Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing,
performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication may be
photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
DAMAGE CLAIMS / LOST EQUIPMENT
Thoroughly examine all components and units as soon as they are received. If any cartons are damaged or missing, write a complete
and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the inspection and sign
the description. Refuse only the damaged product, not the entire shipment.
VEEDER-ROOT’S PREFERRED CARRIER
1.Contact VR Customer Service at 800-873-3313 with the specific part numbers and quantities that were missing or received
damaged.
2. Fax signed Bill of Lading (BOL) to VR Customer Service at 800-234-5350.
3.VR will file the claim with the carrier and replace the damaged/missing product at no charge to the customer. Customer Service
will work with production facility to have the replacement product shipped as soon as possible.
CUSTOMER’S PREFERRED CARRIER
1.It is the customer’s responsibility to file a claim with their carrier.
2.Customer may submit a replacement purchase order. Customer is responsible for all charges and freight associated with
replacement order. Customer Service will work with production facility to have the replacement product shipped as soon as
possible.
3.If “lost” equipment is delivered at a later date and is not needed, VR will allow a Return to Stock without a restocking fee.
4.VR will NOT be responsible for any compensation when a customer chooses their own carrier.
RETURN SHIPPING
For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy" and "Parts Return"
pages in the "Policies and Literature" section of the Veeder-Root North American Environmental Products price list.
Relat e d Ma n ua l s ............ .. .......... ... .. .......... .. .......... .. ... .......... .. .......... .. ... ......... ... ......... ... ....2
Wire Gauges - Color coded...........................................................................4
Power Wiring ............................................................................................................4
Probe Ju n c tion Boxes . .......... .. .. .......... ... ......... ... .. .......... .. .......... ... .. .......... .. .......... .. ..4
Probe W ir in g Sa fe t y Is s ue s ....... ... ......... ... .. .......... .. .......... ... .. .......... .. .......... .. ... ......... ... .... 5
Selec ti n g a Con so l e L oc a ti o n ......... .. .......... ... .. .......... .. .......... .. ... .......... .. .......... .. ... ......... ..5
Console Installation
Mounting the Con s o le .............. .. ... ......... ... ......... ... .. .......... ... ......... ... .. .......... .. .......... .. .......7
Wirin g th e Con s o le ...... ......... ... .. .......... .. .......... .. ... .......... .. .......... .. ... ......... ... .......... .. .. ....... 9
Probe Installation
Probe M a n ho le In s ta ll at i o n ........ ... .. .......... .. .......... .. .......... ... .. .......... .. .......... .. ... ......... ... ..10
Determining Mag Probe Length for Installation in a Dedicated Riser ............................ .10
RS-2 3 2 Co nn e c ti on s . .......... .. .......... .. ... .......... .. .......... .. ... ......... ... .......... .. .. .......... ... .........22
To a Devi ce Less Than 50 Feet fro m th e Con so l e... ... .. .......... .. .......... .. ... ......... ... ..22
To a Device More Than 50 Feet from the Console........................... .......... .......... .22
Surge P ro te c tion for Com mu n ication Dev ic e s ...... .. .......... ... .. .......... .. .......... .. ... ......... ... ..23
Syste m S er ia l S e cu r ity ..... ... .......... .. .. .......... ... ......... ... .. .......... .. .......... ... ......... ... .. .......... ..24
RS-2 3 2 Se ria l C o m mu n ic a tio n Se t up .... ... .. .......... .. .......... ... .. .......... .. .......... .. ... ......... ... ..24
Figure 26.Replacing PROM Chip (Keyp ad/Display version shown).........................65
v
Page 6
Introduction
Label on top of console
This manual describes the site preparation and console installation procedures for all TLS-50 Monitoring Systems.
Except where noted, the procedures described herein apply to all consoles. TLS-50 is used throughout Table 1
lists the various TLS-50 consoles and options by form number. Figure 1 shows where on the top of the console
you can find the information about your console’s form number.
