VEGA Z728 User Manual

Zener barriers - operating instructions
Operating principle
1 Zener barriers - operating instructions
Application
The relevant regulations and directives governing the intended application must be observed.
Installation, commissioning
Zener barriers are constructed to a protection classification of IP20 and accordingly must be appropriately protected from adverse conditions such as splashing water and soiling in excess of pollution severity 2.
Zener barriers must be installed outside the hazardous area! Only those circuits identified as intrinsically safe may be located within the hazardous area.
When intrinsically safe field devices are interconnected with the intrinsically safe circuits of the related Zener barriers, the respective highest values (safety parameters) for the field devices and the Zener barriers - in the sense of explosion protection - must be observed (demonstration of intrinsic safety). The EU certificate of conformity or EU prototype test certificate must be followed. Particular importance is attached to maintaining the "Special conditions" contained in these certificates.
When intrinsically safe circuits are employed in an explosive dust atmosphere (zones 20 and 21), only appropriately certificated field devices are permitted to be incorporated.
Installation and commissioning within zone 2
The devices must be installed in switch boxes or distributor boxes to protection category IP54 or better.
The devices may be installed within zone 2. Only those circuits identified as intrinsically safe are permitted to be installed in zone 1 or zone 0 and in accordance with their ignition protection category approval. The actual installation of the intrinsically safe circuits is to be carried out in accordance with the applicable installation regulations.
When interconnecting intrinsically safe field devices with the intrinsically safe circuits of the associated Zener barriers, the respective highest values (safety parameters) of the field device and the associated device, in the sense of explosion protection, must be taken into account (demonstration of intrinsic safety). The conditions stated on the EU certificates of conformity or EU prototype test certificates must be observed.
In addition, for operation within zone 2, the statements of conformity of the certifying authorities/declarations of conformity of the manufacturer must be observed. Particular importance is attached to maintaining the "Special conditions" contained in these certificates.
When intrinsically safe circuits are employed in an explosive dust atmosphere (zones 20 and 21), only appropriately certificated field devices are permitted to be incorporated.
Servicing and maintenance
The transmission characteristics of the devices remain stable over long periods, so that regular adjustments or other precautions are not required. This also means that no maintenance work is required.
Fault elimination
No modifications may be made to devices that are operated in connection with hazardous areas. Repairs must only be carried out by specially trained and authorised personnel.
1.1 Operating principle
The Zener diodes in the barriers are connected in the reverse direction. The breakdown voltage of the diodes is not exceeded in normal operation.
Hazardous area Safe area
Resistor
R1
Zener diodes
Figure 1.1 Circuit diagram
ZD1
ZD2 ZD3
If this voltage is exceeded, due to a fault in the non-Ex-area, the diodes start to conduct, causing the fuse to blow, thus preventing the transfer of unacceptably high energy into the hazardous area.
Terminals 7 and 8 are connected to the devices in the non­hazardous area. The single condition that these devices must satisfy, is that they must not contain a source whose potential relative to earth is greater than 250 V/253 V
253 V DC.
Fuse
F1
AC or 250/
eff
Terminals 1 and 2 are connected to the intrinsically safe circuits in the hazardous area. If they are used in the hazardous area, active intrinsically safe apparatus must be certificated unless the electrical values of such apparatus do not exceed any of the following values: 1.5 V; 0.1 A; 25 mW.
Pepperl+Fuchs Zener barriers are identified in terms of voltage, resistance and polarity, e. g. 10 V, 50 Ohm, positive polarity. These figures correspond to the Zener voltage U
and
z
the total resistance of all barrier components. They therefore represent the safety values. The values stated on the type identification label correspond to the "worst case" data for U
) and Ik(Io) determined during certification.
z(Uo
I
is obtained by dividing Uz by the resistance R1. It should be
k
noted once again, however, that these values do not correspond to the operating range of the Zener barrier.
Ideally, Zener diodes would not allow any current in the reverse direction until the Zener voltage has been attained. In practice, Zener diodes do allow a small leakage current, the value of which increases as the applied voltage is increased.
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
1
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Zener barriers - operating instructions
Operating principle
The operating range of a Zener barrier must therefore be such that it is below the Zener voltage, so that the leakage current is restricted to a minimum. Zener barriers are normally tested to ensure that at the prescribed voltage the leakage current is smaller than 10 µA.
