
This guide shows a Right Hand configuration for illustration.
Installation
If the unit is configured as Left Hand, then the condensate drain should be installed on the left with the blanking cap on the right.

22mm waste pipe

Fit a waterless trap, or a conventional trap with a water seal of at least 60mm, close to the unit.
An adaptor can be used to adapt from 32mm to 22mm connections.
Fit the blanking cap supplied wit h the unit to the appropriate side, depending on the handing, see page 4. Ensure the sealing gasket is fitted inside the blanking cap.

32mm waste pipe (recommended)

Fit a waterless trap, or a conventional trap with a water seal of at least 60mm, close to the unit.
Fit the blanking cap supplied wit h the unit to the appropriate side of the unit, depending on the handing of the unit, see page 4. Ensure the sealing gasket is fitted inside the blanking cap.
MVHR Installation and User Guide 476930 23
Page 24
Installation
Compliance Guide

Attach the Ducting

1. Always use a short piece of insulated
flexible duct maximum 150 mm long, extended to its full length when connecting to ductwork.
2. Securely connect the ducting to the spigots using worm-drive clips or suitable plastic ties.
3. Insulate any ducting passing through an unheated space to prevent any heat losses or surface condensation.
4. Insulate all ducting to and from outside vents.
All ducting must be installed in accordance with the Domestic Ventilat ion
24 MVHR Installation and User Guide 476930
Page 25

Electrical Installation

THE ENSURE THE ELECTRICAL SUPPLY AND CONTROLS ARE ISOLATED FROM THE POWER SUPPLY BEFORE REMOVING ACCESS COVERS
Step 1: Remove the outer cover by
pressing the tabs either side of t he c ontrol module and lifting the cover outwards from the bottom edge.
Installation
WARNING
Step 2: Remove the control module by sliding it upwards and away from the uni t.
Step 3: Remove the two screws on either
side of the access panel. Lift the pane l outwards from the bottom edge to rem ov e.
Note: The access panel is tethered on the left hand side.
Note: All printed circuit boards are ESD sensitive. Always ensure the correct ESD protection is used (e.g. conductive wrist straps and anti-static mats.)
Step 4: Push the locking tab away from the printed circuit board and slide it outwards to access the terminals
Note: The printed circuit board will relock after 60mm
MVHR Installation and User Guide 476930 25
Page 26
Installation

Connect Switches and Sensors

The unit can be switched to boost by applying 240V to the LS input .

Note: Alternative switches and inputs can be achieved by adding optional input accessories to the printed circuit board. See Accessories on page 42 for further details.
For good EMC engineering practice, any sensor, switched live or Vo lt free cables should not be installed within 50mm of other cable or on the same metal cable tray as o t her cables.
Connect any switches or sensors r equired to control the unit by connecting to the terminal connectors at the bottom of the control unit as shown on the next page in Table 1. If necessary contact your distributor regarding the wiring and fixing of accessories and sensors.
When fitting external controls, all cables should be routed through t he two cable channels on the underside of the unit shown below.
Figure 4: cable channels
26 MVHR Installation and User Guide 476930
Page 27
Installation
May also be used for a connection to a BMS or similar.
Other means of connecting the
unit may be used if they meet
the local wiring regulations.
SEE NOTES ON THE NEXT
Terminal No. Name Description
REMOTE Remote Terminals for connecting a remote external to the unit. SWI Switch 1 Volt-free contact for sensor input between + and - terminals
LED Red Light Emitting Diode
DIAG Diagnostic Diagnosti c port USB USB C om missioning port. LS1 Switched Live 220-240 V AC, 50 Hz input NS1 Switched Neutral 220-240 V AC, 50 Hz input L Mains Live 220-240 V AC, 50 Hz input N Mains Neutral 220-240 V AC, 50 Hz input
EARTH Mains Earth Earth connector
PAGE
Output
A LED driving signal output bet wee n the + and – terminals that enables remote indication of a unit fault. See the Control Panel for fault code (see Service/Fault Code Screens on page 17
).
Table 1: Terminal Connections
MVHR Installation and User Guide 476930 27
Page 28
Installation

Connect the Power Supply

1. MAINS SUPPLY VOLTAGES (220-240 V AC) ARE PRESENT IN THIS EQUIPMENT, WHICH MAY CAUSE DEATH OR SERIOUS INJURY BY ELECTRIC SHOCK. ONLY A SUITABLY QUALIFIED PERSON SHOULD CONNECT THE POWER SUPPLY TO THIS UNIT.
2. THIS UNIT MUST BE CORRECTLY EARTHED.
This unit is designed for operation from a single-phase alternating current source (220-240 VAC). A 1.5m cable is connected internall y t o the unit for connection to an isolato r switch. To connect the power supply:
Ensure the local AC power supply is switched off. One end of the power cable supplied is already connected to the unit in the manner shown above. Connect the other end of the cable to the switched fused spur. Use cable clamps and clips to secure the cable, as appropriate.

Connecting a Boost (Light) Switch

WARNINGS
A Switched Live (LS1) may be used to boost the air flow when a light is turned on, for instance in a bathroom or kitchen. If the LS1 core of the mains cable is not used it should be terminated in an appropriate manner.
If the unit and the LS1 connection are on the same circuit, the jumper should be left between N and NS1 as shown above.