Table 1.- TLS-50 Consoles and Features
Console Form No.Console T ype
8469X0-060TLS-50 w/keypad and display, up to 6 probes
8469X0-160TLS-50 w/keypad and display, w/relay, up to 6 probes
8469X0-260TLS-50 w/keypad and display, w/com and relay, up to 6 probes
8469X0-230TLS-50C w/o keypad or display, w/com, up to 3 probes
8469X0-460TLS-50 w/o keypad or display, w/com and relay, up to 6 probes
This manual assumes that you installing the monitoring system in a new site (before pavement is put down and
with no wiring runs in place). Some of the topics covered in this manual are listed below.
•
Laying out the site
•
Mounting the console and connecting power wiring
•
Assembling and installing probes
•
Installing wiring conduit between the console and probes
•
Field wiring probes
•
Connecting probes to the console
•
RS-232 serial communication connection requirements and available serial commands (consoles with com
option)
•
Troubleshooting information
1
Page 7
IntroductionRelated Manuals
•
TLS-50 system specifications
After the console is wired to its power source and probes, you should program the console following the setup
instructions contained in the TLS-50 Setup & Operation Manual.
Related Manuals
577013-609TLS-50 Setup & Operation Manual
576013-635RS-232 Serial Interface Manual
576013-859Direct Burial Cable Installation Manual
577013-744Mag Plus Probe Assembly Guide
Safety Symbols
The following safety symbols are used in this manual to alert you to important safety hazards and precautions.
EXPLOSIVE
Fuels and their vapors are extremely
explosive if ignited.
ELECTRICITY
High voltage exists in, and is supplied
to, the device. A potential shock hazard exists.
INJURY
Careless or imp roper handling of
materi als can resul t in bo di ly injury.
WEAR EYE PROTECTION
Fuel spray from residual pressure in
the lines can cause serious eye injuries. Always wear eye protection.
WARNING
Heed the adjacent inst ructions to
av oi d equ ip me nt d amage or pe rson al
injury.
FLAMMABLE
Fuels and their vapors are extremely
flammable.
TURN POWER OFF
OFF
Live power to a device creates a
potential shock hazard. Turn Off
power to the device and associated
accessories when servicing the uni t.
GLOVES
Wear gloves to protect hands from
irritation or injury.
READ ALL RELATED MANUALS
Knowledge of all rel ated procedures
before you begi n wo rk is impor t an t .
Read and understand all manuals
thoroughly. If you do not underst an d
a procedure, ask someone who does.
STATIC SENSITIVE COMPONENTS
Handling static se ns itive electr o nic
components without grounding your
body can subject them to damaging
voltage po tentials.
2
Page 8
Site Considerations
g
Control Drawing
Double Wall Tank
MP
MP
I.S.
Circuit breaker panel
or Fused, switched,
neon indication spur
120 or 240 Vac
12 AWG barrier
ground wire
I.S.
NOTE: Intrinsically safe wiring (marked ) shall be installed in
accordance with Article 504-20 of the NEC, ANSI/NFPA 70.
Note: conduit requirements are dependent on local electrical regulations.
For probe-to-console wiring, shielded cable is required regardless of
conduit requirements.
WARNING:
Substitution of components may impair intrinsic safety.
Circuitry within the TLS-50 Console barrier forms an intrinsically safe,
energy-limited system. This system makes TLS-50 probes safe for use in
a Class I, Group D hazardous location. TLS-50 probe wiring is intrinsically
safe only when connected to Veeder-Root's TLS-50 Consoles. Reference
Form Number 8469 (TLS-50/TLS-50C Consoles) and Form Number
8462, 8463, 8468, and 8473 (Probes).
I.S.
