•Zener barriers are used in control and instrumentation
systems for the processing of standardised signals, such as
20 mA and 10 V. Zener barriers contain intrinsically safe
circuits that are used to drive intrinsically safe field devices
within hazardous areas. The manufacturers data sheets
must be consulted.
•The relevant regulations and directives governing the
intended application must be observed.
Installation, commissioning
•Zener barriers are constructed to a protection classification
of IP20 and accordingly must be appropriately protected
from adverse conditions such as splashing water and soiling
in excess of pollution severity 2.
•Zener barriers must be installed outside the hazardous area!
Only those circuits identified as intrinsically safe may be
located within the hazardous area.
•When intrinsically safe field devices are interconnected with
the intrinsically safe circuits of the related Zener barriers, the
respective highest values (safety parameters) for the field
devices and the Zener barriers - in the sense of explosion
protection - must be observed (demonstration of intrinsic
safety). The EU certificate of conformity or EU prototype test
certificate must be followed. Particular importance is
attached to maintaining the "Special conditions" contained
in these certificates.
•When intrinsically safe circuits are employed in an explosive
dust atmosphere (zones 20 and 21), only appropriately
certificated field devices are permitted to be incorporated.
Installation and commissioning within zone 2
•The devices must be installed in switch boxes or distributor
boxes to protection category IP54 or better.
•The devices may be installed within zone 2. Only those
circuits identified as intrinsically safe are permitted to be
installed in zone 1 or zone 0 and in accordance with their
ignition protection category approval. The actual installation
of the intrinsically safe circuits is to be carried out in
accordance with the applicable installation regulations.
•When interconnecting intrinsically safe field devices with the
intrinsically safe circuits of the associated Zener barriers,
the respective highest values (safety parameters) of the field
device and the associated device, in the sense of explosion
protection, must be taken into account (demonstration of
intrinsic safety). The conditions stated on the EU certificates
of conformity or EU prototype test certificates must be
observed.
•In addition, for operation within zone 2, the statements of
conformity of the certifying authorities/declarations of
conformity of the manufacturer must be observed. Particular
importance is attached to maintaining the "Special
conditions" contained in these certificates.
•When intrinsically safe circuits are employed in an explosive
dust atmosphere (zones 20 and 21), only appropriately
certificated field devices are permitted to be incorporated.
Servicing and maintenance
The transmission characteristics of the devices remain stable
over long periods, so that regular adjustments or other
precautions are not required. This also means that no
maintenance work is required.
Fault elimination
No modifications may be made to devices that are operated in
connection with hazardous areas. Repairs must only be carried
out by specially trained and authorised personnel.
1.1Operating principle
The Zener diodes in the barriers are connected in the reverse
direction. The breakdown voltage of the diodes is not
exceeded in normal operation.
Hazardous areaSafe area
Resistor
R1
Zener diodes
Figure 1.1 Circuit diagram
ZD1
ZD2 ZD3
If this voltage is exceeded, due to a fault in the non-Ex-area,
the diodes start to conduct, causing the fuse to blow, thus
preventing the transfer of unacceptably high energy into the
hazardous area.
Terminals 7 and 8 are connected to the devices in the nonhazardous area. The single condition that these devices must
satisfy, is that they must not contain a source whose potential
relative to earth is greater than 250 V/253 V
253 V DC.
Fuse
F1
AC or 250/
eff
Terminals 1 and 2 are connected to the intrinsically safe
circuits in the hazardous area. If they are used in the
hazardous area, active intrinsically safe apparatus must be
certificated unless the electrical values of such apparatus do
not exceed any of the following values: 1.5 V; 0.1 A; 25 mW.
Pepperl+Fuchs Zener barriers are identified in terms of
voltage, resistance and polarity, e. g. 10 V, 50 Ohm, positive
polarity. These figures correspond to the Zener voltage U
and
z
the total resistance of all barrier components. They therefore
represent the safety values. The values stated on the type
identification label correspond to the "worst case" data for
U
) and Ik(Io) determined during certification.
z(Uo
I
is obtained by dividing Uz by the resistance R1. It should be
k
noted once again, however, that these values do not
correspond to the operating range of the Zener barrier.
Ideally, Zener diodes would not allow any current in the reverse
direction until the Zener voltage has been attained. In practice,
Zener diodes do allow a small leakage current, the value of
which increases as the applied voltage is increased.
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
1
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 2
Zener barriers - operating instructions
Operating principle
The operating range of a Zener barrier must therefore be such
that it is below the Zener voltage, so that the leakage current is
restricted to a minimum. Zener barriers are normally tested to
ensure that at the prescribed voltage the leakage current is
smaller than 10 µA.
Hazardous area Safe area
50 mA
Load
Figure 1.2 This figure shows a selection of leakage currents through
the Zener barriers under normal circumstances. The
Zener barriers conduct a maximum of 10 (1) µA leakage
current so long as the supply voltage is less than 25.5 V.
This is normal and has very little effect on the load. If the
voltage exceeds 25.5 V, the Zener diodes start to
conduct more current. This can have an effect on the
operating current and the accuracy. It is therefore
recommended that a controlled voltage source be used,
which maintains the voltage under the value at which the
diodes will start to conduct.
(A 24 V, 300 Ohm barrier is represented here as an
example)
10 µA
24 V
Power
supply
(+)
25.5 V
≤
(-)
These voltages are stated in the data sheet for a given barrier,
together with the leakage current. If the leakage current for a
given voltage differs from 10 µA, this is specifically stated.