Connecting a Boost (Light) Switch from a different circuit

If the supply used for the Switched Liv e (LS) is on a different circuit to the power connections, the connections LS1 and NS1 should both b e connected to the same circuit. LS1 and NS1 are connected to the unit via a built in isolator and a separate isolating relay is not needed. The factory fitted link wire sh ould be removed.
28 MVHR Installation and User Guide 476930
Page 29

Commissioning

Powering up the Unit

Switching On

To switch the unit on:
1. Switch on the power at the mains supply isolator feeding the unit.
2. Following switch-on, the fan motors will start and the Control Unit will display a star t-up screen,
described on page 29.
N.B. If you are intending to carry out work or maintenance inside the unit, isolate the supply to the
unit before removing any covers.

Switching Off

To switch the unit off:
1. Turn the power off at the mains supply isolator.
SAP Compliance
The touch-screen controller consumes 0.5W when fitted to the unit and in standby mode. The SAP PCDB results are achieved with the touch-screen controller removed from the unit. For SAP compliance, remove the controller from the unit after commissioning and store in a safe place, See page 25.
Commissioning

Overview

The instructions in this section ar e i ntended to provide configuration and operation information for setting up the equipment. In the event of problems, see Diagnosing a Problem on page 17.
Follow good practice when commiss i oning the unit. Ensure that the system is installed according to the system designers intent incorporating any acoustic ducting, that all joints are air tight, ducting is well supported, bends are avoided clos e to vents, and that the vent valves are fully open at the start of the commissioning process.

Control Unit Touch Screen Display

The touch screen display can be located on the front of the unit or connected to the unit via a remote docking kit. The Control Uni t provides the user interface for c ommissioning and monitoring purposes. The display is a resistive touchscreen with LED backlight, which will turn off to automatically after 5 minutes to minimise power consumption. To activate the backlight, touch the dis play.
User mode (Boost) button
Scroll Left
Status bar
Scroll Right
Settings & Performance bar
Navigate through the functions by pressing the symbols, adjust settings using t he
buttons. A symbol indicates that t here are further screens related to a menu option. Select the
option on the touchscreen to access the related screens.
MVHR Installation and User Guide 476930 29
Page 30
Commissioning
up the unit for the first time.
menus.

Modifying Settings

If settings need to be changed after t he unit has been commissioned, access to the commissioning menu can be accessed by following the steps bel ow.
Start up screen
Every time the unit is powered up, the start up screen appears as the software loa ds showing the display version.
A Quick Start sequence will appear when powering
User Menu Home Screen
The user menu home screen, consists of a User Mode (LOW, BOOST, PURGE) button, a Machine status bar, and a Settings / Performance bar.
The Machine status scrolls through Mode of operation, Summer bypass status and Frost protection status.
Press ‘Settings / Performance’ to access the
Scroll down to ‘Commissioner menu’ using the
buttons at the bottom of the screen.
Enter the 4 digit lock code using the / buttons on the screen to access the commissioning menu. The default is 0000 and can be c hanged in the Modify Settings menu.
Press to enter the commissioning menu Press to return the settings menu
Press ‘Modify settings’ to enter the commissioning screens.
30 MVHR Installation and User Guide 476930
Page 31

Commissioning Screens Summary

The following pages show all available settin gs within the commissioning menu. Please note that some settings may not be available, or may be in a different order, due to pre-configuration by your distributer. A Quick Start sequence will appear when powering up the unit for the first time.
Commissioning
MVHR Installation and User Guide 476930 31
Page 32
Commissioning
32 MVHR Installation and User Guide 476930
Page 33