Non-Hazardous
Area
ALL FUNCTIONS NORMAL
PA
T1 VOL: 9889 GAL
Hazardous
Area
TLS-50
Single Wall Tank
MP
le Wall Tank
Sin
DP
DISPENSERS
Hazardous Area
LEGEND
Magnetostrictive Probe
MP
Expoxy Sealed Connection in
a Weatherproof Junction Box
Seal-Off
Terminal Connection
1/2'' (12.7 mm) Rigid Conduit
IS
Conduit Enters Console in an
Intrinsically Safe Area Knockout
PA
Conduit Enters Console in a
Power Area Knockout
Product piping
consoles\50sysdia.eps
Figure 2. Control Drawing - Example TLS-50 System Site Layout
3
Page 9
Site Consid era tion sNational Electrical Code Compliance
National Electrical Code Compliance
The following information is for general reference and is not intended to replace recommended National Electric
Code (NEC) procedures. It is important for the installer to understand that electrical equipment and wiring located
in Class I, Division 1 and 2 installations shall comply with the latest appropriate articles found in the National
Electric Code (NFPA 70) and the Automotive and Marine Service Station Code (NFPA 30A), or other local code
such as the CEC, Canadian Electrical Code.
PROBE-TO-CONSOLE WIRING
Shielded Cable or Veeder-Root Direct Burial Cable Required
To ensure the best operating systems available, Veeder-Root REQUIRES the use of shielded cable for all probes
regardless of conduit material or application. In these installations, shielded cable must be rated less than 100 pF/
foot (100 pF/304 mm) and be manufactured with a material suitable for the environment, such as Carol
or Belden
™
88760, 876 0, o r 8770.
Note: Throughout this manual, when mentioning any cable being used for probe-to-console wiring, it will be
referring to shielded cable.
Wire Length
Improper system operation could result in undetected potential environmental and health hazards if the probe-toconsole wire runs exceed 1000 feet (304 m). Wire runs must be less than 1000 feet to meet intrinsic safety
requirements.
™
C2534
Splices
Veeder-Root recommends that no splices be made in the wire run between a probe junction box and the console.
Each splice degrades signal strength and could result in poor system performance.
Wire Gauges - Color coded
•
Shielded cable must be used in all installations. Probe-to-console wires should be #14 - #18 AWG (2.5 to 0.8
2
) stranded copper wire and installed as a Class 1 circuit. As an alternate method when approved by the
mm
local authority having jurisdiction, #22 AWG (>0.3 mm
2
) wires such as Belden 88761 may be suitable in
installations with the following provisions:
- Wire run is less than 750 feet (228 m)
- Capacitance does not exceed 100 pF/foot (100 pF/304 mm)
μ
- Inductance does not exceed 0.2
•
Total cable length per installation: 22,000 feet (6700 m).
H/foot (0.2 μH/304 mm)
POWER WIRING
2
Wires carrying 120 or 240 Vac from the power panel to the console should be #14 AWG (2.5 mm
for line, neutral and chassis ground (3); and #12 AWG (4 mm
2
) copper wire for barrier ground (1).
) copper wire
PROBE JUNCTION BOXES
Weatherproof electrical junction boxes with a gasketed cover are required on the end of each probe conduit run at
the manhole location. Gasketing or sealing compound must be used at each entry to the junction box to ensure a
waterproof junction. The interior volume of each junction box must be a minimum of 16 cubic inches (262 cm
3
).
Veeder-Root recommends the following junction box or equivalent:
•
Appleton Electric Co. - JBDX junction box, JBK-B cover, and JB-GK-V gasket.
Probes operate in area s wher e flammabl e li quid s and ex plos ive v apors may be
present.
Improper installation may result in fire or explosion causing serious injury or
death.
Practice the following:
1. Read thoroughly and f ollow the instructions shipped with each probe.
2. Probe wiring must enter the consol e only thr ough their designated areas.
3. Power wires and condui t must not enter the intrinsically safe
compartment of the console.
4. Substitution of components may impair intrinsi c safety.
Wiring between the console and the probes is of limited electrical power so that there is insufficient energy to
ignite fuel. In the console, the low power probe wiring is considered intrinsically safe because it is physically
isolated from all high power wiring. To maintain the integrity of this safety feature probe wiring can not share the
same conduit with power wiring. In addition, probe cables can only enter the console through the designated
intrinsically safe area knockouts.
If the TLS-50 System is being retrofitted into a paved site, you can cut grooves in the pavement, run direct burial
cable to the probes, and then seal over the cable grooves, subject to approval of the local authority having
jurisdiction.
