VEGA Z728 User Manual

Page 1
Zener barriers - operating instructions
Operating principle
1 Zener barriers - operating instructions
Application
The relevant regulations and directives governing the intended application must be observed.
Installation, commissioning
Zener barriers are constructed to a protection classification of IP20 and accordingly must be appropriately protected from adverse conditions such as splashing water and soiling in excess of pollution severity 2.
Zener barriers must be installed outside the hazardous area! Only those circuits identified as intrinsically safe may be located within the hazardous area.
When intrinsically safe field devices are interconnected with the intrinsically safe circuits of the related Zener barriers, the respective highest values (safety parameters) for the field devices and the Zener barriers - in the sense of explosion protection - must be observed (demonstration of intrinsic safety). The EU certificate of conformity or EU prototype test certificate must be followed. Particular importance is attached to maintaining the "Special conditions" contained in these certificates.
When intrinsically safe circuits are employed in an explosive dust atmosphere (zones 20 and 21), only appropriately certificated field devices are permitted to be incorporated.
Installation and commissioning within zone 2
The devices must be installed in switch boxes or distributor boxes to protection category IP54 or better.
The devices may be installed within zone 2. Only those circuits identified as intrinsically safe are permitted to be installed in zone 1 or zone 0 and in accordance with their ignition protection category approval. The actual installation of the intrinsically safe circuits is to be carried out in accordance with the applicable installation regulations.
When interconnecting intrinsically safe field devices with the intrinsically safe circuits of the associated Zener barriers, the respective highest values (safety parameters) of the field device and the associated device, in the sense of explosion protection, must be taken into account (demonstration of intrinsic safety). The conditions stated on the EU certificates of conformity or EU prototype test certificates must be observed.
In addition, for operation within zone 2, the statements of conformity of the certifying authorities/declarations of conformity of the manufacturer must be observed. Particular importance is attached to maintaining the "Special conditions" contained in these certificates.
When intrinsically safe circuits are employed in an explosive dust atmosphere (zones 20 and 21), only appropriately certificated field devices are permitted to be incorporated.
Servicing and maintenance
The transmission characteristics of the devices remain stable over long periods, so that regular adjustments or other precautions are not required. This also means that no maintenance work is required.
Fault elimination
No modifications may be made to devices that are operated in connection with hazardous areas. Repairs must only be carried out by specially trained and authorised personnel.
1.1 Operating principle
The Zener diodes in the barriers are connected in the reverse direction. The breakdown voltage of the diodes is not exceeded in normal operation.
Hazardous area Safe area
Resistor
R1
Zener diodes
Figure 1.1 Circuit diagram
ZD1
ZD2 ZD3
If this voltage is exceeded, due to a fault in the non-Ex-area, the diodes start to conduct, causing the fuse to blow, thus preventing the transfer of unacceptably high energy into the hazardous area.
Terminals 7 and 8 are connected to the devices in the non­hazardous area. The single condition that these devices must satisfy, is that they must not contain a source whose potential relative to earth is greater than 250 V/253 V
253 V DC.
Fuse
F1
AC or 250/
eff
Terminals 1 and 2 are connected to the intrinsically safe circuits in the hazardous area. If they are used in the hazardous area, active intrinsically safe apparatus must be certificated unless the electrical values of such apparatus do not exceed any of the following values: 1.5 V; 0.1 A; 25 mW.
Pepperl+Fuchs Zener barriers are identified in terms of voltage, resistance and polarity, e. g. 10 V, 50 Ohm, positive polarity. These figures correspond to the Zener voltage U
and
z
the total resistance of all barrier components. They therefore represent the safety values. The values stated on the type identification label correspond to the "worst case" data for U
) and Ik(Io) determined during certification.
z(Uo
I
is obtained by dividing Uz by the resistance R1. It should be
k
noted once again, however, that these values do not correspond to the operating range of the Zener barrier.
Ideally, Zener diodes would not allow any current in the reverse direction until the Zener voltage has been attained. In practice, Zener diodes do allow a small leakage current, the value of which increases as the applied voltage is increased.
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
1
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 2
Zener barriers - operating instructions
Operating principle
The operating range of a Zener barrier must therefore be such that it is below the Zener voltage, so that the leakage current is restricted to a minimum. Zener barriers are normally tested to ensure that at the prescribed voltage the leakage current is smaller than 10 µA.
Hazardous area Safe area
50 mA
Load
Figure 1.2 This figure shows a selection of leakage currents through
the Zener barriers under normal circumstances. The Zener barriers conduct a maximum of 10 (1) µA leakage current so long as the supply voltage is less than 25.5 V. This is normal and has very little effect on the load. If the voltage exceeds 25.5 V, the Zener diodes start to conduct more current. This can have an effect on the operating current and the accuracy. It is therefore recommended that a controlled voltage source be used, which maintains the voltage under the value at which the diodes will start to conduct. (A 24 V, 300 Ohm barrier is represented here as an example)
10 µA
24 V
Power supply
(+)
25.5 V
(-)
These voltages are stated in the data sheet for a given barrier, together with the leakage current. If the leakage current for a given voltage differs from 10 µA, this is specifically stated.
Hazardous area Safe area
50 mA
Load
Figure 1.3 This figure shows that if the maximum permissible input
(supply) voltage is exceeded, the total current drains through the Zener diodes, without reaching the explosive surroundings.
24 V
Power supply
(+)
25.5 V
>
(-)
Pepperl+Fuchs Zener barriers have a low series resistance, given by the sum of the resistance R1 and the resistance value of the fuse F1. Due to the low series resistance, an inadvertent short-circuiting of terminals 1 and 2 can cause the fuse to blow. In order to avoid this, some barriers are available with electronic current limitation (CL-version).
If the Zener barriers are provided with a resistance, this limits the short-circuit current to a safe value in the event of a short­circuit of the connecting wiring in the hazardous area or a connection to earth of the wiring attached to terminal 1, as the fuse blows.