Modifying Commissioning Settings

Commissioning
Country
Select country – This will load any pre-determined national default parameters for all subsequent screens.
Language
Select language – The language choice does not affect the defaults setup by the count ry choice.
Load USB Settings
Settings can be automatically loaded to the unit via the USB port. Note: This option will only appear on the Quick Start sequence. Access to this screen can be obtained by using the Restore D efaults feature.
Date
The Date is pre-loaded as part of the f ac tory defaults, but may be changed if requir ed using the
/ buttons on the screen.
Time
The Time is pre-loaded as part of the factory defaults, but may be changed if requir ed using the
/ buttons on the screen.
Note: The clock is 24 hour
MVHR Installation and User Guide 476930 33
Page 34
Commissioning
menu.
intervals.
Unit configuration
Select the orientation of the unit dep ending on the configuration of the installation.
Units with a preheater are preconfigur ed from the factory and cannot be changed.
See page 18 for a description of t he uni t handing. Press to save and return to the commissioning
Filter Check
Select the time interval for checking the filters using the / buttons on the screen, between 1
month and 18 months. Note: There is an automatic filt er check notification
3 months after installation, irrespective of set
Service interval
Set the service frequency.
Reset Service Timer
After the unit has been serviced, use this option to reset the timer.
34 MVHR Installation and User Guide 476930
Page 35
Commissioning
Mode Names
The names and speed for each mode can b e changed if required.
Note: The user mode 1, Normal, is not editable.
Scroll through the settings using the & buttons and select the mode pre-set for each User mode.
Press to save and return to the commissioning menu.
User Mode
Adjust the supply and extract airflows for each mode pre-set. Select each mode to adjust to the required flow rate.
Adjust the airflows using the / buttons. Press to save and return to the commissioning
menu.
MVHR Installation and User Guide 476930 35
Page 36
Commissioning
specification.
Port Allocation
The unit will automatically detect the following inputs:
- Wired to the lighting
- Current sensors
- Momentary switch
Note: Number of available ports and port types may differ from image shown depending on unit
Select the Port to view the Go To Mode (speed setting), Delay and Over-run parameters.
Select the parameters to edit them.
Scroll through the settings using the & buttons and select the Go To mode for each Port Allocation.
Adjust the time delay for each Port Allocation using the / buttons. Selectable range is 0-20
Adjust the Over-Run for each Port Allocation using the / buttons. Selectable range is 0-30
36 MVHR Installation and User Guide 476930
Page 37
Commissioning
Summer Bypass
See page 59 for a full description of the Summer Bypass modes and functions
Select the required bypass mode.
The indoor temperature setting is the maximum desired room temperature. This should be set to 3° above the central heating temperature.
Change the indoor temperature usin g the / buttons on the screen.
The outdoor temperature is the minimum air temperature that the bypass will permit. This is to prevent cold draughts.
Change the indoor temperature usin g the / buttons on the screen.
This is the mode the bypass will switch to when activated.
The suggested Mode for Evening fresh and Night time fresh setting is Boost.
Scroll through the settings using the & buttons and select the Go To mode.
Note: Number of available modes may differ from image shown depending on bypass s etting and the modes set in the commissioning proces s.
MVHR Installation and User Guide 476930 37
Page 38
Commissioning
Internal RH Trip
The integral humidity sensor increases airflow speed in proportion to relative humidity levels. The sensor also reacts to small but rapid increases in humidity, even if the normal trigger threshold is not reached. The night time relative hum idity setback feature suppresses nuisance tripping as humidity gradually increases with falling temperature.
Scroll through the settings using the & buttons and select the required Go To mode.
Adjust the internal Relative Humidity using the / buttons. Selectable range is 60% - 90%.
Internal RH sensing can be switche d off by selecting “OFF”, this option is above 90%, or below 60%.
Control Mode
Select whether the unit should operate in Normal or Constant Volume mode.
38 MVHR Installation and User Guide 476930
Page 39
Commissioning
Frost Protection
Frost Protection is required to prevent condensate freezing in the heat exchanger at low temperatures. The process is fully automatic. T he method used for frost protection will depend on the model and building it is installed in.
For buildings with a leak rate of 3m 50Pa), a balanced frost protect i on mode must be used. A balanced mode must also be used when a combustion device without a dedicated air supply is present.
Airflow (Imbalanced)
Airflow mode reduces the Intake flow and increases the Extract flow in var ying proportions dependent on the incoming air temper ature. The unit will continue to recover heat as low as -20C. At this point, the unit switches to 'Extrac t Only' mode.
Bypass (Balanced)
Bypass mode opens the Summer Bypass an d stops recovering heat until the external temperature increases sufficiently.
3
/hr or less (at
Airflow & Preheater (Imbalanced)
If a preheater is fitted, the preheater will turn on to warm the incoming air to above freezing. If the air temperature is so low that the heater cannot warm the air sufficiently, the supply flow rate will be reduced to compensate.
Airflow & Preheater (Balanced)
If a preheater is fitted, the preheater will turn on to warm the incoming air to above freezing. If the air temperature is so low that the heater cannot warm the air sufficiently, both the su pply and extract flow rate will be reduced to compensate.
Relays
Select whether the external prehe ater outputs are activated. These outputs are 230V 5A m aximum each.
MVHR Installation and User Guide 476930 39
Page 40
Commissioning
Mode Scheduling
Use a schedule to set a Mode (Airflow setting) for a fixed, repeated period. For exampl e, set Boost Mode every morning between 7:00am and 8:00am while cooking breakfast.
Select the Schedule to view the settings
Scroll through the settings using the & buttons and select the Go To mode for each Schedule.
Scroll through the days of the week us ing the &
buttons and select each day to be included in
the Schedule program.
Adjust the start and finish times f or each day using the / buttons.
Silent Hours
Silent Hours mode is useful to impose a speed/flow restriction on the unit to minimise unwanted noise during the night.
If Silent hours are enabled, the unit will not speed up above the set Maximum Mode. Silent Hours can be set to reoccur on specific da ys and times.
40 MVHR Installation and User Guide 476930
Page 41
Commissioning
buttons.
screen.
return to the Commissioning Home sc reen
Service Phone
The Service Phone screen enables the installer to enter the telephone number that shoul d be called for service in the event of a unit fault or for routine maintenance.
Enter the number using the buttons on the screen, Scroll through the number using the
Set Lock Code
Set the lock code using the / but tons on the screen, press OK to save the code.
Note: Default code if not set at this point will be
0000.
Commissioner Menu
Once the commissioning settings have been modified exit to the commissioning menu.
Settings are stored in a non-volatile memory and will be retained irrespective of mains supply breaks, however, the unit can also be restored back to factory defaults at this scr een.
Press EXIT to return to the User Menu Home
To complete the setup process, pres s the EXIT button.
If a USB device is present, the settings from the unit can be saved and used for the setup of s i m i lar units.
Restore Defaults
To return the unit back to factory settings press the Restore Defaults button. A confirm ation screen will appear. Press YES to confirm, or CANCEL to
Once confirmed the following scr een will appear, the restore process takes approxim ately 5 seconds. Press CANCEL to stop the restore process during this time.
Once the system has restored back to fac tory default settings it will go back to t he s tart up screens.
MVHR Installation and User Guide 476930 41
Page 42
Commissioning