Hazardous areaSafe area
50 mA
Load
Figure 1.3 This figure shows that if the maximum permissible input
(supply) voltage is exceeded, the total current drains
through the Zener diodes, without reaching the explosive
surroundings.
24 V
Power
supply
(+)
25.5 V
>
(-)
Pepperl+Fuchs Zener barriers have a low series resistance,
given by the sum of the resistance R1 and the resistance value
of the fuse F1. Due to the low series resistance, an inadvertent
short-circuiting of terminals 1 and 2 can cause the fuse to blow.
In order to avoid this, some barriers are available with
electronic current limitation (CL-version).
If the Zener barriers are provided with a resistance, this limits
the short-circuit current to a safe value in the event of a shortcircuit of the connecting wiring in the hazardous area or a
connection to earth of the wiring attached to terminal 1, as the
fuse blows.
Many barriers are available with a resistance connected
between the output terminals. These are used in
4 mA … 20 mA transmitter circuits. The resistance converts
the current in the intrinsically safe circuit into a voltage that can
be measured in the safe area.
Pepperl+Fuchs Zener barriers can be used in many
applications. In the simplest case, a single channel barrier with
a ground connection is used. But in many applications it is not
desirable that the intrinsically safe circuit is connected directly
to ground. If the circuit in the safe area is grounded, under
some circumstances grounding of the intrinsically safe circuit
can lead to faults within the system. In this case, quasi groundfree intrinsically safe circuits can be constructed with two or
more barriers. This floating circuitry can be simply achieved
with 2- or 3-channel barriers.
Double grounding of intrinsically safe circuits is not permitted.
The insulation voltage of the wiring and field devices,
measured with respect to ground, must be greater than
500 V AC. The permissible ambient temperature of the Zener
barriers is between -20 °C … 60 °C.
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
2
Page 3
Zener barriers - operating instructions
y
Multi-channel barriers
1.2Multi-channel barriers
Analogue circuits are often connected to two-channel barriers
(see Figure 1.5). Since there is no grounding on this type of
circuit, the system is a quasi floating one. It is termed "quasi
floating", because it is "one Zener voltage" above the ground
potential. Although it does not actually float, the signal-to-noise
ratio is improved.
A further advantage of multi-channel Zener barriers is that a
higher packing density can be achieved.
.
Hazardous area
4 mA ... 20mA
transmitter
Safe area
(+)
24 V
R
M
Power supply can
not be grounded.
Figure 1.4 Single-channel Zener barrier
1.3Grounding of Zener barriers
Intrinsically safe circuits with Zener barriers without galvanic
isolation must be grounded. The cross-section of the ground
connection, using a copper conductor, must be at least 4 mm
(for further details see EN 60079-14, section 12.2.4). The
maintenance of these requirements prevents the occurrence of
a dangerous potential with respect to ground.
A fault of the type illustrated in figure 8.6 can cause a
dangerous spark if the Zener barrier is not grounded, but
grounding is provided via the field device in the intrinsically
safe circuit (Figure 1.5). If a potential occurs in the fault case,
which is higher than permitted (see Figure 1.6) the Zener
diodes become conducting and the current is conducted away
via the ground. The fuse "blows".
.
Hazardous area
4 mA ... 20mA
transmitter
Figure 1.5 Two-channel Zener barrier
2
Safe area
(+)
24 V
R
M
Hazardous
Safe area
area
Hazardous potential
Hazardous potential
Figure 1.6 Non-grounded Zener barrier
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
3
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
AC/DC
supply
voltage
Fault
Power suppl
Transformer
Hazardous
area
Safe area
Fault
Power supply
Transformer
Fault current
Intrinsically
safe ground
Figure 1.7 Grounded Zener barriers
The system must have its own independent ground
conductor, through which no supply system current
flows.
Date of issue05/23/03
Page 4
1.4Installation notes
Pepperl+Fuchs Zener barriers in the Z7, Z8 and Z9 series can
be mounted on a standard rail to EN 50022 in 3 different
arrangements.
•Equipotential bonding via the standard rail (grounding of all
snapped-on Zener barriers)
Insertion strip
ZH-ES/LB
Label carrier
ZH-Z.BT
DIN rail NS 35/7.5
35 mm standard rail
to DIN EN 50 022
Clamp
ZH-Z.USLKG5
Figure 1.8 Equipotential bonding via the standard rail
Pepperl+Fuchs Zener barriers also feature a space-saving
12.5 mm housing which incorporates up to 3 channels.
11012.5
115
Figure 1.11 Mechanical features
Construction: Modular terminal housing in Makrolon,
flammability classification UL 94: V -0
Fixing: Snaps onto 35 mm standard rail to DIN EN 50022
Connection options: Self-opening terminals, max. core cross-
section 2 x 2.5 mm²
The barriers are usually installed in racks or control cabinets.
They can be built into housings under production conditions,
with the proviso that the housing must afford adequate
protection. They can also be employed in hazardous areas,
when it has been ascertained that the housing has been
certificated for this purpose.
The installation must be carried out in such a way that the
intrinsic safety is not compromised by the following factors:
•Danger of mechanical damage
•Non-authorised changes or influence exerted by external
personnel
•Humidity, dust or foreign bodies
•Ambient temperature exceeding the permissible level
•The connection of non-intrinsically safe circuits to
intrinsically safe circuits
Grounding of the mounting rail is of the normal type, i. e. both
ends are connected to the intrinsically safe ground. This also
simplifies checking the grounding.
Many installations provide the option of subsequent expansion.