Many barriers are available with a resistance connected between the output terminals. These are used in 4 mA … 20 mA transmitter circuits. The resistance converts the current in the intrinsically safe circuit into a voltage that can be measured in the safe area.
Pepperl+Fuchs Zener barriers can be used in many applications. In the simplest case, a single channel barrier with a ground connection is used. But in many applications it is not desirable that the intrinsically safe circuit is connected directly to ground. If the circuit in the safe area is grounded, under some circumstances grounding of the intrinsically safe circuit can lead to faults within the system. In this case, quasi ground­free intrinsically safe circuits can be constructed with two or more barriers. This floating circuitry can be simply achieved with 2- or 3-channel barriers.
Double grounding of intrinsically safe circuits is not permitted. The insulation voltage of the wiring and field devices, measured with respect to ground, must be greater than 500 V AC. The permissible ambient temperature of the Zener barriers is between -20 °C … 60 °C.
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
2
Page 3
Zener barriers - operating instructions
y
Multi-channel barriers
1.2 Multi-channel barriers
Analogue circuits are often connected to two-channel barriers (see Figure 1.5). Since there is no grounding on this type of circuit, the system is a quasi floating one. It is termed "quasi floating", because it is "one Zener voltage" above the ground potential. Although it does not actually float, the signal-to-noise ratio is improved.
A further advantage of multi-channel Zener barriers is that a higher packing density can be achieved.
.
Hazardous area
4 mA ... 20mA
transmitter
Safe area
(+)
24 V
R
M
Power supply can not be grounded.
Figure 1.4 Single-channel Zener barrier
1.3 Grounding of Zener barriers
Intrinsically safe circuits with Zener barriers without galvanic isolation must be grounded. The cross-section of the ground
connection, using a copper conductor, must be at least 4 mm (for further details see EN 60079-14, section 12.2.4). The maintenance of these requirements prevents the occurrence of a dangerous potential with respect to ground.
A fault of the type illustrated in figure 8.6 can cause a dangerous spark if the Zener barrier is not grounded, but grounding is provided via the field device in the intrinsically safe circuit (Figure 1.5). If a potential occurs in the fault case, which is higher than permitted (see Figure 1.6) the Zener diodes become conducting and the current is conducted away via the ground. The fuse "blows".
.
Hazardous area
4 mA ... 20mA
transmitter
Figure 1.5 Two-channel Zener barrier
2
Safe area
(+)
24 V
R
M
Hazardous
Safe area
area
Hazardous potential
Hazardous potential
Figure 1.6 Non-grounded Zener barrier
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
3
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
AC/DC supply voltage
Fault
Power suppl
Transformer
Hazardous area
Safe area
Fault
Power supply
Transformer
Fault current
Intrinsically safe ground
Figure 1.7 Grounded Zener barriers
The system must have its own independent ground conductor, through which no supply system current flows.
Date of issue 05/23/03
Page 4
1.4 Installation notes
Pepperl+Fuchs Zener barriers in the Z7, Z8 and Z9 series can be mounted on a standard rail to EN 50022 in 3 different arrangements.
Equipotential bonding via the standard rail (grounding of all snapped-on Zener barriers)
Insertion strip ZH-ES/LB
Label carrier ZH-Z.BT
DIN rail NS 35/7.5 35 mm standard rail to DIN EN 50 022
Clamp ZH-Z.USLKG5
Figure 1.8 Equipotential bonding via the standard rail
Group grounding through insulated mounting
Mounting block ZH-Z.AB / NS
Figure 1.9 Insulated mounting (Individual grounding)
Individual grounding through insulated mounting
Mounting block ZH-Z.AB/SS
Single socket ZH-Z.ES
N-Combined rail ZH-Z.NLS-Cu3/10
Zener barriers - operating instructions
Installation notes
Pepperl+Fuchs Zener barriers also feature a space-saving
12.5 mm housing which incorporates up to 3 channels.
11012.5
115
Figure 1.11 Mechanical features
Construction: Modular terminal housing in Makrolon, flammability classification UL 94: V -0
Fixing: Snaps onto 35 mm standard rail to DIN EN 50022 Connection options: Self-opening terminals, max. core cross-
section 2 x 2.5 mm² The barriers are usually installed in racks or control cabinets.
They can be built into housings under production conditions, with the proviso that the housing must afford adequate protection. They can also be employed in hazardous areas, when it has been ascertained that the housing has been certificated for this purpose.
The installation must be carried out in such a way that the intrinsic safety is not compromised by the following factors:
Danger of mechanical damage
Non-authorised changes or influence exerted by external personnel
Humidity, dust or foreign bodies
Ambient temperature exceeding the permissible level
The connection of non-intrinsically safe circuits to intrinsically safe circuits
Grounding of the mounting rail is of the normal type, i. e. both ends are connected to the intrinsically safe ground. This also simplifies checking the grounding.
Many installations provide the option of subsequent expansion. Replacement cable for this purpose can be connected to the Z799 dummy barrier and unused cable can be connected to the intrinsically safe ground.
Connector for ground lead ZH-Z.AK4
Connector ZH-Z.AK16
Ground rail feed ZH-Z.LL
Spacing roller ZH-Z.AR.125
Figure 1.10 Insulated mounting (Individual grounding)
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
4
Page 5
Zener barriers - operating instructions
Zener barrier specifications
1.5 Zener barrier specifications
Nominal data
The following are typical data used in the description of a barrier: 28 V, 300 Ohm, 93 mA. These values relate to the maximum voltage, the minimum value of the built-in resistance and the resulting maximum current.
The maximum voltage stated is not representative of the operating range, it is the maximum value that can be attained in a failure case, before the fuse responds. The resistance value is not identical to the maximum series resistance. These values merely provide an indication of the maximum values that can apply in the case of a failure.
Series resistance
This is the resistance that can be measured between the two ends of a barrier channel. It is obtained from the sum of the resistance R and resistance value of the fuse at an ambient temperature of 20 °C.