Commissioning the Unit via USB

When carrying out commissioning on multiple similar installati ons , commissioned settings may be downloaded and saved onto a USB at the end of the setup routine (see page 40). They can then be uploaded onto subsequent units saving time on site. The option to uplo ad the settings is available at the begi nning of the commissioning quick st ar t menu (see page 29 & 32).
No two systems are exactly the same and the settings and flow rates at eac h i ns tallation should be verified.
The USB does not have to be blank however only the most recent file will be read.
42 MVHR Installation and User Guide 476930
Page 43
Accessories

Accessories

Accessories

• WIFI Controller Accessory 409195 The WIFI controller is a plug & play acc essory that fits next to the Control module. This offers the user
instant access to various functions and features for direct monitoring and control of the unit using a smart phone or tablet via the Vent-Axia mobile application.
• Volt-Free Input Switch PCB Accessory 472697 The optional Input Switch Accessory offers four volt-free pairs of switch terminals to allow boosting f rom
manual switches or a full range of Vent-Axia controllers e.g. humidistats, PIRs and timers.
• Switched Live expansion PCB Accesso ry 472699
The optional Switched Live (LS) expansion accessory offers two extra switched live inputs (LS2 and LS3) for boosting via light switches (220-240V AC) or Normal/Boost switch. This connection has the advantage of Delay and Over-run features. Delay enables the prevention of boost airflow between 1-20 minutes. Over-run enables boost airflow to co ntinue after the light switch has been turned off between 1-30 minutes
• Analogue Input PCB Accessory 472701

The Analogue Input Accessory has t wo terminals with 0-10V inputs to allow proportional 0–10V control by sophisticated controllers such as CO2 sensors and proportional humidistats.

• Wired Remote Docking Kit Accessory 474491 The Controller Docking Kit has been d es igned to allow the Controller mo dule to be removed from the
MVHR & mounted remotely to either a single or double gang flush mount back -box of 25mm depth (min). The kit is supplied with a 15m lead and control panel cover.
• Opto-coupler Accessory 447340

The LED terminals are intended to driv e a remote LED to indicate that a fault has occurred.

• Remote LED Indicator and Lead Accessory 448356 Remote LED to indicate that there is a message in the control display.
Further information regarding these alternative control options i s available at the back of this document, Please contact your supplier for availabili ty in your region. Some accessories may be included as standard equipment depending on unit version, please check before ordering.
MVHR Installation and User Guide 476930 43
Page 44
Accessories

WiFi Controller

The WiFi controller is a plug & play accessory that fits next to the control module. It allows the user instant access to commissioning, configuration, direct monitoring and control of the MVHR unit, using a smart phone or tablet with the Vent-Axia Connect app, av ai labl e from the iTunes Store or on Google Play.
Device Compatibility
iOS
The app is compatible with the following iOS devices:
• iPhone 4s (or newer)
• iPod touch (5th generation or newer)
• iPad (3rd generation or newer)
Android
The app is compatible with most Android devices equi pped with Bluetooth 4.0 and running Android 4.3 (Jelly Bean) or later
Installation
Installation must be carried out by a competent per son. Installation may be carried out without removing power from the
unit, provided no screws are removed. Step 1: Remove the outer cover by pressing the tabs either
side of the control module and lifting the cover outwards from the bottom edge.
Step 2: Insert WiFi module into slot to the left of the touchscreen control module.
Step 3: The WiFi controller status LED illum i nates when the module is fitted correctly.
Step 4: Connect phone or tablet device to WiFi network using the AP SSID (network name) indicated on the WiFi co ntroller. Status LED will indicate green when connected.
Step 5: Use the app to connect to the unit, either using the phone camera, or entering the device name and security key indicated on the WiFi controller label .
Step 6: Replace outer cover.
.
• iPad mini
• iPad air
44 MVHR Installation and User Guide 476930
Page 45
Accessories
not configured to communicate online .
from the App.
device to the app.
of the label.
the WiFi controller.
Understanding the product label
AP SSID
The name of the wireless network hosted by the WiFi controller when it i s
DEVICE ID The name the WiFi module identifies as
when selecting a device to configure
SECURITY KEY The pass-phrase required to enable
secure communications with WiFi controller, required when adding the
RESET BUTTON A reset button is hidden behind this area
STATUS LED A tri-colour LED is placed behind this
area of the label, indicating the s tatus of
Resetting the WiFi Controller
A reset button is provided behind the label on the front of the WiFi Controller. It may be accessed by piercing the label with a small screwdriver in the position indicated on the label.
Short Press (< 5 seconds) A press less than 5 seconds shall toggle the WiFi controller between ‘Temporary AP’ and ‘WLAN’
modes (if the unit is configured for WLAN access ). Us e this if the WiFi status indicates ‘WiFi error’ to correct network settings.
Long Press (≥ 5 seconds) - Reset to fact ory defaults A press longer than 5 seconds shall put the WiFi cont roll er into ‘reset confirm’ state, with a fast red LED
flash. To confirm the intent to reset to factory defaults, press and hold the reset button for a further 5 seconds. The LED will change to solid red to confirm i t is res etting and will reboot when the button is released.
Supportsed Networks The WiFi controller supports IEEE 802.11 b/g/n networks at 2.4GHz using the following network
security:
• Open
• WEP
• WPA
• WPA2
MVHR Installation and User Guide 476930 45
Page 46
Accessories
Troubleshooting
LED Status Description Actions
Solid blue Slow blue flash Solid green Fast green flash
Solid yellow
Fast yellow flash
Slow red flash
Fast red flash
Solid Light Blue
Solid Purple
Solid Red
Initialising Connecting to a wireless network Connected to a wireless network Active communication with a connected
network WiFi controller is hosting a temporary
network, without a device currently connected
Active communication & weak signal
WiFi error (e.g. cannot connect to network)
Factory defaults reset confirm
Bootloader mode Should not appear in normal operation
Network controller update mode
Should not appear in normal operation
Communications fault between mainboard and WiFi controller
None - normal operation
Connect phone or tablet to the AP SSID (network name) indicated on the WiFi controller
Move existing or introduce additional WiFi access point closer to the MVHR unit.
Configure WiFi controller in temporary access point mode (see previous page) and correct network settings
See previous page regarding resetting the WiFi controller
Isolate power to the MVHR unit, wait 30 seconds and re-power the MVHR.
If this fault persists, contact your distributor support for further assistance.
Slow Flash - Red / Green
Internal fault on WiFi controller
46 MVHR Installation and User Guide 476930
Page 47
Accessories