Before trenching, you should diagram all conduit runs between the console’s intended location and its deployed
probes. Your site diagram will help you calculate conduit and wiring lengths, and necessary quantities of junction
boxes, sealing boxes, clamps, brackets, etc.
Throughout this planning process and in the actual installation, you must follow all latest National Electric Codes,
and applicable federal, state, and local codes as regards conduit type, depth below grade, sealing, grounding,
wire capacities, direct burial (if permitted), etc.
Selecting a Console Location
WARNING
Explosive vapors or flammable liquid s could be pre sent near locations where
fuels are stored or being dispensed. The TLS-50 Console is not explosion
proof.
An explosion or fire resulting in serious injury or death, property loss and
equipment damage could occur if the console is installed in a volatile,
combustible or explosive atmosphere (Class I, Division 1 or 2).
Do not install this c onsole in a v olatile, comb ustib le, or e xplosiv e atmosph ere.
5
Page 11
Site Consid era tion sSelecting a Console Location
Select a mounting location on the inside of any building. The console must be protected from severe vibration,
extremes in temperature and humidity, rain, and other conditions that could harm computerized electronic
equipment.
The equipment is designed to operate safely under the following range of conditions:
•
Temperature range 0 to 40°C - ( storage temperature range of -40 to +74°C).
•
A maximum relative humidity of 95% RH (non-condensing) at temperatures up to 40°C.
•
Console may be powered by either 120 or 240 Vac. A switchmode power supply automatically detects the
input voltage (no jumpers required).
•
Main supply voltage fluctuations not exceeding ±10%.
•
Pollution Degree Category 2.
•
Installation Category II.
Important! Consoles must be installed within the interior of buildings. They are not suitable for any external
location.
Ensure that the console is located where neither the console nor its associated cabling will be damaged by doors,
furniture, barrows, etc. Consider the ease of routing wiring, ducting, and probe cables to the console. Check that
the mounting surface is strong enough to support the console’s weight of about 4 pounds.
Important! If the unit requires cleaning, do not use any liquids, wipe only with a clean, dry cloth.
6
Page 12
Console Installation
consoles\tls-50\50mnt.eps
T
O
s
f
m
d
Mounting the Console
Figure 3 illustrates recommended console mounting. Install the console fastening devices to the mounting surface
using the hole pattern (6.7” x 5.7”) shown in Figure 4. Mounting screws up to 3/16” diameter may be used.
Install metal conduit (1/2” I.P.S.) between the console and the power panel. Figure 4 shows the three designated
knockouts (one each on top, left side, and bottom) through which power wiring can safely enter the console.
1000 mm
(Maximum)
ALL FUNCTIONS NORMAL
T1 VOL: 9889 GAL
TLS-50
o an external alarm (i.e., Forecourt Alarm)-
ne 2 ampere fused, switched, neon indication
pur or a dedicated circuit breaker rated
or 120 Vac or 240 Vac. NOTE, circuit breaker
ust be marked as the external alarm
isconnect for the console.
One 5 ampere fused, switched, neon
indication spur (for 240 Vac), or a dedicated
circuit breaker rated for 15 amperes, 120 Vac
or 240 Vac. NOTE, circuit breaker must be
marked as the power disconnect for the console.
From an independent 24 hour supply at the distribution
panel, run three 2.5 mm (minimum) standard color coded
wires; live, neutral, and earth, to the fused spur. Run one
4 mm wire, color coded green/yellow, from the earth bus
bar at the distribution panel direct to the console location.
Leave at least 1 metre of free cable for connection to the
console.
1/2-inch IPS and .56 inch (22 & 14 mm)
Power wiring only - conduit knockouts
(4 places)
1.25''
(32 mm)
3.75"
(95mm)
1/2, 3/4, & 1 inch IPS (22, 28, & 35 mm)
Intrinsically safe wiring only - conduit knockouts
(2 places)
0.93''
0.4''
(10 mm)
(24 mm)
1.18''
2" (51 mm
Figure 4. Console Dimensions and Designated Conduit Knockouts
8
Page 14
Console InstallationWiring the Console
A
t
A
w
Wiring the Console
WARNING
The console contains voltages which can be letha l. It is connected to devices
that must be intrinsically safe.