Polarity
Zener barriers are available in various versions. On Zener barriers for positive polarities the anodes of the Zener diodes are grounded. On barriers for negative polarities it is the cathodes which are grounded. On barriers for alternating polarities, interconnected Zener diodes are employed and one side is grounded. These can be used for both alternating voltage signals and direct voltage signals.
Maximum voltage in the intrinsically safe circuit. (U
This is the maximum value of voltage that can occur in the intrinsically safe circuit in the failure case.
Maximum current in the intrinsically safe circuit (Ik)
)
z
This is the maximum current that can flow in the intrinsically safe circuit in the failure case.
Maximum input voltage (max. U
)
in
The maximum voltage (correct polarity) that can be applied between the contacts in the safe area and the ground without the fuse responding. This value is determined for an open intrinsically safe circuit and an ambient temperature of 20 °C.
Input voltage (Uin at 10 (1) µA)
The maximum voltage (correct polarity) that can be applied between the contacts in the safe area and the ground at a defined leakage current (as a rule 10 µA). This is the upper value of the recommended operating range.
Maximum connectable external capacitance C
max
This is the maximum capacitance that can be connected to the terminals of the barrier intrinsically safe circuit. This value is determined from the sum of the wiring capacitance and the input capacitance of the field device.
Maximum connectable external inductance L
max
This is the maximum inductance that can be connected to the terminals of the barrier intrinsically safe circuit. The value is determined from the sum of the inductance of the wiring and the input inductance of the field device.
Note: The designations of the values given in the specifications
above are not those of the relevant standards, but those specified on certificates of conformity (e. g. in EN 60079-14, Section 3, IK is now IO).
1.6 How to select the correct barrier
For very many applications the standard solutions are given in this catalogue, in the section on Example Applications. However, in the event that a particular application has not been covered, the following information may be helpful.
1. First decide whether it will be necessary to have a floating circuit, or whether the intrinsically safe circuit can be connected directly to ground. Check whether any existing instrumentation is grounded. If the answer is yes, then check whether additional grounding could lead to faults. Bear in mind that the floating circuit offers a better common­mode rejection characteristic than the grounded circuit. On the other hand, it is more expensive. If a floating circuit is employed, the barriers will normally resist a ground fault.
2. Select the required polarity. This is either determined by the circuit itself, or by any other existing grounds in the circuit. In most applications barriers for positive polarities are used. In order to achieve greater system standardisation, barriers suitable for alternating polarities can be used in place of unipolar ones.
3. Decide the nominal voltage of the Zener barrier. Then determine the maximum output voltage of the device in the safe area during normal operation. Normally the required value is the next highest nominal voltage of a Zener barrier. If these values are close together, it could be that the
recommended operating range of the Zener barrier is exceeded. The consequence of this is that the leakage current will be greater than 10 µA. In this case a barrier with a higher nominal voltage should be used. The leakage current is determined for an open intrinsically safe circuit and this then represents the maximum value at the given voltage.
4. Take account of the maximum series resistance of the Zener barrier and its effect on the intrinsically safe circuit. Make sure that this resistance does not cause an inadmissibly high loss of voltage. In circuits having high resistance - usually when voltage signals are being transferred - this resistance is not relevant. If for example a barrier has a max. series resistance of 1 kOhm, then the resulting error is 0.1 %, if the input resistance of the connected device is 1 MOhm.
5. Check whether or not the field device must be certificated for use in the hazardous area. If certification is necessary, check what the prerequisites are for permitting the field device to be used in connection with a Zener barrier.
6. What is the overall length of the cabling between the voltage supply and the field device? Note the number of conductors in the system!
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
5
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 6
7. The following points have to be clarified if special field devices are used.
If the field device is a 4 mA ... 20 mA transmitter: What load in ohms can be connected to the transmitter so that it can attain 20 mA as before?
If the field device is a current/pressure converter: What load can be connected to the controller card so that it can attain 20 mA as before?
If the field device is a transmitter: How high is the load in the safe area? (typically, resistances of up to 250 Ohm are used in the controller)
Z ...
Zener barriers - operating instructions
How to select the correct barrier
Barrier with replaceable back-up fuse
The introduction of a replaceable back-up fuse ahead of the integrated fuse provides protection against faults which could occur during the commissioning of the system. It is always
Type
Channels
Z715.F 1 106 13 13.6 100 63 217,063
Z728.F 1 327 27 28 80 50 217,05
Z728.H.F 1 250 27 28 80 50 217,05
Z765.F 2 106
Z779.F 2 327
Z779.H.F 2 250
Z787.F 2 327
Z787.H.F 2 250
Z960.F 2 64
Z961.F 2 106
Z966.F 2 166
Max. series
resistance
Ohm V V mA mA
106
327
250
36 + 0.9V
25 + 0.9V
64
106
166
Uin
at 10 µA
13
13 27 27
27 27 27
27 27 27
6.5
6.5
6.5
6.5 10 10
arranged that the outer fuse will respond before the inner, innaccessible fuse. The fuses used are specially intended for use on barriers.
Uin
max
13.6
13.6 28 28
28 28 28
28 28 28
9.5
9.5
8.1
8.1
11.7
11.7
Fuse rating External fuse Fuse supplied
100
100
80 80
80 80 80
80 80 80
80
80 160
160 100 100
63
63 50 50
50 50 50
50 50 50
50
50 100
100
63
63
by LITTLEFUSE
217,063
217,05
217,05
217,05
217,05
217.05
217.1
217.063
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
6
Page 7
Zener barriers - operating instructions
How to select the correct barrier
Type Nominal data Ex-characteristics for [EEx ia] IIC Certification no.