Input Switch Accessory

WARNING
THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM
THE POWER SUPPLY DURING ANY MAINTENANCE AND WHEN FI T TING THIS
CONTROL MODULE.
The volt free Input Switch accessory board has four in put s for volt free contacts, allowing up to four independent switched inputs to be used.
Installation
1. Access the main printed circuit board following the electrical installation instruction in the “Installation & Commissioning” sections of this document.
2. Fit the three plastic stand-offs provided, into the three holes in the Input Switch PCB.
3. Fit the Input switch PCB to the main PCB in position shown.
MVHR Installation and User Guide 476930 47
Page 48
Accessories
4. Connect the lead from Input Switch PCB into the socket on the left hand side of the PCB marked “I/P VentWise”.
5. For cable routing from the switches into the unit, refer to the electrical installation instruction on page 25.
6. Connect the lead from each switch into the terminal block, one wire in the + and the other in t he -.
7. Before fitting the covers, note whi ch terminals have been used.
8. Replace the covers and turn it on.
9. Activate each switch input in turn to ensure functionality.
10. To adjust the speed for each input refer to the Installation & Commissioning sections of t hi s
document and go to the commissioning menu and f ol l ow t he steps to change speeds.
48 MVHR Installation and User Guide 476930
Page 49
Accessories

Switched Live Expansion PCB Accessory

WARNING
THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM
THE POWER SUPPLY DURING ANY MAINTENANCE AND WHEN FITTING THIS
CONTROL MODULE.
The LS2/3 accessory board has two independent LS (S wit ched live) inputs which can be connected to switches on different circuits to the power circuit of the MVHR unit.
Installation.
1. Access the main printed circuit board following the electrical installation instruction in the “Installation & Commissioning” sections of this document.
2. Fit the three plastic stand-offs provided into the three holes in the LS2/3 PCB.
3. Fit the LS2/3 PCB to the main PCB in positi on shown.
MVHR Installation and User Guide 476930 49
Page 50
Accessories
4. Connect the lead from LS2/3 PCB int o the so cket J21 shown below.
5. For routing the wires into the unit reference the electrical installation instruction on page 25.
6. From the required circuit, take the switched live and the neutral. Connect the switched live wire to the terminal marked LS2 and the neutral wire to t he t erm inal m arked NS2. For additional circuit use terminals LS3 and NS3.
7. Replace the covers and turn it on.
8. The LS2 & 3 input can be set up with delay on, over run and boost speed, refer to the Installation & Commissioning sections of this document to change settings.
9. After set up, test the LS input functi ons as required.
50 MVHR Installation and User Guide 476930
Page 51
Accessories

Analogue Input PCB Accessory

WARNING
THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM
THE POWER SUPPLY DURING ANY MAINTENANCE AND WHEN FITTING THIS
CONTROL MODULE.
The analogue input (I/O) PCB accessory has two 0-10V inputs for proportional sensors, and two 0-10V outputs for proportional dampers. Note: The pr oportional sensors and dampers require their o wn power supply.
Installation.
1. Access the main printed circuit board following the electrical installation instruction in the “Installation & Commissioning” sections of this document.
2. Fit the three plastic stand-offs provided into the three holes in the Analogue input PCB.
3. Fit the Analogue input PCB to the Mai n PCB in position shown.
MVHR Installation and User Guide 476930 51
Page 52
Accessories
4. Connect the lead from Analogue I/O PCB into the socket marked “Analogue I/O” shown bel ow.
5. For routing the sensor leads into the unit, reference the electrical installation instr uct ion on page 25.
6. For the siting of the Temperature, Humidity and CO2 proportional sensors refer to their
instructions.
7. For connecting proportional sensors, connect the ground (0V) from the sensor to the t erminal P1-
of Analogue board and the 0–10V signal from senso r to the terminal P1+ of Analogue board. For additional sensor repeat above using P2 terminal.
8. For the siting of the proportional dampers refer to their instructions.
9. For connecting proportional dampers, connect the ground (0V) from the damper to t he t erm inal
V1- of Analogue board and the 0–10V signal input from damper to the terminal V1+ of Analogue board. For additional sensor repeat above using V2 t erm inal .
10. To set up the speed, type and operating range, refer to the Installation & Commissioning sections
of this document to change settings.
11. After set up, test the inputs and outputs function as required.
52 MVHR Installation and User Guide 476930
Page 53
Accessories