Connecting power wires to a live circuit can cause electrical shock that may
resul t in serious inju r y o r dea th.
OFF
1. Turn power off at the circuit breaker connecting the power supply wires.
2. Attach conduit from the power panel to the console's Power Area
knockouts only (1 on top and bottom, ref. Figure 4).
1. Pull four wires between the power panel and the console; three #14 AWG color-coded wires for AC line (L),
AC neutral (N) and chassis ground; and one #12 AWG (4 mm
2
) green and yellow wire for barrier ground.
For international applications using 240 Vac, pull four wires between the power panel and a 5 A fused,
switched, neon indication spur; three #14 AWG color-coded wires for AC line (L), AC neutral (N) and chassis
2
ground; and one #12 AWG (4 mm
) green and yellow wire for barrier ground. Pull four identical wires be-
tween the spur and the console.
2. Open the right door of the console and connect the four power/ground wires as shown in [Figure 5]. Do not
connect the power wires to breaker panel at this time.
L2 L4
WARNING!
ttach neutral wire to top
erminal ("N") of J4
CONSOLE
POWER
RELAY RATING
120/240 VAC
2 A MAX
Attach hot wire to bottom
terminal ("L") of J4
ttach chassis ground
ire to ground lug
N
J4
C24C27
L
J5
1234
OPEN
SW1
SEC
SETUP
J3
POWER WIRING NOTES:
1. Barrier ground must be #12 AWG (4 mm
or larger diameter.
2. Check to be sure that the electrical resistance
between the console ground lug and a known
good earth ground is less than 1 ohm.
3. Connect the power supply wires in the power
panel to a separate dedicated circuit.
4. Electrical rating power input -- 120 Vac or
240 Vac, 50/60 Hz, 2 A maximum.
5. See the "Console Dimensions and Designated
Conduit Knockouts" figure for actual locations of
power conduit knockouts into the console. Power
wiring must enter only in Power Area conduit
knockouts.
Protective Earthing
Conductor (Green and
Yellow) Attach #12AWG
2
(4 mm
) barrier ground
wire to ground lug
Shock hazard. Do not
touch metal ends of
capacitors C24/C27
or the metal bands
on chokes L2/L4.
2
)
WARNING
SUBSTITUTION OF COMPONENTS
MAY IMPAIR INTRINSIC SAFETY.
NO REPAIRS SHOULD BE ATTEMPTED.
REFER SERVICING TO QUALIFIED
PERSONNEL ONLY.
PROBE 6
PROBE 5
PROBE 4
PROBE 3
PROBE 2
PROBE 1
AVERTISSEMENT
LA SUBSTITUTION DE COMPOSANTS
PEUT COMPROMETTRE LA SECURITE
INTRINSEQUE.
+
+
+
+
+
+
consoles\tls50\50powr.eps
Power
Side
Intrinsically
Safe Side
Figure 5. Wiring AC Power to the Console
9
Page 15
Probe Installation
Probe Manhole Installation
At each underground probe location, install a 14-inch (355 mm) minimum diameter approved manhole according
to the manufacturer’s instructions (Note: probes should be located at least 24 inches (610 mm) from the
submersible pump to avoid erroneous probe readings when the pump is running). Position the manhole so that
there is necessary clearance for junction box installation and wiring.
Determining Mag Probe Length for Installation in a Dedicated Riser
1. Measure the distance from the bottom of the tank to the top of the probe manway - this is the minimum probe
length (ref. Figure 6).
2. The probe canister must be within the riser pipe (minimum length of 10 inches [254mm]).
3" (76mm) min. clearance from
top of canister to top of riser
10" (254mm) minimum
riser length
Probe canister must
be within riser pipe
Manway cover
STP manway
Tank
probes\probemeasurement.eps
24" ( 610 mm) min.