+ ve - ve a.c. V W Uz (V) R
Z705
Z710
– –
Z713 Z813 15.75 22 15.75 21.8 723 2.84 0.48 0.076 12.5 BAS 01 ATEX 7005
Z715
Z715.F
Z715.1K
Z722
Z728 Z728.H
Z728.F
Z728.H.F
Z728.CL
Z755 Z855 5
Z805
Z810
Z810.CL
Z815
Z815.F
– – –
Z822
Z828 Z828.H
Z828.F
Z828.H.F
Z828.CL
Z905
Z910
– –
Z915
Z915.1K
– – –
– – –
Z928
5
5 10
10 10
15 15
15 15 15
22 28 28
28 28 28
28
5
10
4.94
10
4.98
50
9.56
50
9.94
50
9.56
100
14.7
100
14.7
100
15.0
1k
14.7
1k
150 300 240
300 240 300
300
10104.94
4.94
4.94
15
22 28 28
28 28 28
28
(W) IK(mA) P
min
9.8
9.8 49
49 49
98 98
98
980 980
147 301 235
301 235 301
301
9.8
9.8
4.9
504 499 195
203 195
150 150
153
15 15
150
93
119
93
119
93
93
504
504
1008
max
0.62
0.61
0.47
0.50
0.47
0.55
0.55
0.57
0.06
0.06
0.82
0.65
0.83
0.65
0.83
0.65
0.65
0.62
0.62
1.25
(W) C
max
100 100
3
3 3
0.58
0.62
0.58
0.58
0.58
0.17
0.083
0.083
0.083
0.083
0.083
0.083
100
100 100
(µF) L
(mH) L/R Ratio
max
0.14
0.14
0.86
0.86
0.86
1.3
1.45
1.3 144 144
1.45
3.05
1.82
4.21
2.59
3.05
3.05
0.14
0.14
0.03
57
BAS 01 ATEX 7005
57
BAS 01 ATEX 7005
73
BAS 01 ATEX 7005
73
BAS 01 ATEX 7005
73
BAS 01 ATEX 7005
64
BAS 01 ATEX 7005
67
BAS 01 ATEX 7096
64
BAS 01 ATEX 7005
570
BAS 01 ATEX 7005
570
BAS 01 ATEX 7005
45
BAS 01 ATEX 7005
56
BAS 01 ATEX 7005
44
BAS 01 ATEX 7005
55
BAS 01 ATEX 7096
44
BAS 00 ATEX 7096
56
BAS 01 ATEX 7005
56
BAS 01 ATEX 7005
57
BAS 01 ATEX 7005
57 22
Z955 5
Z757
Z764 Z864 12121k1k11.6
Z964 12
Z765
Z765.F
Z857
Z865
Z865.F
Z961
Z961.F
Z961.H
10104.89
5
7
10
7
10
9
100
9
100
9
100
9
100
9
360
9
360
121k1k
15
100
15
100
15
100
15
100
4.89
9.78
7.14
7.14
7.14
17.4
17.4
17.4
11.6
11.6
14.7
14.7
14.7
14.7
14.7
14.7
8.7
8.7
8.7
8.7
8.7
8.7
12 12
24
9.8
9.8
4.9
9.8
9.8
4.9
98 98 98
98 98 98
352.8
352.8 355
980 980
490
980 980
490
98
98 49 98
98 49
499
499 998
729 729
1457
89 89
178
89 89
178
25 25 49
12 12
24
12 12
24
150
150 300 150
150 300
0..61
0.61
1.22
1.3
1.3
2.6
0.19
0.19
0.39
0.192
0.192
0.384
0.05
0.05
0.11
0.03
0.03
0.06
0.04
0.04
0.08
0.55
0.55
1.1
0.55
0.55
1.1
100
100
3.3
13.5
13.5
13.5
4.9
4.9
0.346
4.9
4.9
0.31
4.9
4.9
0.346
1.41
1.41
1.41
1.41
1.41
0.125
0.58
0.58
0.58
0.62
0.62
0.62
0.14
0.14
0.03
0.07
0.07
0.02
4.69
4.69
1.14
4.39
4.39
1.07
57 57
15.2
240 240
61
240 240
61
1.3
1.3
0.32
1.45
1.45
0.32
57
BAS 01 ATEX 7005
57 22
28
BAS 01 ATEX 7005 28 11
182
BAS 01 ATEX 7005
182
72
176
BAS 01 ATEX 7096
176
67
BAS 01 ATEX 7005
613 613 249
1.0
BAS 01 ATEX 7005
1.0
360
1.0
BAS 01 ATEX 7005
1.0
360
64
BAS 01 ATEX 7005
64 22 67
BAS 01 ATEX 7096
67 22
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
7
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 8
Zener barriers - operating instructions
How to select the correct barrier
Max.
end-to-end
resistance
W VVmA
18.18
18.18 56
56
63 + 2 V
29 13.7 14.6 160
107 119
107 1025 1025
166
327
250
338
261
342 + 2 V
327
18.18
18.18 –
18.18
18.18 –
15.5
15.5 –
106 106
113 380
380 380
1033 1033
1033 1033
U
in
at 10 µA
0.9 (1 µA)
0.9 (1 µA)
6.5
6.5
6.5
13.0
13.0
13.0
13.0
13.0
19.0
26.5
26.5
26.5
26.5
26.5
26.0
0.9 (1 µA)
0.9 (1 µA) –
0.9 (1 µA)
0.9 (1 µA) –
6.0
6.0 –
6.5
6.5 –
6.5
6.5 –
6.5
6.5 –
10.0
10.0
10.0
10.0
U
max
4.8
4.7
8.9
9.3
8.9
13.6
13.8
14.0
13.6
14.0
20.1
28.0
28.0
28.0
28.0
28.0
27.6
4.8
4.8 –
4.7
4.7 –
6.9
6.9 –
8.1
8.1 –
8.0
8.1 –
8.1
8.1 –
11.0
11.0
11.7
11.7
in
Fuse rating
250 250 100
100 100
100
63
100 100 100
50 50 80
50 50 50
50
250
250
250
250
200 200
100 100
100
50
50 50
50 50
50 50
see circuit
diagram No.