Wired Remote docking Kit Accessory

WARNING
THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM
THE POWER SUPPLY DURING ANY MAINTENANCE AND WHEN FITTING THIS
CONTROL MODULE.
The Wired Controller Docking Kit is designed so that the Control Module on the MVHR unit can be mounted remotely. The Docking module is designed to fit a single or double gang flush mounting back box with a min. depth of 25mm.
The Kit contains the 1 x Docking module, 1 x 15m connection cable, 1 x blank cover and mounting screws.
Installation.
1. The main printed circuit board following the electrical installation instruction in the Installation & Commissioning sections of this document.
2. Site the Docking module at a height of 1.5m from the floor and within the distance of a 15m cable run from the kinetic Advance unit. Do not extend the cable provided.
3. Fit the Connection cable provided into the back box , feed the cable through to the MVHR unit with the plug in terminal connector end at the back box. A void routing cable alongside mains power cable.
4. To fit the Docking module to the back box, first remove the two screws, one either side.(1) Slide up the front fascia then press the two tabs at t he bottom.(2) This will release the 2 clips that are retaining the front fascia. You can now slide up the fas ica as far as it will go and lift it off the back section.(3) Fit the cable connector to the socket on the back section. Fit the back section to the back box by using two screws supplied with the back box. (4) Refit front fascia in reverse order of its removal.
MVHR Installation and User Guide 476930 53
Page 54
Accessories
Terminal ref - A
Black
Black
Terminal ref - B
White
Orange
Terminal ref - C
Green
Brown
Terminal ref - D
Red
Red
5. For routing the cable from the Docking module into the Kinetic Advance, reference the electrical installation instruction in the “Installation & Commissioning” document suppl i ed with your unit. The cable should be routed in on the left hand side of unit.
6. The cable is connected to the terminal block TB2 EXTE RNAL REMOTE/LED/SW1 at A, B, C and D terminals. The cable has one of two wire colour codes and should be connected in the order shown in the table below. (5).
7. To remove the display controller from the unit pus h up the units front panel. This will give you access to the controller. Remove the controller and repl ace it with the blanking cover provided.
8. Refit the front panel on the unit.
9. To fit the display controller to the docking module f irst ensure that the two side screws are
removed. Push the front fascia up until it stops. Ins ert the display controller module into the docking module. (6) Push down the front fascia to enga ge the display controller module with the contacts. (7) Refit both side screws (8).
10. Turn on the unit and check that the controller w orks.
54 MVHR Installation and User Guide 476930
Page 55
Accessories
Opto-coupler Accessory
WARNING
THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM
THE POWER SUPPLY DURING ANY MAINTENANCE AND WHEN FITTING THIS
CONTROL MODULE.

Connecting an Opto-coupler

The LED terminals are intended to drive a remote LE D t o indi cate that a fault has occurred. They provide a LED driving signal output between the + and – terminals that enables remote indication of a unit fault. See the Control Panel for fault code (See page 17). This signal could also be used by a BMS system so that its informed that a fault has oc curred. If a volt-free contact is required then use this opto-coupler to provide electri cal separation.
Connect the flying leads of the opto-coupler pcb i nto the LED terminals, + to + and - to ­Connect the pair of leads from the BMS to the terminal block of the opto-coupler pcb. Polarity does matter here.

Remote LED Indicator and Lead Accessory

The LED terminals are intended to dri ve a remote LED to indicate that ther e i s a message in the control display.
They provide a LED driving signal output between the + and – terminals that enables remote indication of filter check or unit fault. See the Control Panel for message (See page 17 f or fault codes).
Connect the 2 core flying lead fr om the Remote LED indicator terminal block. Terminal 1 on the Remote LED is + and terminal 2 is –
MVHR Installation and User Guide 476930 55
Page 56
Accessories
Connect the other end of the lead to the LED + &- terminals on the Kinetic unit PCB. Please ensure that the + goes to + and the – goes to -.
56 MVHR Installation and User Guide 476930
Page 57
Technical data
- Low
- Night time
- Normal (Unit default operating mode)
- Party
- Boost
- Unoccupied
- Purge
- Over pressure
- Holiday
- Fireplace

Flow Rate settings

The Sentinel Kinetic Advance has four (4) user defined speeds in addition to the non-adjustable Maximum speed. User defined speeds can be assigned a Mode name from the list below. (some opt ions may not be available in your
region)
Note: The flow rate for each mode is set independently and not defined by the m ode name. When setting up Over Pressure or F i r eplace Mode, the supply rate must b e set higher than extract rate. This is to
provide a positive internal press ur e i n the dwelling to assist with the initial expulsion of combustion products from the fireplace via the flue.
Fireplace mode does not prevent under-pressure Mechanical Ventilation with Heat Recovery (MVHR) systems are not designed to provide combustion air. NOTE: It is the responsibility of the open-flued appliance installer to ensure conformance with the curre nt local
building regulations for fuel bur ning appliances.