Hazardous area Safe area
50 mA
Load
Figure 1.2 This figure shows a selection of leakage currents through
the Zener barriers under normal circumstances. The Zener barriers conduct a maximum of 10 (1) µA leakage current so long as the supply voltage is less than 25.5 V. This is normal and has very little effect on the load. If the voltage exceeds 25.5 V, the Zener diodes start to conduct more current. This can have an effect on the operating current and the accuracy. It is therefore recommended that a controlled voltage source be used, which maintains the voltage under the value at which the diodes will start to conduct. (A 24 V, 300 Ohm barrier is represented here as an example)
10 µA
24 V
Power supply
(+)
25.5 V
(-)
These voltages are stated in the data sheet for a given barrier, together with the leakage current. If the leakage current for a given voltage differs from 10 µA, this is specifically stated.
Hazardous area Safe area
50 mA
Load
Figure 1.3 This figure shows that if the maximum permissible input
(supply) voltage is exceeded, the total current drains through the Zener diodes, without reaching the explosive surroundings.
24 V
Power supply
(+)
25.5 V
>
(-)
Pepperl+Fuchs Zener barriers have a low series resistance, given by the sum of the resistance R1 and the resistance value of the fuse F1. Due to the low series resistance, an inadvertent short-circuiting of terminals 1 and 2 can cause the fuse to blow. In order to avoid this, some barriers are available with electronic current limitation (CL-version).
If the Zener barriers are provided with a resistance, this limits the short-circuit current to a safe value in the event of a short­circuit of the connecting wiring in the hazardous area or a connection to earth of the wiring attached to terminal 1, as the fuse blows.
Many barriers are available with a resistance connected between the output terminals. These are used in 4 mA … 20 mA transmitter circuits. The resistance converts the current in the intrinsically safe circuit into a voltage that can be measured in the safe area.
Pepperl+Fuchs Zener barriers can be used in many applications. In the simplest case, a single channel barrier with a ground connection is used. But in many applications it is not desirable that the intrinsically safe circuit is connected directly to ground. If the circuit in the safe area is grounded, under some circumstances grounding of the intrinsically safe circuit can lead to faults within the system. In this case, quasi ground­free intrinsically safe circuits can be constructed with two or more barriers. This floating circuitry can be simply achieved with 2- or 3-channel barriers.
Double grounding of intrinsically safe circuits is not permitted. The insulation voltage of the wiring and field devices, measured with respect to ground, must be greater than 500 V AC. The permissible ambient temperature of the Zener barriers is between -20 °C … 60 °C.
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
2
Zener barriers - operating instructions
y
Multi-channel barriers
1.2 Multi-channel barriers
Analogue circuits are often connected to two-channel barriers (see Figure 1.5). Since there is no grounding on this type of circuit, the system is a quasi floating one. It is termed "quasi floating", because it is "one Zener voltage" above the ground potential. Although it does not actually float, the signal-to-noise ratio is improved.
A further advantage of multi-channel Zener barriers is that a higher packing density can be achieved.
.
Hazardous area
4 mA ... 20mA
transmitter
Safe area
(+)
24 V
R
M
Power supply can not be grounded.
Figure 1.4 Single-channel Zener barrier
1.3 Grounding of Zener barriers
Intrinsically safe circuits with Zener barriers without galvanic isolation must be grounded. The cross-section of the ground
connection, using a copper conductor, must be at least 4 mm (for further details see EN 60079-14, section 12.2.4). The maintenance of these requirements prevents the occurrence of a dangerous potential with respect to ground.
A fault of the type illustrated in figure 8.6 can cause a dangerous spark if the Zener barrier is not grounded, but grounding is provided via the field device in the intrinsically safe circuit (Figure 1.5). If a potential occurs in the fault case, which is higher than permitted (see Figure 1.6) the Zener diodes become conducting and the current is conducted away via the ground. The fuse "blows".
.
Hazardous area
4 mA ... 20mA
transmitter
Figure 1.5 Two-channel Zener barrier
2
Safe area
(+)
24 V
R
M
Hazardous
Safe area
area
Hazardous potential
Hazardous potential
Figure 1.6 Non-grounded Zener barrier
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
3
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
AC/DC supply voltage
Fault
Power suppl
Transformer
Hazardous area
Safe area
Fault
Power supply
Transformer
Fault current
Intrinsically safe ground
Figure 1.7 Grounded Zener barriers
The system must have its own independent ground conductor, through which no supply system current flows.
Date of issue 05/23/03
1.4 Installation notes
Pepperl+Fuchs Zener barriers in the Z7, Z8 and Z9 series can be mounted on a standard rail to EN 50022 in 3 different arrangements.