1), 2)
3)
1), 2)
3)
1), 2)
1), 2)
3)
3)
1), 2)
1), 2)
1), 2)
Hazardous area Safe area connections connections
1)
18
CL
x3
27
+VE type
2)
18
CL
x3
27
-VE type
3)
Circuit diagram
1), 2)
3)
4), 5) A1
6) A1
18
x3
x3
27
AC type
4)
18
x3
x3
6
4), 5)
6)
27
3
45
+VE type
5
)
18
27
6)
3
45
4), 5) A1
-VE type
x3
x3
6
6)
6) A1
18
27
x3 x3
see note 2
A2
B
A2
B
A1 A2
B
A1 A2
B
A1 A2
B
A1 A2
B
A2
B
A2
B
107
107
– 119
119
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
13.0
13.0 –
13.0
13.0 –
13.6
13.6 –
13.9
13.9 –
100
100
– 63
63
4), 5) A1
3
45
AC type
x3 x3
6
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
A2
B A1
A2
B
8
Page 9
Zener barriers - operating instructions
How to select the correct barrier
Type Nominal data Ex-characteristics for [EEx ia] IIC Certification no.
+ ve - ve a.c. V W Uz (V) R
Z966 1212150
1501212
24
Z966.F
12 12
150 150
12 12 24
Z966.H
12 12
75 75
12 12 24
Z772 Z872 2222150
1502222
22
Z778
Z878
28 28
600 600
28 28
28
Z779
Z879
28 28
300 300
28 28
28
Z779.H
Z879.H
28 28
240 240
28 28
28
Z779.F
Z779.H.F
Z879.F
Z879.H.F
28 28
28 28
300 300
240 240
28 28
28 28
(W) IK(mA) P
min
147 147
73.5
164
147 147
73.5
73.5
73.5
36.5
147 147
73.5
164
164 164 328
150 150
300
607 607
303.5 301 301
150.5 235 235
117.5
186 119 119
238 301 301
235 235
120
120
82 82
82 82
46 46
93 93 93
93 93
max
0.24
0.24
0.48
0.24
0.24
0.49
0.49
0.49
0.98
0.82
0.82
1.64
0.32
0.32
0.65
0.65
0.65
1.3
0.83
0.83
1.67
0.65
0.65
0.83
0.83
(W) C
(µF) L
max
max
1.41
1.41
0.125
1.41
1.41
0.125
0.17
0.17
no approval for IIC
0.083
0.083
0.083
0.083
0.083
no approval for IIC
0.083
0.083
no approval for IIC
0.083
0.083
0.083
0.083
(mH) L/R Ratio
5.52
5.52
1.38
1.38
1.38
0.33
1.45
147 147
57
75 75 36
4545BAS 01 ATEX 7005
1.45
17.2
17.2
3.05
3.05
3.05
1.82
1.82
4.21
4.21
2.59
2.59
109 109
42 56 56
44 44
55 55
44 44
BAS 01 ATEX 7005
BAS 01 ATEX 7096
BAS 01 ATEX 7005
BAS 01 ATEX 7005
BAS 01 ATEX 7005
BAS 01 ATEX 7005
BAS 00 ATEX 7096
BAS 01 ATEX 7096
Z796 Z896 26.6
Z788
Z788.H
Z788.R
Z888
Z888.H
Z786 Z886 28
Z787
Z787.H
Z787.F
Z787.H.F
Z887
Z887.H
Z887.F
Z887.H.F
20.5
28 10
28 10
28 10
28
28
28
28
28
28
28
28
28
28
320 415
300
50
240
50
300
50
Diode Diode
Diode
300
Diode
240
Diode
300
Diode
240
Diode
26.6
20.5
26.6
28
9.56 28
28
9.56
28 28
9.56
28
28 28
28
28
28 28 28
28 28 28
28 28 28
28 28
314 407 177
301
49 42
235
49
40
301
49
42
Diode Diode
Diode
301
Diode
301 235
Diode
235 301
21.8 301
235.2
14.7
235.2
85 50
135
93 195 288
119 195
314
93 195
288
0 0
0
93
0
93 119
0
119
93
Diode
93 120
Diode
120
0.56
0.26
0.82
0.65
0.47
0.87
0.83
0.47
1.0
0.65
0.47
0.87
0.0
0.0
0.0
0.65
0
0.65
0.83
0
0.83
0.65
0
0.65
0.83
0
0.83
0.094
0.204
0.094
0.083
3.0
0.083
0.083
3.0
0.083
0.083
3.0
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
0.083
5.14
14.6
2.05
3.05
0.86
0.32
1.82
0.86
0.26
3.05
0.86
0.32
– –
3.05
3.05
2.82
see note 1
2.82
4.21
4.21
2.59
2.59
64
BAS 01 ATEX 7005
138
34
56
BAS 01 ATEX 7005 73 26
44
BAS 01 ATEX 7005 73
25 56
BAS 01 ATEX 7005 73
26
BAS 01 ATEX 7005
56
BAS 01 ATEX 7005
– 56 44
BAS 01 ATEX 7005
44
BAS 01 ATEX 7096
55
55
BAS 01 ATEX 7096
44
44
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
9
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 10
Zener barriers - operating instructions
How to select the correct barrier
Max.
end-to-end
resistance
U
in
at 10 µA
U
max
in
Fuse rating
W VVmA
166 166
169 169
82 82
166 166
646 646
– 327 327
– 250 250
– 338 338
264 264
340 437
327
64
250
64
– 327
64
36 + 0.9 V 36 + 0.9 V
327
36 + 0.9 V
– 250
25+ 0.9 V
– 338
46+ 0.9 V
– 264
39+ 0.9 V
10.0
10.0 –
10.0
10.0 –
10.0
10.0 –
19.0
19.0
26.5
26.5
26.5
26.5
26.5
26.5
26.5
26.6
26.5
26.5
24.0
18.0 –
26.5
6.5 –
26.5
6.5
26.5 –
26.5
26.5
26.5
26.5 –
26.5
26.5 –
26.5
26.5 –
26.5
26.5 –
11.7
11.7 –
11.9
11.9 –
11.7
11.7 –
20.1
20.1
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
25.1
19.5 –
28.0
9.1 –
28.0
9.1
28.0
9.1
28.0
28.0
28.0
28.0 –
28.0
28.0 –
28.0
28.0 –
28.0
28.0 –
50 50
63 63
100 100
50 50
50 50
– 50 50
– 80 80
– 50 50
50 50
50 50
50 50
80 80
– 50 50
50 50
50
50
– 80
80
– 50
50
– 50
50
see circuit
diagram No.
