Overvoltage suppressor (lightningprotection barrier)
20 mm ISO thread
• 2-wire protection
• For insulated C&I circuits
• Fulfills requirements to 500 V
insulation to earth, housing
components and other intrinsically
safe circuits
• Installation directly in the hazardous
area for protecting the field devices
• Discharge current 10 kA
• Simple installation in the free cable
gland on the field device
• Uninterruptable operation (auto
reset)
(red)
GND (green/yellow)
(black)
FS-LB-I
Function
By using an F*-LB-I, field devices and
control interface units are safely
protected from voltage surges due to
e. g. flash of lightning, switching
processes etc.).
This is accomplished by the derivation
of the higher current to ground and a
voltage limit during the high level pulse.
The continuous current capacity of the
circuit that is to be protected must not
exceed the rated operational current.
Composition
098916_ENG.xml 2003-03-24
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
1
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Technical Data
Supply
Rated voltage ≤ 48 V
Rated current ≤ 250 mA
Leakage current ≤ 5 µA
On-state voltage ≤ 85 V
Ground insulation ≥ 500 V breakdown voltage
Ambient conditions
Ambient temperature -30 ... 60 °C (243 ... 333 K) for Ex application; please observe declaration of conformity
Mechanical specifications
Housing material stainless steel 1.4401 (AISI 316)
Protection degree IP20
Data for application in conjunction
with hazardous areas
EC-Type Examination Certificate PTB 00 ATEX 2175 , conformity information is to consider
Group, category, type of protection,
Temperature classification
Voltage U
50 V
i
Type of protection [EEx ia and EEx ib]
Internal capacitance (EEx ia) negligibly small
Internal inductance (EEx ia) negligibly small
Nominal leakage current 10 kA (8/20 µs) per core according to IEC 60-2
Nominal response time
Symmetrical 1 ns
Asymmetric 100 ns
Bandwidth ≥ 40 kHz
surface all over polished
¬ II 2 G EEx ia IIC T6
FS-LB-I
Notes
Surge protectors must always be connected to a solid ground (large cross sections, short wiring). This is the basic requirement
for an effective protection.
Examples:
Terminal box
22
GND
Length 400 mm
Cross sectional area 1.0 mm
M20 x 1.5 or
PG13.5 or ½" NPT
55
Transmitter
22
F*-LB-I
F*-LB-I
098916_ENG.xml 2003-03-24
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
2