Frost Protection

Frost Protection is required to prevent condensate freezing in the heat exchanger at low temperatures. The process is fully automatic. The method used for frost protection will depend on the model and building it is installed in.
For buildings with a leak rate of 3m3/ hr or less (at 50Pa), a balanced frost prot ection mode must be used. A balanced mode must also be used when a combustion device without a dedicated air supply is present.
Airflow (Imbalanced)
Airflow mode reduces the Intake flow and increases the Extract flow in varying proportions dependent on the incoming air temperature. The unit will continue to recover heat as low as -20C. At this point, the unit switches to 'Extract Only' mode.
Bypass (Balanced)
Bypass mode opens the Summer Bypass an d stops recovering heat until the external temperature increases sufficiently.
Airflow & Preheater (Imbalanced)
If a preheater is fitted, the preheater will turn on to warm the incoming air to abov e freezing. If the air temperature is so low that the heater cannot warm the air sufficiently, the supply flow rate will be reduced to compensate.
Airflow & Preheater (Balanced)
If a preheater is fitted, the preheater will turn on to warm the incoming air to abov e freezing. If the air temperature is so low that the heater cannot warm the air sufficiently, both the supply and extract flow rate will be reduced to compensate.
MVHR Installation and User Guide 476930 57
Page 58
Technical data
The unit will run on the user selected Mode for 5-hours before reverting to Normal, unless cancelled

Summer Bypass Mode

The Sentinel Kinetic Advance inclu des a Summer Bypass (SBP) feature to bypass the heat exchanger to provide cooling when the desired I ndoor Temperature is above the ambi ent temperature.
Note that the volume of air provided by a ventilation system is a fractio n of that required for space heating or space cooling and will not in itself be sufficient to cool a room. It will however, provide a contribution.
Modes of operation
Bypass Mode Operation
Off Bypass feature is disabled
Normal The unit will run on Normal Mode, unless cancelled
Evening Fresh Night Time Fresh*
Bypass mode will operate when both the Indoor and Outdoor temperature thresholds are exceeded, and the outdoor temperature is below the in door temperature.
Indoor Temp: This is the maximum desired indoor temperature. A bove the set indoor temperature the summer bypass will operate.
Indoor temp should be set, 2-3°C higher than the central heating ther m ostat to prevent the bypass operating in winter, and 2-3°C lower than any air c onditioning thermostat if fi tt ed.
Outdoor Temp: This is the minimum allowed outdoor air temperatur e. The air temperature must be above this value for the Bypass to operate, use this value to prevent the bypass operating in winter.
The suggested Outdoor Temp, is 14°C, set as appropriate for your region.
Bypass mode will be cancelled when either:
- The internal air temperature drops below the Indoor Temp threshold, or
- The external air temperature drops b el ow the Outdoor Temp threshold
Note: Pressing the Boost button dur ing Evening Fresh and Night Time fresh operation will revert the unit to Normal bypass mode.
The unit will run at the user selected Mode, unless cancelled
It is recommended that the user select ed mode chosen for Evening Fresh and Night Time Fresh is higher than Normal flow rate to reduce the indoor temperature more rapidly.
*Night Time Fresh Mode is intended for use through the night when cooling is a higher priority than any increase of noise. Note, that the air noise in your system is influenced by flowrate, ducting design, layout and the size and type of vents used in the rooms. If improvements are required please c ontact your installer.
58 MVHR Installation and User Guide 476930
Page 59
(Label is positioned to the right of the controller).

Product Dimensions

Technical data
Figure 2: Dimensions
Remove front cover (see page 24) to view Rating l abel.
MVHR Installation and User Guide 476930 59
Page 60
Technical data

Spares

The following spare parts may be ordered from Vent-Axia:
Part No Description
472663 Main Power Board 472665 Control Module
472667 Filters G3, 2 per pack 472669 Filters M5, 1 per pack 472671 Filters F7, 1 per pack 472673 Motor Scroll Assembly 472675 Summer Bypass Motor Assembly
472685 Temperature/Humidity Sensor T1 (Right) 472679 Temperature Sensor T2 (Left) 472687 Temperature/Humidity Sensor T3 (Left) 472683 Temperature Sensor T4 (Right) 478335 Constant Volume + Clean Filter Pressure Sensors PCBA
Please note: If the grade of filter used in the unit is c hanged from what was initially supplied, the performance of the preheater may be
affected. An external preheater may be necessary depending on the specific installation and filter combination.
60 MVHR Installation and User Guide 476930
Page 61