Equipotential bonding via the standard rail (grounding of all snapped-on Zener barriers)
Insertion strip ZH-ES/LB
Label carrier ZH-Z.BT
DIN rail NS 35/7.5 35 mm standard rail to DIN EN 50 022
Clamp ZH-Z.USLKG5
Figure 1.8 Equipotential bonding via the standard rail
Group grounding through insulated mounting
Mounting block ZH-Z.AB / NS
Figure 1.9 Insulated mounting (Individual grounding)
Individual grounding through insulated mounting
Mounting block ZH-Z.AB/SS
Single socket ZH-Z.ES
N-Combined rail ZH-Z.NLS-Cu3/10
Zener barriers - operating instructions
Installation notes
Pepperl+Fuchs Zener barriers also feature a space-saving
12.5 mm housing which incorporates up to 3 channels.
11012.5
115
Figure 1.11 Mechanical features
Construction: Modular terminal housing in Makrolon, flammability classification UL 94: V -0
Fixing: Snaps onto 35 mm standard rail to DIN EN 50022 Connection options: Self-opening terminals, max. core cross-
section 2 x 2.5 mm² The barriers are usually installed in racks or control cabinets.
They can be built into housings under production conditions, with the proviso that the housing must afford adequate protection. They can also be employed in hazardous areas, when it has been ascertained that the housing has been certificated for this purpose.
The installation must be carried out in such a way that the intrinsic safety is not compromised by the following factors:
Danger of mechanical damage
Non-authorised changes or influence exerted by external personnel
Humidity, dust or foreign bodies
Ambient temperature exceeding the permissible level
The connection of non-intrinsically safe circuits to intrinsically safe circuits
Grounding of the mounting rail is of the normal type, i. e. both ends are connected to the intrinsically safe ground. This also simplifies checking the grounding.
Many installations provide the option of subsequent expansion. Replacement cable for this purpose can be connected to the Z799 dummy barrier and unused cable can be connected to the intrinsically safe ground.
Connector for ground lead ZH-Z.AK4
Connector ZH-Z.AK16
Ground rail feed ZH-Z.LL
Spacing roller ZH-Z.AR.125
Figure 1.10 Insulated mounting (Individual grounding)
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
4
Zener barriers - operating instructions
Zener barrier specifications
1.5 Zener barrier specifications
Nominal data
The following are typical data used in the description of a barrier: 28 V, 300 Ohm, 93 mA. These values relate to the maximum voltage, the minimum value of the built-in resistance and the resulting maximum current.
The maximum voltage stated is not representative of the operating range, it is the maximum value that can be attained in a failure case, before the fuse responds. The resistance value is not identical to the maximum series resistance. These values merely provide an indication of the maximum values that can apply in the case of a failure.
Series resistance
This is the resistance that can be measured between the two ends of a barrier channel. It is obtained from the sum of the resistance R and resistance value of the fuse at an ambient temperature of 20 °C.
Polarity
Zener barriers are available in various versions. On Zener barriers for positive polarities the anodes of the Zener diodes are grounded. On barriers for negative polarities it is the cathodes which are grounded. On barriers for alternating polarities, interconnected Zener diodes are employed and one side is grounded. These can be used for both alternating voltage signals and direct voltage signals.
Maximum voltage in the intrinsically safe circuit. (U
This is the maximum value of voltage that can occur in the intrinsically safe circuit in the failure case.
Maximum current in the intrinsically safe circuit (Ik)
)
z
This is the maximum current that can flow in the intrinsically safe circuit in the failure case.
Maximum input voltage (max. U
)
in
The maximum voltage (correct polarity) that can be applied between the contacts in the safe area and the ground without the fuse responding. This value is determined for an open intrinsically safe circuit and an ambient temperature of 20 °C.
Input voltage (Uin at 10 (1) µA)
The maximum voltage (correct polarity) that can be applied between the contacts in the safe area and the ground at a defined leakage current (as a rule 10 µA). This is the upper value of the recommended operating range.
Maximum connectable external capacitance C
max
This is the maximum capacitance that can be connected to the terminals of the barrier intrinsically safe circuit. This value is determined from the sum of the wiring capacitance and the input capacitance of the field device.
Maximum connectable external inductance L
max
This is the maximum inductance that can be connected to the terminals of the barrier intrinsically safe circuit. The value is determined from the sum of the inductance of the wiring and the input inductance of the field device.