Replacement cable for this purpose can be connected to the
Z799 dummy barrier and unused cable can be connected to
the intrinsically safe ground.
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
4
Page 5
Zener barriers - operating instructions
Zener barrier specifications
1.5Zener barrier specifications
Nominal data
The following are typical data used in the description of a
barrier:
28 V, 300 Ohm, 93 mA. These values relate to the maximum
voltage, the minimum value of the built-in resistance and the
resulting maximum current.
The maximum voltage stated is not representative of the
operating range, it is the maximum value that can be attained
in a failure case, before the fuse responds. The resistance
value is not identical to the maximum series resistance. These
values merely provide an indication of the maximum values
that can apply in the case of a failure.
Series resistance
This is the resistance that can be measured between the two
ends of a barrier channel. It is obtained from the sum of the
resistance R and resistance value of the fuse at an ambient
temperature of 20 °C.
Polarity
Zener barriers are available in various versions. On Zener
barriers for positive polarities the anodes of the Zener diodes
are grounded. On barriers for negative polarities it is the
cathodes which are grounded. On barriers for alternating
polarities, interconnected Zener diodes are employed and one
side is grounded. These can be used for both alternating
voltage signals and direct voltage signals.
Maximum voltage in the intrinsically safe circuit. (U
This is the maximum value of voltage that can occur in the
intrinsically safe circuit in the failure case.
Maximum current in the intrinsically safe circuit (Ik)
)
z
This is the maximum current that can flow in the intrinsically
safe circuit in the failure case.
Maximum input voltage (max. U
)
in
The maximum voltage (correct polarity) that can be applied
between the contacts in the safe area and the ground without
the fuse responding. This value is determined for an open
intrinsically safe circuit and an ambient temperature of 20 °C.
Input voltage (Uin at 10 (1) µA)
The maximum voltage (correct polarity) that can be applied
between the contacts in the safe area and the ground at a
defined leakage current (as a rule 10 µA). This is the upper
value of the recommended operating range.
Maximum connectable external capacitance C
max
This is the maximum capacitance that can be connected to the
terminals of the barrier intrinsically safe circuit. This value is
determined from the sum of the wiring capacitance and the
input capacitance of the field device.
Maximum connectable external inductance L
max
This is the maximum inductance that can be connected to the
terminals of the barrier intrinsically safe circuit. The value is
determined from the sum of the inductance of the wiring and
the input inductance of the field device.
Note:
The designations of the values given in the specifications
above are not those of the relevant standards, but those
specified on certificates of conformity (e. g. in EN 60079-14,
Section 3, IK is now IO).
1.6How to select the correct barrier
For very many applications the standard solutions are given in
this catalogue, in the section on Example Applications.
However, in the event that a particular application has not been
covered, the following information may be helpful.
1. First decide whether it will be necessary to have a floating
circuit, or whether the intrinsically safe circuit can be
connected directly to ground. Check whether any existing
instrumentation is grounded. If the answer is yes, then
check whether additional grounding could lead to faults.
Bear in mind that the floating circuit offers a better commonmode rejection characteristic than the grounded circuit. On
the other hand, it is more expensive. If a floating circuit is
employed, the barriers will normally resist a ground fault.
2. Select the required polarity. This is either determined by the
circuit itself, or by any other existing grounds in the circuit. In
most applications barriers for positive polarities are used. In
order to achieve greater system standardisation, barriers
suitable for alternating polarities can be used in place of
unipolar ones.
3. Decide the nominal voltage of the Zener barrier. Then
determine the maximum output voltage of the device in the
safe area during normal operation. Normally the required
value is the next highest nominal voltage of a Zener barrier.
If these values are close together, it could be that the
recommended operating range of the Zener barrier is
exceeded. The consequence of this is that the leakage
current will be greater than 10 µA. In this case a barrier with
a higher nominal voltage should be used. The leakage
current is determined for an open intrinsically safe circuit
and this then represents the maximum value at the given
voltage.
4. Take account of the maximum series resistance of the
Zener barrier and its effect on the intrinsically safe circuit.
Make sure that this resistance does not cause an
inadmissibly high loss of voltage. In circuits having high
resistance - usually when voltage signals are being
transferred - this resistance is not relevant. If for example a
barrier has a max. series resistance of 1 kOhm, then the
resulting error is 0.1 %, if the input resistance of the
connected device is 1 MOhm.
5. Check whether or not the field device must be certificated for
use in the hazardous area. If certification is necessary,
check what the prerequisites are for permitting the field
device to be used in connection with a Zener barrier.
6. What is the overall length of the cabling between the voltage
supply and the field device? Note the number of conductors
in the system!
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
5
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 6
7. The following points have to be clarified if special field
devices are used.
•If the field device is a 4 mA ... 20 mA transmitter: What load
in ohms can be connected to the transmitter so that it can
attain 20 mA as before?
•If the field device is a current/pressure converter: What load
can be connected to the controller card so that it can attain
20 mA as before?
•If the field device is a transmitter: How high is the load in the
safe area? (typically, resistances of up to 250 Ohm are used
in the controller)
Z ...
Zener barriers - operating instructions
How to select the correct barrier
Barrier with replaceable back-up fuse
The introduction of a replaceable back-up fuse ahead of the
integrated fuse provides protection against faults which could
occur during the commissioning of the system. It is always
Type
Channels
Z715.F11061313.610063217,063
Z728.F132727288050217,05
Z728.H.F125027288050217,05
Z765.F2106
Z779.F2327
Z779.H.F2250
Z787.F2327
Z787.H.F2250
Z960.F264
Z961.F2106
Z966.F2166
Max. series
resistance
OhmVVmAmA
106
327
250
36 + 0.9V
25 + 0.9V
64
106
166
Uin
at 10 µA
13
13
27
27
27
27
27
27
27
27
6.5
6.5
6.5
6.5
10
10
arranged that the outer fuse will respond before the inner,
innaccessible fuse. The fuses used are specially intended for
use on barriers.