Top of probe
manway
Minimum
Probe length
Figure 6. Determining the Minimum Mag Probe Length
Probe Installation
1. Turn OFF power to the console.
2. Remove any sludge from the bottom of the tank.
3. Check that floats, boot, and cable are assembled correctly on probe (ref. Mag Probe Assembly Manual).
4. Gently slide the float(s) to the bottom of the probe shaft before raising the probe. Carefully lower the probe into
the riser pipe until the boot rests on the bottom of the tank [See Figure 7 for UST installation or Figure 8 for
AST installation].
10
Page 16
Probe InstallationProbe Installation
e
CAUTION! Handle probes carefully. Striking or dropping the probe will result in loss of calibration and could
cause permanent damage.
14'' min. dia. manhole
Riser cap with cord grip
bushing and nut
Concrete slab or packed
earth per NFPA 80
A = 14" minimum for global mag
plus/mag plus probes. When
installing a probe longer than the
the tank diameter, increase this
minimum dimension to compensate.
(Example: a 7'-6'' diameter tank will
use an 8' probe, in which case you
must add 6" to minimum riser length
'A', i.e., 20").
Use bushing and body of grip
fitting supplied with probe and
Adaptor nut supplied with
AST kit.
Riser pipe: 2-, 3-, or 4'' API
schedule 40 - depending on
probe type
A = 14" minimum for global mag
plus/mag plus probes. When
installing a probe longer than the
the tank diameter, increase this
minimum dimension to compensate.
(Example: a 7'-6'' diameter tank will
use an 8' probe, in which case you
must add 6" to minimum riser length
'A', i.e., 20").
.
.
.
.
.
.
.
.
.
.
.
..
.
Tank
Mag Probe
(rests on bottom)
Probe cable
Weatherproof junction box with 1/2" NPT
threads (16 cubic inch minimum)
Cord grip seals
.
.
.
.
.
.
.
.
.
.
.
..
.
Seal-off, epoxy seal per NFPA spec
A
1/2" Rigid conduit (to Console)
Riser pipe: 2-, 3-, or 4'' API schedule 40
depending on probe type (To prevent
erroneous probe readings, install probe
riser a minimum of 24'' from the submersibl
pump.)
Split-Ring Collar
(P/N 576008-617)
required if probe
enters the riser.
Top view
3/4" ID
Side view
probes\pbinstcen.eps
Figure 7. TLS-50 Probe Installation Example - Underground Storage Tank
Flexible metal conduit
supplied with AST kit
Liquidtight
fittings from
AST kit
Weatherproof junction box with
1/2" NPT threads (16 cubic inch
minimum)
Epoxy seal per NFPA specs
A
Split-Ring Collar
(P/N 576008-617)
required if probe
enters the riser.
Top view
3/4" ID
Side view
Rigid conduit
probes\astpbins.eps
Mag Probe
(rests on bottom)
Figure 8. TLS-50 Probe Installation Example - Above ground Storage Tank
11
Page 17
Probe InstallationProbe Installation
A
SPECIAL INSTRUCTIONS FOR UST’S WITH METAL RISER CAPS
If you are installing the metal cap and adapter ring, screw the ring onto the 4” riser until the gasket contacts the
pipe, then use a pipe wrench to tighten it an additional 3/4 turn. Push the cable through the metal cap and cord
grip, then clamp the cap onto the ring.
At sites that require installation of a riser adaptor (Phil-Tite M/F 4X4 or equivalent) at the top of the riser, do so
following the manufacturer’s instructions. Next screw the adapter ring from the Veeder-Root kit (
P/N 312020-952)
onto the riser adaptor by hand until the gasket contacts the sealing surface. Then use a torque wrench attached to
an appropriate strap wrench (K-D Specialty tools nylon strap oil filter wrench, or equivalent) and tighten the ring to
35 - 45 ft-lbs. Loosen the cord grip nut and push the cable through the metal cap and cord grip, then clamp the
cap onto the ring (see Figure 9).
Make sure there is a minimal amount of slack between the probe and cap, then tighten the cord grip nut until the
cable is held firmly. Push the end of the cable through the field J-box cord grip, then tighten that cord grip nut as
well. Splice and seal the wires in the J-box as shown in Figure 12.