Note: The designations of the values given in the specifications
above are not those of the relevant standards, but those specified on certificates of conformity (e. g. in EN 60079-14, Section 3, IK is now IO).
1.6 How to select the correct barrier
For very many applications the standard solutions are given in this catalogue, in the section on Example Applications. However, in the event that a particular application has not been covered, the following information may be helpful.
1. First decide whether it will be necessary to have a floating circuit, or whether the intrinsically safe circuit can be connected directly to ground. Check whether any existing instrumentation is grounded. If the answer is yes, then check whether additional grounding could lead to faults. Bear in mind that the floating circuit offers a better common­mode rejection characteristic than the grounded circuit. On the other hand, it is more expensive. If a floating circuit is employed, the barriers will normally resist a ground fault.
2. Select the required polarity. This is either determined by the circuit itself, or by any other existing grounds in the circuit. In most applications barriers for positive polarities are used. In order to achieve greater system standardisation, barriers suitable for alternating polarities can be used in place of unipolar ones.
3. Decide the nominal voltage of the Zener barrier. Then determine the maximum output voltage of the device in the safe area during normal operation. Normally the required value is the next highest nominal voltage of a Zener barrier. If these values are close together, it could be that the
recommended operating range of the Zener barrier is exceeded. The consequence of this is that the leakage current will be greater than 10 µA. In this case a barrier with a higher nominal voltage should be used. The leakage current is determined for an open intrinsically safe circuit and this then represents the maximum value at the given voltage.
4. Take account of the maximum series resistance of the Zener barrier and its effect on the intrinsically safe circuit. Make sure that this resistance does not cause an inadmissibly high loss of voltage. In circuits having high resistance - usually when voltage signals are being transferred - this resistance is not relevant. If for example a barrier has a max. series resistance of 1 kOhm, then the resulting error is 0.1 %, if the input resistance of the connected device is 1 MOhm.
5. Check whether or not the field device must be certificated for use in the hazardous area. If certification is necessary, check what the prerequisites are for permitting the field device to be used in connection with a Zener barrier.
6. What is the overall length of the cabling between the voltage supply and the field device? Note the number of conductors in the system!
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
5
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
7. The following points have to be clarified if special field devices are used.
If the field device is a 4 mA ... 20 mA transmitter: What load in ohms can be connected to the transmitter so that it can attain 20 mA as before?
If the field device is a current/pressure converter: What load can be connected to the controller card so that it can attain 20 mA as before?
If the field device is a transmitter: How high is the load in the safe area? (typically, resistances of up to 250 Ohm are used in the controller)
Z ...
Zener barriers - operating instructions
How to select the correct barrier
Barrier with replaceable back-up fuse
The introduction of a replaceable back-up fuse ahead of the integrated fuse provides protection against faults which could occur during the commissioning of the system. It is always
Type
Channels
Z715.F 1 106 13 13.6 100 63 217,063
Z728.F 1 327 27 28 80 50 217,05
Z728.H.F 1 250 27 28 80 50 217,05
Z765.F 2 106
Z779.F 2 327
Z779.H.F 2 250
Z787.F 2 327
Z787.H.F 2 250
Z960.F 2 64
Z961.F 2 106
Z966.F 2 166
Max. series
resistance
Ohm V V mA mA
106
327
250
36 + 0.9V
25 + 0.9V
64
106
166
Uin
at 10 µA
13
13 27 27
27 27 27
27 27 27
6.5
6.5
6.5
6.5 10 10
arranged that the outer fuse will respond before the inner, innaccessible fuse. The fuses used are specially intended for use on barriers.
Uin
max
13.6
13.6 28 28
28 28 28
28 28 28
9.5
9.5
8.1
8.1
11.7
11.7
Fuse rating External fuse Fuse supplied
100
100
80 80
80 80 80
80 80 80
80
80 160
160 100 100
63
63 50 50
50 50 50
50 50 50
50
50 100
100
63
63
by LITTLEFUSE
217,063
217,05
217,05
217,05
217,05
217.05
217.1
217.063
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
6
Zener barriers - operating instructions
How to select the correct barrier
Type Nominal data Ex-characteristics for [EEx ia] IIC Certification no.