Uin
max
13.6
13.6
28
28
28
28
28
28
28
28
9.5
9.5
8.1
8.1
11.7
11.7
Fuse ratingExternal fuseFuse supplied
100
100
80
80
80
80
80
80
80
80
80
80
160
160
100
100
63
63
50
50
50
50
50
50
50
50
50
50
100
100
63
63
by LITTLEFUSE
217,063
217,05
217,05
217,05
217,05
217.05
217.1
217.063
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
6
Page 7
Zener barriers - operating instructions
How to select the correct barrier
TypeNominal dataEx-characteristics for [EEx ia] IICCertification no.
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
7
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 8
Zener barriers - operating instructions
How to select the correct barrier
Max.
end-to-end
resistance
WVVmA
18.18
18.18
56
56
63 + 2 V
2913.714.6160
107
119
107
1025
1025
166
327
250
338
261
342 + 2 V
327
18.18
18.18
–
18.18
18.18
–
15.5
15.5
–
106
106
–
113
380
–
380
380
–
1033
1033
–
1033
1033
–
U
in
at 10 µA
0.9 (1 µA)
0.9 (1 µA)
6.5
6.5
6.5
13.0
13.0
13.0
13.0
13.0
19.0
26.5
26.5
26.5
26.5
26.5
26.0
0.9 (1 µA)
0.9 (1 µA)
–
0.9 (1 µA)
0.9 (1 µA)
–
6.0
6.0
–
6.5
6.5
–
6.5
6.5
–
6.5
6.5
–
10.0
10.0
–
10.0
10.0
–
U
max
4.8
4.7
8.9
9.3
8.9
13.6
13.8
14.0
13.6
14.0
20.1
28.0
28.0
28.0
28.0
28.0
27.6
4.8
4.8
–
4.7
4.7
–
6.9
6.9
–
8.1
8.1
–
8.0
8.1
–
8.1
8.1
–
11.0
11.0
–
11.7
11.7
–
in
Fuse rating
250
250
100
100
100
100
63
100
100
100
50
50
80
50
50
50
50
250
250
–
250
250
–
200
200
–
100
100
–
100
50
–
50
50
–
50
50
–
50
50
–
see circuit
diagram No.
1), 2)
3)
1), 2)
3)
1), 2)
1), 2)
3)
3)
1), 2)
1), 2)
1), 2)
Hazardous areaSafe area
connectionsconnections
1)
18
CL
x3
27
+VE type
2)
18
CL
x3
27
-VE type
3)
Circuit diagram
1), 2)
3)
4), 5)A1
6)A1
18
x3
x3
27
AC type
4)
18
x3
x3
6
4), 5)
6)
27
3
45
+VE type
5
)
18
27
6)
3
45
4), 5)A1
-VE type
x3
x3
6
6)
6)A1
18
27
x3
x3
see note 2
A2
B
A2
B
A1
A2
B
A1
A2
B
A1
A2
B
A1
A2
B
A2
B
A2
B
107
107
–
119
119
–
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
13.0
13.0
–
13.0
13.0
–
13.6
13.6
–
13.9
13.9
–
100
100
–
63
63
–
4), 5)A1
3
45
AC type
x3
x3
6
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
A2
B
A1
A2
B
8
Page 9
Zener barriers - operating instructions
How to select the correct barrier
TypeNominal dataEx-characteristics for [EEx ia] IICCertification no.
+ ve- vea.c.VWUz (V) R
––Z9661212150
1501212
24
–
–
Z966.F
12
12
150
150
12
12
24
–
–
Z966.H
12
12
75
75
12
12
24
Z772Z872–2222150
1502222
22
Z778
Z878
–
28
28
600
600
28
28
28
Z779
Z879
–
28
28
300
300
28
28
28
Z779.H
Z879.H
–
28
28
240
240
28
28
28
Z779.F
Z779.H.F
Z879.F
Z879.H.F
–
–
28
28
28
28
300
300
240
240
28
28
28
28
(W) IK(mA) P
min
147
147
73.5
164
147
147
73.5
73.5
73.5
36.5
147
147
73.5
164
164
164
328
150
150
300
607
607
303.5
301
301
150.5
235
235
117.5
186
119
119
238
301
301
235
235
120
120
82
82
82
82
46
46
93
93
93
93
93
max
0.24
0.24
0.48
0.24
0.24
0.49
0.49
0.49
0.98
0.82
0.82
1.64
0.32
0.32
0.65
0.65
0.65
1.3
0.83
0.83
1.67
0.65
0.65
0.83
0.83
(W) C
(µF) L
max
max
1.41
1.41
0.125
1.41
1.41
0.125
0.17
0.17
no approval for IIC
0.083
0.083
0.083
0.083
0.083
no approval for IIC
0.083
0.083
no approval for IIC
0.083
0.083
0.083
0.083
(mH) L/R Ratio
5.52
5.52
1.38
1.38
1.38
0.33
1.45
147
147
57
75
75
36
4545BAS 01 ATEX 7005
1.45
17.2
17.2
3.05