6)
6)
4), 5) A1
4), 5)
4), 5)
4), 5)
Hazardous area Safe area connections connections
4)
18
27
3
45
+VE type
5
)
18
27
3
45
-VE type
x3
x3
x3
x3
6
6
6)
18
27
3
45
AC type
x3 x3
x3 x3
6
7)
Circuit diagram
18
4), 5) A1
4), 5)
4), 5)
27
3
45
AC type
All diodes are turned 180˚
for the -VE version.
x3
x3
6
8)
7)
8) A1
9)
18
27
3
45
All diodes are turned 180˚
for the -VE version.
x3
x3
6
9)
9)
18
27
3
45
All diodes are turned 180˚
for the -VE version.
x3
x3
6
see note 2
A1 A2
B
A1 A2
B
A1 A2
B
A2
B
A1 A2
B A1 A2
B A1 A2
B
A2
B
A1 A2
B
A1 A2
B A1 A2
B
A2
B
A1
A2
B A1
A2
B A1
A2
B A1
A2
B
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
10
Page 11
Zener barriers - operating instructions
How to select the correct barrier
Type Nominal data Ex-characteristics for [EEx ia] IIC Certification no.
+ ve - ve a.c. V W Uz (V) R
Z965 1515100
Z967 1717120
Z972 2222300
Z978 2828600
Z954 4.5
Z960
Z960.F
10 10
10 10
4.5
4.5
50
9.94
50
9.94
9.94
50
9.94
50
9.94
9.94
1001515
15
16.8
120
16.8
16.8
3002222
22
6002828
28
12
4.5
12
4.5
12
4.5
9.0
9.0
9.0
(W) IK(mA) P
min
49 49
24.5
98 49 49
98 98 49
117 117
58
301 301
150
607
607 304
11.76
11.76
11.76
5.88
3.92
17.64
203 203 406
203 203 406
153 153 306
143 143
286
73 73
146
46
46 93
383
383 383 765
1150
510
max
0.50
0.50
1.0
0.51
0.51
1.02
0.57
0.57
1.14
0.60
0.60
1.20
0.40
0.40
0.80
0.32
0.32
0.65
0.43
0.43
0.43
0.86
1.29
1.15
(W) C
max
3;0 3;0 3;0
2.63
2.63
2.63
0.58
0.58
0.58
0.38
0.38
0.38
0.17
0.17
0.17
0.083
0.083
0.083
100
100 100
4.9
4.9
4.9
(µF) L
(mH) L/R Ratio
max
0.86
0.86
0.19
0.82
0.82
0.82
1.3
1.3
0.29
1.63
1.63
0.24
6.95
6.95
1.45
17.2
17.2
3.05
0.24
0.24
0.24
0.068
0.03
0.12
73
BAS 01 ATEX 7005 73 26
69
BAS 01 ATEX 7096 69 25
64
BAS 01 ATEX 7005 64 20
60
BAS 01 ATEX 7005 60
21
90
BAS 01 ATEX 7005 90
35
109
BAS 01 ATEX 7005
109
42
81
BAS 01 ATEX 7005
81 81 41
27 30
Dummy
Z799
11
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 12
Zener barriers - operating instructions
How to select the correct barrier
Max. end-to-end resistance
W VVmA
64 64
– 75 75
115 115
136 136
327 327
646
646
U
in
at 10 µA
6.5
6.5 –
6.5
6.5
13.0
13.0 –
15.0
15.0
19.0
19.0
26.0
26.0 –
U
max
9.5
9.5 –
9.7
9.7
14.2
14.2 –
16.2
16.2
20.9
20.9
27.6
27.6 –
in
Fuse rating
50 50
– 50 50
50 50
50 50
50 50
50
50
see circuit
diagram No.
10)
Hazardous area Safe area connections connections
10)
Circuit diagram
18
27
3
10) A1
10) A1
45
11)
x3
x3
6
18
x3
10) A1
36
x3
2
7
x3
10) A1
45
see note 2
A1 A2
B
A1 A2
B
A2
B
A2
B
A2
B
A2
B
27.27
27.27
27.27 –
– –
0.9 (1 µA)
0.9 (1 µA)
0.9 (1 µA) –
– –
4.9
4.9
4.9 –
– –
50
50 50
– –
Note 1:
Zener barriers type Z787H and Z887H have channels with diode returns.
The Ex-terminals for the channels with diode returns should be regarded as 28 V voltage sources.
The 28 V must be considered as the theoretical maximum up to which a capacitive load can be applied to the Ex-terminals due to the leakage current of the diode return. This voltage is only used in calculating the load capacitance.
11) A1
A2 A3
18
27
3
6
45
Note 2:
A1, A2 and A3 are separate channels. B: Two channels in parallel circuit with a ground connection. C: Two channels in series circuit without a ground return.
B
B C
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
12
Page 13
Zener barriers - operating instructions
Application examples
1.7 Application examples
Temperature measurement
Hazardous area
Not grounded
The simplest and most favourably priced solution is a single­channel Zener barrier. It should be noted, however, that the
1
CL
2
Hazardous area
1
2
3
4
Safe area
Z705
8
x3
7
Temperature
monitoring
or control
device is not grounded in the safe area. The system is approved for [EEx ia] IIC.
Safe area
Z960
8
x3
x3
x3
7
6
5
Temperature
monitoring
or control
The use of a two-channel barrier prevents the direct ground connection of the intrinsically safe circuit. Grounding only takes place in the event of a fault, when the Zener diodes conduct.