+ ve - ve a.c. V W Uz (V) R
Z705
Z710
– –
Z713 Z813 15.75 22 15.75 21.8 723 2.84 0.48 0.076 12.5 BAS 01 ATEX 7005
Z715
Z715.F
Z715.1K
Z722
Z728 Z728.H
Z728.F
Z728.H.F
Z728.CL
Z755 Z855 5
Z805
Z810
Z810.CL
Z815
Z815.F
– – –
Z822
Z828 Z828.H
Z828.F
Z828.H.F
Z828.CL
Z905
Z910
– –
Z915
Z915.1K
– – –
– – –
Z928
5
5 10
10 10
15 15
15 15 15
22 28 28
28 28 28
28
5
10
4.94
10
4.98
50
9.56
50
9.94
50
9.56
100
14.7
100
14.7
100
15.0
1k
14.7
1k
150 300 240
300 240 300
300
10104.94
4.94
4.94
15
22 28 28
28 28 28
28
(W) IK(mA) P
min
9.8
9.8 49
49 49
98 98
98
980 980
147 301 235
301 235 301
301
9.8
9.8
4.9
504 499 195
203 195
150 150
153
15 15
150
93
119
93
119
93
93
504
504
1008
max
0.62
0.61
0.47
0.50
0.47
0.55
0.55
0.57
0.06
0.06
0.82
0.65
0.83
0.65
0.83
0.65
0.65
0.62
0.62
1.25
(W) C
max
100 100
3
3 3
0.58
0.62
0.58
0.58
0.58
0.17
0.083
0.083
0.083
0.083
0.083
0.083
100
100 100
(µF) L
(mH) L/R Ratio
max
0.14
0.14
0.86
0.86
0.86
1.3
1.45
1.3 144 144
1.45
3.05
1.82
4.21
2.59
3.05
3.05
0.14
0.14
0.03
57
BAS 01 ATEX 7005
57
BAS 01 ATEX 7005
73
BAS 01 ATEX 7005
73
BAS 01 ATEX 7005
73
BAS 01 ATEX 7005
64
BAS 01 ATEX 7005
67
BAS 01 ATEX 7096
64
BAS 01 ATEX 7005
570
BAS 01 ATEX 7005
570
BAS 01 ATEX 7005
45
BAS 01 ATEX 7005
56
BAS 01 ATEX 7005
44
BAS 01 ATEX 7005
55
BAS 01 ATEX 7096
44
BAS 00 ATEX 7096
56
BAS 01 ATEX 7005
56
BAS 01 ATEX 7005
57
BAS 01 ATEX 7005
57 22
Z955 5
Z757
Z764 Z864 12121k1k11.6
Z964 12
Z765
Z765.F
Z857
Z865
Z865.F
Z961
Z961.F
Z961.H
10104.89
5
7
10
7
10
9
100
9
100
9
100
9
100
9
360
9
360
121k1k
15
100
15
100
15
100
15
100
4.89
9.78
7.14
7.14
7.14
17.4
17.4
17.4
11.6
11.6
14.7
14.7
14.7
14.7
14.7
14.7
8.7
8.7
8.7
8.7
8.7
8.7
12 12
24
9.8
9.8
4.9
9.8
9.8
4.9
98 98 98
98 98 98
352.8
352.8 355
980 980
490
980 980
490
98
98 49 98
98 49
499
499 998
729 729
1457
89 89
178
89 89
178
25 25 49
12 12
24
12 12
24
150
150 300 150
150 300
0..61
0.61
1.22
1.3
1.3
2.6
0.19
0.19
0.39
0.192
0.192
0.384
0.05
0.05
0.11
0.03
0.03
0.06
0.04
0.04
0.08
0.55
0.55
1.1
0.55
0.55
1.1
100
100
3.3
13.5
13.5
13.5
4.9
4.9
0.346
4.9
4.9
0.31
4.9
4.9
0.346
1.41
1.41
1.41
1.41
1.41
0.125
0.58
0.58
0.58
0.62
0.62
0.62
0.14
0.14
0.03
0.07
0.07
0.02
4.69
4.69
1.14
4.39
4.39
1.07
57 57
15.2
240 240
61
240 240
61
1.3
1.3
0.32
1.45
1.45
0.32
57
BAS 01 ATEX 7005
57 22
28
BAS 01 ATEX 7005 28 11
182
BAS 01 ATEX 7005
182
72
176
BAS 01 ATEX 7096
176
67
BAS 01 ATEX 7005
613 613 249
1.0
BAS 01 ATEX 7005
1.0
360
1.0
BAS 01 ATEX 7005
1.0
360
64
BAS 01 ATEX 7005
64 22 67
BAS 01 ATEX 7096
67 22
Date of issue 05/23/03
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
7
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Loading...
+ 16 hidden pages