3.05
3.05
1.82
1.82
4.21
4.21
2.59
2.59
109
109
42
56
56
44
44
55
55
44
44
BAS 01 ATEX 7005
BAS 01 ATEX 7096
BAS 01 ATEX 7005
BAS 01 ATEX 7005
BAS 01 ATEX 7005
BAS 01 ATEX 7005
BAS 00 ATEX 7096
BAS 01 ATEX 7096
Z796Z896–26.6
Z788
Z788.H
Z788.R
Z888
Z888.H
–
–
–
–
Z786Z88628
Z787
Z787.H
Z787.F
Z787.H.F
Z887
Z887.H
Z887.F
Z887.H.F
–
–
–
–
20.5
28
10
28
10
28
10
28
28
28
28
28
28
28
28
28
28
320
415
300
50
240
50
300
50
Diode
Diode
Diode
300
Diode
240
Diode
300
Diode
240
Diode
26.6
20.5
26.6
28
9.56
28
28
9.56
28
28
9.56
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
314
407
177
301
49
42
235
49
40
301
49
42
Diode
Diode
Diode
301
Diode
301
235
Diode
235
301
21.8
301
235.2
14.7
235.2
85
50
135
93
195
288
119
195
314
93
195
288
0
0
0
93
0
93
119
0
119
93
Diode
93
120
Diode
120
0.56
0.26
0.82
0.65
0.47
0.87
0.83
0.47
1.0
0.65
0.47
0.87
0.0
0.0
0.0
0.65
0
0.65
0.83
0
0.83
0.65
0
0.65
0.83
0
0.83
0.094
0.204
0.094
0.083
3.0
0.083
0.083
3.0
0.083
0.083
3.0
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
5.14
14.6
2.05
3.05
0.86
0.32
1.82
0.86
0.26
3.05
0.86
0.32
–
–
–
3.05
–
3.05
2.82
see note 1
2.82
4.21
–
4.21
2.59
–
2.59
64
BAS 01 ATEX 7005
138
34
56
BAS 01 ATEX 7005
73
26
44
BAS 01 ATEX 7005
73
25
56
BAS 01 ATEX 7005
73
26
–
BAS 01 ATEX 7005
–
–
56
BAS 01 ATEX 7005
–
56
44
BAS 01 ATEX 7005
44
BAS 01 ATEX 7096
55
–
55
BAS 01 ATEX 7096
44
–
44
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
9
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 10
Zener barriers - operating instructions
How to select the correct barrier
Max.
end-to-end
resistance
U
in
at 10 µA
U
max
in
Fuse rating
WVVmA
166
166
–
169
169
–
82
82
–
166
166
–
646
646
–
327
327
–
250
250
–
338
338
264
264
340
437
–
327
64
–
250
64
–
327
64
–
36 + 0.9 V
36 + 0.9 V
–
327
36 + 0.9 V
–
250
25+ 0.9 V
–
338
46+ 0.9 V
–
264
39+ 0.9 V
–
10.0
10.0
–
10.0
10.0
–
10.0
10.0
–
19.0
19.0
–
26.5
26.5
–
26.5
26.5
–
26.5
26.5
–
26.5
26.6
26.5
26.5
24.0
18.0
–
26.5
6.5
–
26.5
6.5
–
26.5
–
–
26.5
26.5
–
26.5
26.5
–
26.5
26.5
–
26.5
26.5
–
26.5
26.5
–
11.7
11.7
–
11.9
11.9
–
11.7
11.7
–
20.1
20.1
–
28.0
28.0
–
28.0
28.0
–
28.0
28.0
–
28.0
28.0
28.0
28.0
25.1
19.5
–
28.0
9.1
–
28.0
9.1
–
28.0
9.1
–
28.0
28.0
–
28.0
28.0
–
28.0
28.0
–
28.0
28.0
–
28.0
28.0
–
50
50
–
63
63
–
100
100
–
50
50
–
50
50
–
50
50
–
80
80
–
50
50
50
50
50
50
–
50
50
–
80
80
–
50
50
–
50
50
–
50
50
–
80
80
–
50
50
–
50
50
–
see circuit
diagram No.
6)
6)
4), 5)A1
4), 5)
4), 5)
4), 5)
Hazardous areaSafe area
connectionsconnections
4)
18
27
3
45
+VE type
5
)
18
27
3
45
-VE type
x3
x3
x3
x3
6
6
6)
18
27
3
45
AC type
x3
x3
x3
x3
6
7)
Circuit diagram
18
4), 5)A1
4), 5)
4), 5)
27
3
45
AC type
All diodes are turned 180˚
for the -VE version.
x3
x3
6
8)
7)
8)A1
9)
18
27
3
45
All diodes are turned 180˚
for the -VE version.
x3
x3
6
9)
9)
18
27
3
45
All diodes are turned 180˚
for the -VE version.
x3
x3
6
see note 2
A1
A2
B
A1
A2
B
A1
A2
B
A2
B
A1
A2
B
A1
A2
B
A1
A2
B
A2
B
A1
A2
B
A1
A2
B
A1
A2
B
A2
B
A1
A2
B
A1
A2
B
A1
A2
B
A1
A2
B
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
10
Page 11
Zener barriers - operating instructions
How to select the correct barrier
TypeNominal dataEx-characteristics for [EEx ia] IICCertification no.