Hazardous area
1
2
3
4
1
2
3
4
Z961
Z961
This circuit arrangement prevents the occurrence of mutual interference between the various circuits. The system is approved for [EEx ia] IIC.
Safe area
8
x3 x3
x3 x3
x3 x3
x3 x3
7
6
5
V
8
7
6
5
The illustration shows the set up for a temperature measurement with a 4-wire Pt100. None of the 4 wires is connected directly to ground. The complete system is therefore "quasi ground-free".
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
13
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
This is the best option when the intention is to suppress the influence of the end-to-end resistance of the barrier on the measuring accuracy as far as possible.
Date of issue 05/23/03
Page 14
Temperature measurement
Zener barriers - operating instructions
Application examples
Hazardous area
Z954
1
3
2
4
The circuit arrangement shows the connection of a Pt100 in 3­wire technology, using the 3-channel Zener barrier Z954. The whole system is quasi ground-free. All 3 barriers have identical
Hazardous area
1
2
3
4
Z961
Safe area
8
x3
x3 x3
x3
x3 x3
6
7
Test circuit
5
end-to-end resistances, so that the resulting error is restricted to a minimum. The system is approved for [EEx ia] IIC.
Safe area
8
x3 x3
x3 x3
7
6
5
Z954
1
3
2
4
Z954
1
3
2
4
The circuit consists of a system of a maximum of seven Pt100s. The Pt100s are connected in series to a constant current source. Each voltage signal is transferred to a receiver via a Z954.
8
x3
x3 x3
x3 x3
x3
x3 x3
x3 x3
x3 x3
6
7
5
Receiver with
galvanically
isolated inputs
8
6
7
5
The Z954s have been selected due to their high end-to-end resistance. Due to the high input resistance of the receiver, the high end-to-end resistance has practically no effect on the accuracy of measurement.
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
14
Page 15
Zener barriers - operating instructions
Application examples
0 mA … 20 mA/4 mA … 20 mA transmitter
Hazardous area
Z728
1
CL
2
If a ground-free power supply is available, the use of a single­channel Zener barrier, grounded in the safe area, represents the simplest and most economical solution. The ammeter can be used in combination with a recording instrument, a trip amplifier, or a 250 Ohm resistance, or replaced by these devices. In so doing, the overall resistance of the arrangement must be taken into account. The working range of the barrier
Hazardous area
Z788
1
2
Safe area
8
x3
7
A
caters for an input voltage of up to 27 V. For each built-in 250 Ohm resistance the output voltage of the power supply can be increased by 1 V. By using a 250 Ohm resistance and a supply voltage of 28 V, a source of 16.5 V at 20 mA is available to the transmitter in the hazardous area. The internal voltage drop across the barrier is then 6.5 V. The system is approved for [EEx ia] IIC.
Safe area
8
x3
7
3
4
With this 2-channel Zener barrier, it is possible to supply a number of circuits with one source. All the wiring is quasi ground-free. The maximum voltage supply is 27 V. The internal voltage drop across the barrier is 7.8 V at 20 mA, so that
19.2 V are available for the field device and ammeter. If the
6
x3
5
A
ammeter for converting the current signal into a 1 V … 5 V voltage signal is replaced by a 250 Ohm resistance, then
14.2 V are available at the field device. The system is approved for [EEx ia] IIC.
15
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 16
0 mA … 20 mA/4 mA … 20 mA transmitter
Zener barriers - operating instructions
Application examples
Hazardous area
Z788.R
1
2
3
4
This system can be used if the field device requires a relatively high voltage. A 250 Ohm resistance is connected in parallel with the Ex-output of the 10 V/50 Ohm output of this 2-channel
Hazardous area
Z787
1
2
3
4
x3
Safe area
8
x3
x3
7
6
5
V
barrier. Thus a voltage of 15.5 V is available at the field device if the voltage supply is 27 V. The system is approved for [EEx ia] IIC.
Safe area
8
x3
x3
7
6
5
A
The combination of a 28 V, 300 Ohm and a 28 V barrier with diode return is the solution for applications with 3-wire transmitters. Special attention must be paid here to the internal
voltage drop. The reason for this is the diode return. The system is approved for [EEx ia] IIC.
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
16
Page 17
Zener barriers - operating instructions
Application examples
SMART transmitter
Hazardous area
Z787
1
2
3
4
The simplest possible solution is the use of a 2-channel Zener barrier with 28 V, 300 Ohm and 28 V diode return. If a regulated power supply unit provides an output voltage of 27 V,
13.9 V will be available to the transmitter and wiring in the Ex­area.
Strain gauge bridges
Hazardous area
1
2
Z966
Safe area
8
x3
x3
7
6
5
A
The data transfer is bidirectional, so that a non-certificated communicator can be connected and used in the the safe area. The system is approved for [EEx ia] IIC.
Safe area
8
x3 x3
7
3
4
1
2
3
4
1
2
3
4
Z964
Z964
x3 x3
x3 x3
x3 x3
x3 x3
x3 x3
6
5
8
7
6
5
8
7
6
5
+
-
Signal
The strain gauge bridge is supplied via the Z966. The Z966 enables a 350 Ohm strain gauge bridge to be supplied with 8 V. The voltage feedback via the Z964 can be dispensed with, although in practice most applications require this feedback to
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
17
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
obtain the best possible accuracy of measurement. The millivolt signal is transferred to the safe area via the Z964.
The system is approved for [EEx ia] IIC.
Date of issue 05/23/03
Page 18
Wire strain gauges
Zener barriers - operating instructions
Application examples
Hazardous area
350 Ohm
350 Ohm
Z966
1
x3
Z966
Z964
x3
x3 x3
x3 x3
x3 x3
x3 x3
x3 x3
2
3
4
1
2
3
4
1
2
3
4
8
7
6
5
8
7
6
5
8
7
6
5
Sensor +
Sensor -
-0+
Safe area
350 Ohm
1
2
3
4
Z964
If more than one strain gauge bridge is to be supplied from a common power supply (in the example shown above there are three), a possible solution is to supply them via two Z966s, as shown.