.
.
.
.
.
.
.
.
.
..
Metal cap from kit
dapter ring from kit
Riser adaptor
(Phil-Tite M/F4X4,
or equivalent)
probes\riseradapt.eps
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
Tank
Figure 9. Installing the Riser Adapter
12
Page 18
Probe InstallationInstalling Field Wiring from Probes to TLS-50 Console
Installing Field Wiring from Probes to TLS-50 Console
Two wiring run methods are commonly used for probes - Shielded wiring pulled through buried, sealed 1/2” rigid
conduit (discussed in the following paragraphs); or direct burial cable (discussed on page 15).
WARNING
Probes operate in areas where flammable liquids and explosive vapors may be present.
Improper inst all atio n may res ult in fir e or explo si on causi ng se rious injury or death.
Practice the f ollowing:
1. Read thoroughly and follow the instructions shipped with each probe.
2. Probe wiring conduit must not contain any other wires.
3. Probe wiring and conduits must enter the console only through their designated
areas ( se e Figure 4).
4. Power and communication wires and conduit must not enter the intrinsically safe
compartment of the conso le. (see Fi gure 4).
Buried Rigid Conduit
The preferred method, especially in new sites before driveway surfaces are paved, is to pull probe wiring through
buried 1/2” rigid conduit [Figure 10].
Weatherproof junction
box with 1/2-inch N.P.T.
threads (16 cubic inch
Splice Closure
Seal-Off
minimum)
Cord grip seals
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
..
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Epoxy seal per NFPA spec
1/2'' rigid conduit (to console)
Tank
probes\pconduit.eps
Figure 10. Example Probe Wiring Run in Buried Rigid Conduit
Pull shielded cable consisting of two conductors, color-coded #14-18 AWG stranded copper wire, between the
console and the junction box at each
probe location (do not gang wires together). Use single lengths of wire with
no splices to ensure optimum signal strength.
IMPORTANT! Maximum probe-to-console cable length is 1000 feet (305m).
Since wires for multiple probes may enter the console through a single conduit, it is recommended that you use a
different color-code for each wire or individually mark each wire to identify probe inputs. Also, if the intrinsically
safe wires enter the building in a wiring trough, only intrinsically safe wires (from TLS-50/-50C probes) can be in
the trough. Keep all low power (intrinsically safe) wiring physically isolated from high power wires in all wiring
troughs per the NEC.
13
Page 19
Probe InstallationBuried Rigid Conduit
e
p
SEALING FIELD CONNECTIONS
1. Pull the wires from the probe canister into the junction box. Pull two wires from the console through the seal-off
box and into the junction box.
2. Using wire nuts, connect the two wires from the probe to the two wires coming from the console. Be sure to
observe color codes or tags when making these connections. Figure 11 diagrams a typical probe field wiring
connection in the junction box.
3. Do NOT terminate drain wire at this location, ground drain wire at console only.
4. Seal wire nuts with epoxy sealant using one bag for two-wire nut connections (Figure 12).
5. Push the tie-wrapped, epoxy sealed bag into the junction box. Replace and tighten the junction box cover.
Do not ground drain wire
in junction box
To
PROBE
Terminal
Seal-off
Block In
Console
1/2'' rigid
conduit
robes\3mpwir.eps
Epoxy sealed connections in a
weatherproof junction box
ACB
Instructions:
NOTE: When temperature is below 50˚F (10˚C), keep
resin in a warm place prior to mixing (e.g., in an
inside pocket next to body).
1. Open epoxy sealant package, and remove resin pak.
2. Holding resin pak as shown in A, bend pak along long
length.
3. As shown in B, firmly squeeze the RED SIDE of the
resin, forcing it through the center seal and into
BLACK SIDE.
Black
From
Prob
White
Figure 11. Probe Field Wiring Connection
From probe,
sensor, or
transducer
Make sure that
the ends of cable
sheathing are submerged in sealant
4. Mix thoroughly to a uniform color by squeezing
contents back and forth 25-30 times.