+ ve- vea.c.VWUz (V) R
–
–
––Z9651515100
––Z9671717120
––Z9722222300
––Z9782828600
––Z9544.5
–
–
Z960
Z960.F
10
10
10
10
4.5
4.5
50
9.94
50
9.94
9.94
50
9.94
50
9.94
9.94
1001515
15
16.8
120
16.8
16.8
3002222
22
6002828
28
12
4.5
12
4.5
12
4.5
9.0
9.0
9.0
(W)IK(mA) P
min
49
49
24.5
98
49
49
98
98
49
117
117
58
301
301
150
607
607
304
11.76
11.76
11.76
5.88
3.92
17.64
203
203
406
203
203
406
153
153
306
143
143
286
73
73
146
46
46
93
383
383
383
765
1150
510
max
0.50
0.50
1.0
0.51
0.51
1.02
0.57
0.57
1.14
0.60
0.60
1.20
0.40
0.40
0.80
0.32
0.32
0.65
0.43
0.43
0.43
0.86
1.29
1.15
(W) C
max
3;0
3;0
3;0
2.63
2.63
2.63
0.58
0.58
0.58
0.38
0.38
0.38
0.17
0.17
0.17
0.083
0.083
0.083
100
100
100
4.9
4.9
4.9
(µF) L
(mH) L/R Ratio
max
0.86
0.86
0.19
0.82
0.82
0.82
1.3
1.3
0.29
1.63
1.63
0.24
6.95
6.95
1.45
17.2
17.2
3.05
0.24
0.24
0.24
0.068
0.03
0.12
73
BAS 01 ATEX 7005
73
26
69
BAS 01 ATEX 7096
69
25
64
BAS 01 ATEX 7005
64
20
60
BAS 01 ATEX 7005
60
21
90
BAS 01 ATEX 7005
90
35
109
BAS 01 ATEX 7005
109
42
81
BAS 01 ATEX 7005
81
81
41
27
30
Dummy
Z799
11
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 12
Zener barriers - operating instructions
How to select the correct barrier
Max.
end-to-end
resistance
WVVmA
64
64
–
–
75
75
115
115
–
136
136
–
327
327
–
646
646
–
U
in
at 10 µA
6.5
6.5
–
–
6.5
6.5
13.0
13.0
–
15.0
15.0
–
19.0
19.0
–
26.0
26.0
–
U
max
9.5
9.5
–
–
9.7
9.7
14.2
14.2
–
16.2
16.2
–
20.9
20.9
–
27.6
27.6
–
in
Fuse rating
50
50
–
–
50
50
50
50
–
50
50
–
50
50
–
50
50
–
see circuit
diagram No.
10)
Hazardous areaSafe area
connectionsconnections
10)
Circuit diagram
18
27
3
10)A1
10)A1
45
11)
x3
x3
6
18
x3
10)A1
36
x3
2
7
x3
10)A1
45
see note 2
A1
A2
B
A1
A2
B
A2
B
A2
B
A2
B
A2
B
27.27
27.27
27.27
–
–
–
0.9 (1 µA)
0.9 (1 µA)
0.9 (1 µA)
–
–
–
4.9
4.9
4.9
–
–
–
50
50
50
–
–
–
Note 1:
Zener barriers type Z787H and Z887H have channels with
diode returns.
The Ex-terminals for the channels with diode returns should be
regarded as 28 V voltage sources.
The 28 V must be considered as the theoretical maximum up
to which a capacitive load can be applied to the Ex-terminals
due to the leakage current of the diode return. This voltage is
only used in calculating the load capacitance.
11)A1
A2
A3
18
27
3
6
45
Note 2:
A1, A2 and A3 are separate channels.
B: Two channels in parallel circuit with a ground connection.
C: Two channels in series circuit without a ground return.
B
B
C
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
12
Page 13
Zener barriers - operating instructions
Application examples
1.7Application examples
Temperature measurement
Hazardous area
Not grounded
The simplest and most favourably priced solution is a singlechannel Zener barrier. It should be noted, however, that the
1
CL
2
Hazardous area
1
2
3
4
Safe area
Z705
8
x3
7
Temperature
monitoring
or control
device is not grounded in the safe area. The system is
approved for [EEx ia] IIC.
Safe area
Z960
8
x3
x3
x3
7
6
5
Temperature
monitoring
or control
The use of a two-channel barrier prevents the direct ground
connection of the intrinsically safe circuit. Grounding only takes
place in the event of a fault, when the Zener diodes conduct.
Hazardous area
1
2
3
4
1
2
3
4
Z961
Z961
This circuit arrangement prevents the occurrence of mutual
interference between the various circuits. The system is
approved for [EEx ia] IIC.
Safe area
8
x3
x3
x3
x3
x3
x3
x3
x3
7
6
5
V
8
7
6
5
The illustration shows the set up for a temperature
measurement with a 4-wire Pt100. None of the 4 wires is
connected directly to ground. The complete system is therefore
"quasi ground-free".
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
13
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
This is the best option when the intention is to suppress the
influence of the end-to-end resistance of the barrier on the
measuring accuracy as far as possible.
Date of issue05/23/03
Page 14
Temperature measurement
Zener barriers - operating instructions
Application examples
Hazardous area
Z954
1
3
2
4
The circuit arrangement shows the connection of a Pt100 in 3wire technology, using the 3-channel Zener barrier Z954. The
whole system is quasi ground-free. All 3 barriers have identical
Hazardous area
1
2
3
4
Z961
Safe area
8
x3
x3
x3
x3
x3
x3
6
7
Test circuit
5
end-to-end resistances, so that the resulting error is restricted
to a minimum. The system is approved for [EEx ia] IIC.