8
x3 x3
x3 x3
7
6
5
Both channels of these Zener barriers are arranged in parallel in order to reduce the end-to-end resistance. This arrangement provides 8 V to the bridges if the voltage supply is 20 V. The system is approved for [EEx ib].
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
18
Page 19
Zener barriers - operating instructions
Application examples
Potentiometric position detection
Hazardous area
1
2
3
4
Applications in which the accuracy is not critical can be satisfied as shown above. The intrinsically safe circuit has a direct connection to ground. An additional resistance on this
Harzardous area
1
x3
Z715
CL
Safe area
Z960
8
x3
x3
7
6
5
V
side would have an effect on the voltage signal and would have to be taken into account. The system is approved for [EEx ia] IIC.
Safe area
8
x3
2
Z715.1K
1
CL
x3
2
Z715.1K
1
CL
x3
2
7
8
7
Signal
8
7
If greater accuracy is required, a 4-wire solution must be applied. The Z715 Zener barrier transfers the power supply to the potentiometer, whilst two Z715.1K barriers transfer the
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
19
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
signal to the receiver. The supply voltage in the example above could be 13 V.
Date of issue 05/23/03
Page 20
Solenoid valves
Zener barriers - operating instructions
Application examples
Hazardous area
Z728
1
CL
2
The simplest and most economical solution is a single channel Zener barrier, with the power supply grounded on its safe side. If the valve requires 30 mA at a minimum 12 V, then at a
Hazardous area
Z787
1
4
3
2
Safe area
8
x3
7
supply voltage of 27 V, 4 V would remain for the voltage drop through the field wiring. The system is approved for [EEx ia] IIC.
Safe area
8
x3
x3
5
6
7
If the switch is in parallel circuit with the nominal mains voltage, it is usual to use a barrier combination of 28 V, 300 Ohm and a 28 V diode return. In this solution, special attention has to be
Switch status
Hazardous area
Z787
1
4
3
2
In the traditional method of switch status detection, the switch is provided with noble metal contacts suitable for low voltages and currents. A ground fault in any field wire leaves the relay in the de-energised state, despite the switch being closed. This problem is solved by the use of quasi ground-free wiring.
Z887
paid to the voltage drop in the barrier, since the diode return causes an additional loss of voltage. The system is approved for [EEx ia] IIC.
Safe area
8
x3
x3
At a nominal voltage of up to 27 V, a typical coil with 12 V and approx. 350 Ohm can be used to match the power. The Zener barrier is approved for [EEx ia] IIC. Negative polarities can be accommodated with the Z887.
5
6
7
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
20
Page 21
Zener barriers - operating instructions
Application examples
Pulse transmission and flow measurement
Hazardous area
Z728
Flow meter with pulse output
1
CL
2
The simplest method of flow measurement, with or without a pre-amplifier, is illustrated in the circuit above. The flow meter sensor generates voltage or current pulses, which are transmitted to the safe area via the Z728. If the sensor
Hazardous area
Flow meter with pulse output
1
4
3
2
Z787
Safe area
8
x3
7
Output
generates sinusoidal signals, e. g. an inductive sensor, a Zener barrier for alternating polarities can be used, for example the Z928. The Zener barrier is approved for [EEx ia] IIC.
Safe area
8
x3
x3
5
6
7
Output
If the power supply to the flow meter is provided via a 28 V, 300 Ohm barrier and ground, the signal can be transferred via the diode return of the Z787. When selecting the receiver
LED display
Hazardous area
Z728
1
CL
2
The simplest and most economical solution is the single­channel Zener barrier shown above. The nominal supply voltage is sufficiently low that the end-to-end resistance of the
(counter), consideration must be given to the fact that the high signal is damped by the diode. The system is approved for [EEx ia] IIC.
Safe area
8
x3
7
barrier limits the flow of current through the LED to an acceptable value. Otherwise a current-limiting resistor is required. The system is approved for [EEx ia] IIC.
21
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Page 22
LED display
Zener barriers - operating instructions
Application examples
Hazardous area
Z728.CL
1
CL
2
The circuit shown above does not require a current limiting resistor, since the Z728.CL limits the current electronically to a maximum of 40 mA. At a supply voltage of 18 V … 27 V a current of 40 mA flows in the intrinsically safe circuit. This
Smoke and fire alarms
Hazardous area
Z728
1
CL
Safe area
8
x3
7
current reduces at lower nominal supply voltages. To special order, the Z728.CL can be supplied with lower current-limiting values. The system is approved for [EEx ia] IIC. The Z828.CL is also suitable for negative polarities.
Safe area
Output
8
I
2
The simplest and most cost-effective solution is shown in the illustration above. With a 24 V nominal supply voltage, there is an off-state current of approx. 4 mA. When the detector responds, the current increases to approx. 25 mA or greater.
Hazardous area
Z787
1
I
4
3
2
x3
7
The current applied to the detector is sufficient to operate the LED display with sufficient brightness. The system is approved for [EEx ia] IIC.
Safe area
Output
8
x3
x3
5
6
7
The system shown above is comparable to the Z728 and is also relatively inexpensive. The Z787 is a 2-channel device. In
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
this application the intrinsically safe circuit is quasi ground-free. The system is approved for [EEx ia] IIC.
22
Page 23
Zener barriers - operating instructions
Application examples
Audible alarms
Hazardous area
1
CL
2
Audible alarms operate at relatively high voltages and low currents. They are approved for use with various Zener
I/P converters
Hazardous area
1
P
I
2
3
4
Z728
Z787
Safe area
8
x3
7
barriers. The simplest solution is the circuit shown above.
Safe area
8
x3
x3
7
6
5
The simplest and most cost-effective solution is a single­channel Zener barrier. The nominal supply control voltage must either be ground-free or connected to the negative output to earth. In theory, the field circuit can have a resistance of
900 Ohm if the voltage supply is 27 V. In practice, however, the voltage values are lower, so that the field circuit normally has a resistance of 300 Ohm.
23
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Loading...