Default settings

Commissioning Screens
Time
Mode Names
Low Supply/Extract
Control Mode
Service Phone
Boost Over-run
LS1/LS2/LS3
Parameters Settings
Country United Kingdom Language English. Date Automatic - Factory set
Unit configuration Right Hand Filter Check 12 months Summer Bypass Normal
User Mode Boost Supply/Extract 50 % Normal Supply/ Extract 30 %
Purge Supply/Extract 100% Internal RH Mode On Internal RH Setpoint 70%
Frost Protection Airflow Mode Mode schedule 1 All days set to 0:00 (on), 00:00 (off) – inactive Mode Schedule 2 All days set to 0:00 (on). 00:00 (off) – inactive
Set Lock code 0000 Indoor Temp 25 C Outdoor Temp 14 C
Boost Overrun set time 15 Boost Delay Off Boost Delay set time 00
SW1/SW2/SW3/SW4/SW5 User Mode 3 (Boost) Proportional 1/2 Humidity – Boost, Normal (60 %)
Technical data
Automatic GMT/BST - Factory set
Normal, Boost, Low, Purge
20%
Normal
Not Set
Off
User Mode 3 (Boost)
CO2 – Boost (2000 ppm), Normal (1000 ppm) Temperature – Boost (27ºC, Normal (17ºC)
Table 2 Default settings
The touch screen controller consum es 0.5 Watts in stand-by mode when fitted t o the MVHR unit. If required this controller may be removed from the unit and stored s eparately, further minimising t he overall energy consumption.
MVHR Installation and User Guide 476930 61
Page 62
Technical data
Name:
Vent-Axia
SEC Class
A+
SEC Value ('Average')
-43.03
SEC Value ('Warm')
-17.88
SEC Value ('Cold')
-87.71
Label Required? (Yes/No=Out of scope)
Yes
Declared as: RVU or NRVU/UVU or BVU
RVU/BVU
Speed Drive
Variable Speed
Type HRS (Recuperative, Regenerative, None)
Recuperative
Thermal Eff: [ (%), NA(if none)]
89
Max. Flow Rate (m3/h)
378
Max. Power Input (W): (@Max.Flow Rate)
190
LWA: Sound Power Level (dB)
56.0
Ref. Flow Rate (m3/s)
0.07350
Ref. Pressure Diff. (Pa)
50
SPI [W/(m3/h)]
0.25
Control Factor & Control Typology: (CTRL/ Typology)
Control Factor; CTRL
0.65
Control Typology
Local Demand Control
(for regenerative heat exchangers only),
-&Ext. Leakage Rates (%) for Ducted UVUs;
connection on either supply or extract air side;
performance and energy efficiency of the unit
For UVUs (Instructions Install Regulated Supply/Extract Grilles Façade)
N/A
Internet Address (for Disassembly Instructions)
www.vent-axia.com
Sensitivity p. Variation@+20/-20 Pa: (for Non-Ducted VUs)
N/A
Air Tightness-ID/OD-(m3/h) (for Non-Ducted VUs)
N/A
Annual Electricity Consumption: AEC (kWh/a) pr. m²
1.75
Annual Heating Saved: AHS (kWh/a) pr. m²
AHS: Average
46.73
AHS: Warm
21.13
AHS: Cold
91.41
Product fiche
Model ID (Stock Ref.) :
405215 Advance S
405216 Advance SX
476808 Advance Sp LH
476809 Advance Sp RH
Declared: -Max Internal & External Leakage Rates(%) for BVUs or carry over
Mixing Rate of Non-Ducted BVUs not intended to be equipped with one duct
Position and description of visual filter warning for RVUs intended for use with filters, including text pointing out the importance of regular filter changes for
<5% Internal, <5% External
N/A
Refer to User Instructions
62 MVHR Installation and User Guide 476930
Page 63
MVHR Installation and User Guide 476930 63
Page 64
Head Office: Fleming Way, Crawley, West Sussex, RH10 9YX.
EU Authorised Representative: Vent
UK NATIONAL CALL CENTRE
SALES ENQUIRIES: TECHNICAL SUPPORT
476930N 0521

Disposal

This product should not be disposed of with household waste. Please recycle where facilities exist. Check with your local authority for recycling advice.
The  Guarantee
Applicable only to products installed and used in the United Kingdom. For details of guarantee outside the United Kingdom contact your local
Vent-Axia guarantees its products for two years from date of purchase against faulty material or workmanship. In the event of any part being found
to be defective, the product will be repaired, or at the Company’s option replaced, without charge, provided that the product:-
• Has been installed and used in accordance with the instructions given with each unit.
• Has not been connected to an unsuitable electricity supply. (The correct electricity supply voltage is shown on the product rating label
attached to the unit).
• Has not been subjected to misuse, neglect or damage.
• Has not been modified or repaired by any person not authorised by the company.
IF CLAIMING UNDER TERMS OF GUARANTEE
Please return the complete product, carriage paid to your original supplier or nearest Vent-Axia Centre, by post or personal visit. Please ensure
that it is adequately packed and accompanied by a letter clearly marked “Guarantee Claim” stating the nature of the fault and providing evidence of
date and source of purchase.
The guarantee is offered to you as an extra benefit, and does not affect your legal rights
supplier.
-Axia Bedrijvenweg 17 7442 CX Nijverdal Nederland [email protected]
, Newton Road, Crawley, West Sussex, RH10 9 JA
Tel: 0344 8560590 Fax: 01293 565169
: Tel: 0344 8560594 Fax: 01293 539209
64 MVHR Installation and User Guide 476930
Loading...