Safe area
8
x3
x3
x3
x3
7
6
5
Z954
1
3
2
4
Z954
1
3
2
4
The circuit consists of a system of a maximum of seven
Pt100s. The Pt100s are connected in series to a constant
current source. Each voltage signal is transferred to a receiver
via a Z954.
8
x3
x3
x3
x3
x3
x3
x3
x3
x3
x3
x3
x3
6
7
5
Receiver with
galvanically
isolated inputs
8
6
7
5
The Z954s have been selected due to their high end-to-end
resistance. Due to the high input resistance of the receiver, the
high end-to-end resistance has practically no effect on the
accuracy of measurement.
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
14
Page 15
Zener barriers - operating instructions
Application examples
0 mA … 20 mA/4 mA … 20 mA transmitter
Hazardous area
Z728
1
CL
2
If a ground-free power supply is available, the use of a singlechannel Zener barrier, grounded in the safe area, represents
the simplest and most economical solution. The ammeter can
be used in combination with a recording instrument, a trip
amplifier, or a 250 Ohm resistance, or replaced by these
devices. In so doing, the overall resistance of the arrangement
must be taken into account. The working range of the barrier
Hazardous area
Z788
1
2
Safe area
8
x3
7
A
caters for an input voltage of up to 27 V. For each built-in
250 Ohm resistance the output voltage of the power supply
can be increased by 1 V. By using a 250 Ohm resistance and a
supply voltage of 28 V, a source of 16.5 V at 20 mA is available
to the transmitter in the hazardous area. The internal voltage
drop across the barrier is then 6.5 V. The system is approved
for [EEx ia] IIC.
Safe area
8
x3
7
3
4
With this 2-channel Zener barrier, it is possible to supply a
number of circuits with one source. All the wiring is quasi
ground-free. The maximum voltage supply is 27 V. The internal
voltage drop across the barrier is 7.8 V at 20 mA, so that
19.2 V are available for the field device and ammeter. If the
6
x3
5
A
ammeter for converting the current signal into a 1 V … 5 V
voltage signal is replaced by a 250 Ohm resistance, then
14.2 V are available at the field device. The system is
approved for [EEx ia] IIC.
15
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 16
0 mA … 20 mA/4 mA … 20 mA transmitter
Zener barriers - operating instructions
Application examples
Hazardous area
Z788.R
1
2
3
4
This system can be used if the field device requires a relatively
high voltage. A 250 Ohm resistance is connected in parallel
with the Ex-output of the 10 V/50 Ohm output of this 2-channel
Hazardous area
Z787
1
2
3
4
x3
Safe area
8
x3
x3
7
6
5
V
barrier. Thus a voltage of 15.5 V is available at the field device
if the voltage supply is 27 V. The system is approved for
[EEx ia] IIC.
Safe area
8
x3
x3
7
6
5
A
The combination of a 28 V, 300 Ohm and a 28 V barrier with
diode return is the solution for applications with 3-wire
transmitters. Special attention must be paid here to the internal
voltage drop. The reason for this is the diode return. The
system is approved for [EEx ia] IIC.
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
16
Page 17
Zener barriers - operating instructions
Application examples
SMART transmitter
Hazardous area
Z787
1
2
3
4
The simplest possible solution is the use of a 2-channel Zener
barrier with 28 V, 300 Ohm and 28 V diode return. If a
regulated power supply unit provides an output voltage of 27 V,
13.9 V will be available to the transmitter and wiring in the Exarea.
Strain gauge bridges
Hazardous area
1
2
Z966
Safe area
8
x3
x3
7
6
5
A
The data transfer is bidirectional, so that a non-certificated
communicator can be connected and used in the the safe area.
The system is approved for [EEx ia] IIC.
Safe area
8
x3
x3
7
3
4
1
2
3
4
1
2
3
4
Z964
Z964
x3
x3
x3
x3
x3
x3
x3
x3
x3
x3
6
5
8
7
6
5
8
7
6
5
+
-
Signal
The strain gauge bridge is supplied via the Z966. The Z966
enables a 350 Ohm strain gauge bridge to be supplied with
8 V. The voltage feedback via the Z964 can be dispensed with,
although in practice most applications require this feedback to
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
17
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
obtain the best possible accuracy of measurement.
The millivolt signal is transferred to the safe area via the Z964.
The system is approved for [EEx ia] IIC.
Date of issue05/23/03
Page 18
Wire strain gauges
Zener barriers - operating instructions
Application examples
Hazardous area
350 Ohm
350 Ohm
Z966
1
x3
Z966
Z964
x3
x3
x3
x3
x3
x3
x3
x3
x3
x3
x3
2
3
4
1
2
3
4
1
2
3
4
8
7
6
5
8
7
6
5
8
7
6
5
Sensor +
Sensor -
-0+
Safe area
350 Ohm
1
2
3
4
Z964
If more than one strain gauge bridge is to be supplied from a
common power supply (in the example shown above there are
three), a possible solution is to supply them via two Z966s, as
shown.
8
x3
x3
x3
x3
7
6
5
Both channels of these Zener barriers are arranged in parallel
in order to reduce the end-to-end resistance. This arrangement
provides 8 V to the bridges if the voltage supply is 20 V. The
system is approved for [EEx ib].
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
18
Page 19
Zener barriers - operating instructions
Application examples
Potentiometric position detection
Hazardous area
1
2
3
4
Applications in which the accuracy is not critical can be
satisfied as shown above. The intrinsically safe circuit has a
direct connection to ground. An additional resistance on this
Harzardous area
1
x3
Z715
CL
Safe area
Z960
8
x3
x3
7
6
5
V
side would have an effect on the voltage signal and would have
to be taken into account. The system is approved for [EEx ia]
IIC.
Safe area
8
x3
2
Z715.1K
1
CL
x3
2
Z715.1K
1
CL
x3
2
7
8
7
Signal
8
7
If greater accuracy is required, a 4-wire solution must be
applied. The Z715 Zener barrier transfers the power supply to
the potentiometer, whilst two Z715.1K barriers transfer the
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
19
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
signal to the receiver. The supply voltage in the example above
could be 13 V.
Date of issue05/23/03
Page 20
Solenoid valves
Zener barriers - operating instructions
Application examples
Hazardous area
Z728
1
CL
2
The simplest and most economical solution is a single channel
Zener barrier, with the power supply grounded on its safe side.
If the valve requires 30 mA at a minimum 12 V, then at a
Hazardous area
Z787
1
4
3
2
Safe area
8
x3
7
supply voltage of 27 V, 4 V would remain for the voltage drop
through the field wiring. The system is approved for
[EEx ia] IIC.
Safe area
8
x3
x3
5
6
7
If the switch is in parallel circuit with the nominal mains voltage,
it is usual to use a barrier combination of 28 V, 300 Ohm and a
28 V diode return. In this solution, special attention has to be
Switch status
Hazardous area
Z787
1
4
3
2
In the traditional method of switch status detection, the switch
is provided with noble metal contacts suitable for low voltages
and currents. A ground fault in any field wire leaves the relay in
the de-energised state, despite the switch being closed. This
problem is solved by the use of quasi ground-free wiring.
Z887
paid to the voltage drop in the barrier, since the diode return
causes an additional loss of voltage. The system is approved
for [EEx ia] IIC.
Safe area
8
x3
x3
At a nominal voltage of up to 27 V, a typical coil with 12 V and
approx. 350 Ohm can be used to match the power. The Zener
barrier is approved for [EEx ia] IIC. Negative polarities can be
accommodated with the Z887.
5
6
7
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
20
Page 21
Zener barriers - operating instructions
Application examples
Pulse transmission and flow measurement
Hazardous area
Z728
Flow meter with
pulse output
1
CL
2
The simplest method of flow measurement, with or without a
pre-amplifier, is illustrated in the circuit above. The flow meter
sensor generates voltage or current pulses, which are
transmitted to the safe area via the Z728. If the sensor
Hazardous area
Flow meter with
pulse output
1
4
3
2
Z787
Safe area
8
x3
7
Output
generates sinusoidal signals, e. g. an inductive sensor, a Zener
barrier for alternating polarities can be used, for example the
Z928. The Zener barrier is approved for [EEx ia] IIC.
Safe area
8
x3
x3
5
6
7
Output
If the power supply to the flow meter is provided via a 28 V,
300 Ohm barrier and ground, the signal can be transferred via
the diode return of the Z787. When selecting the receiver
LED display
Hazardous area
Z728
1
CL
2
The simplest and most economical solution is the singlechannel Zener barrier shown above. The nominal supply
voltage is sufficiently low that the end-to-end resistance of the
(counter), consideration must be given to the fact that the high
signal is damped by the diode. The system is approved for
[EEx ia] IIC.
Safe area
8
x3
7
barrier limits the flow of current through the LED to an
acceptable value. Otherwise a current-limiting resistor is
required. The system is approved for [EEx ia] IIC.
21
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 22
LED display
Zener barriers - operating instructions
Application examples
Hazardous area
Z728.CL
1
CL
2
The circuit shown above does not require a current limiting
resistor, since the Z728.CL limits the current electronically to a
maximum of 40 mA. At a supply voltage of 18 V … 27 V a
current of 40 mA flows in the intrinsically safe circuit. This
Smoke and fire alarms
Hazardous area
Z728
1
CL
Safe area
8
x3
7
current reduces at lower nominal supply voltages. To special
order, the Z728.CL can be supplied with lower current-limiting
values. The system is approved for [EEx ia] IIC. The Z828.CL
is also suitable for negative polarities.
Safe area
Output
8
I
2
The simplest and most cost-effective solution is shown in the
illustration above. With a 24 V nominal supply voltage, there is
an off-state current of approx. 4 mA. When the detector
responds, the current increases to approx. 25 mA or greater.
Hazardous area
Z787
1
I
4
3
2
x3
7
The current applied to the detector is sufficient to operate the
LED display with sufficient brightness. The system is approved
for [EEx ia] IIC.
Safe area
Output
8
x3
x3
5
6
7
The system shown above is comparable to the Z728 and is
also relatively inexpensive. The Z787 is a 2-channel device. In
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
this application the intrinsically safe circuit is quasi ground-free.
The system is approved for [EEx ia] IIC.
22
Page 23
Zener barriers - operating instructions
Application examples
Audible alarms
Hazardous area
1
CL
2
Audible alarms operate at relatively high voltages and low
currents. They are approved for use with various Zener
I/P converters
Hazardous area
1
P
I
2
3
4
Z728
Z787
Safe area
8
x3
7
barriers. The simplest solution is the circuit shown above.
Safe area
8
x3
x3
7
6
5
The simplest and most cost-effective solution is a singlechannel Zener barrier. The nominal supply control voltage
must either be ground-free or connected to the negative output
to earth. In theory, the field circuit can have a resistance of
900 Ohm if the voltage supply is 27 V. In practice, however, the
voltage values are lower, so that the field circuit normally has a
resistance of 300 Ohm.
23
Date of issue05/23/03
Subject to reasonable modifications due to technical advances.Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.