5. Squeeze mixed, warm resin into one end of bag and
cutoff other end.
6. Slowly insert wiring connections into sealing pack
until they fit snugly against the opposite end as
shown in C.
7. Twist open end of bag and use tie wrap to close it off
and position the tie wrapped end up until the resin
jells.
To console
Tie wrap
Wire nuts
CAUTION: Epoxy sealant is irritating to eyes, respiratory system,
and skin. Can cause allergic skin reaction. Contains: epoxy resin
and Cycloaliphatic epoxycarboxylate.
Precautions: Wear suitable protective clothing, gloves, eye, and
face protection. Use only in well ventilated areas. Wash
thoroughly before eating, drinking, or smoking.
consoles\epxy2w.eps
Figure 12. Epoxy Sealing Conn ect ion s
14
Page 20
Probe InstallationDirect Burial Cable - Probe to Console Field Wiring
G
n.
Direct Burial Cable - Probe to Console Field Wiring
An alternative to trenching through existing pavement is to use direct burial cable.
IMPORTANT! Maximum probe-to-console cable length is 1000 feet (305m).
Prior to installing direct burial cable with epoxy splices, consult with the local authority having jurisdiction. Use of
direct burial cable is only allowed in locations where local codes permit the use of buried cable.
The direct burial method requires grinding a 1/4” to 3/8” wide by 1-1/4” deep groove (adding 1/4” of depth for
each additional cable) in the pavement surface, laying Veeder-Root supplied direct burial cable down in the bottom
of the groove, laying an expanded polyethylene foam backer rod over the cable(s), and then a placing a 1/4” to 1/
2” bead of Veeder-Root recommended silicone sealant over the backer rod to within a minimum of 3/8” below the
pavement surface [see Figure 13].
If you decide to use the direct burial method, you should order the Veeder-Root Direct Burial Cable Preparation
Kit, P/N 848100-500.
Splice closure
Cord grip
rade
.
.
.
..
Epoxy filled
splice
enclosure
Drill oversized hole
in manhole for cable
890-SL silicone sealant
SOF ROD backer rod
1
2
Direct burial cable
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
CONCRETE
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
...
Seal-off
Rigid conduit
3'' Mi
ASPHALT
EARTH
1
Dow Corning Silicone Pavement Sealant
2
Expanded polyethylene foam rod - trademark of
Applied-Extrusion Technologies.
probes\pdburial.eps
Figure 13. Example Probe Wiring Run via Direct Burial Cable
DIRECT BURIAL CABLE FIELD WIRING
When using direct burial cable for probe-to-console wiring runs, the wiring connections are the same as shown in
Figure 11 on page 14, but the sealing materials and procedure is completely different. If you are using Direct
Burial Cable you seal the field wiring connections as instructed in the Direct Burial Cable Installation Manual.
15
Page 21
Probe InstallationConnecting Probes to the Console
Connecting Probes to the Console
WARNING
The equipment is used in location where lethal voltages and explosive vapors
or flammable fuels may be present.
Care must be taken when installing, servicing or replacing part s in the syst em
or serious injury or death from explosion, fire or shock may occur.
For this system:
1. Comply with the latest Nati onal Electric Code, feder al, state, and local
codes, and an y other a pplicab le safet y codes . In ad diti on, take necess ary
precautions during installation, service, and re pair to prevent personal
injury, property loss and equipm ent damage.
2. Refer servicing to trained and qualified personnel only.
3. Substitution of components may impair intrinsi c safety.
OFF
4. Be sure AC power is “Off” before opening the console panel cover and
connecting probe wires. Do not short any voltage across any barrier
terminal including probes.
Precautions To Follow When Connecting Probes to TLS-50 Console
To The Installer! You Must Read And Understand This Information.
INPUT/OUTPUT WIRING POSITIONS AND LABELING
In all cases, the devices wired to the console’s input/output terminal blocks must be recorded to prevent
improper replacement during installation or service. A circuit directory is listed below for this purpose.
During programming, the probes wired to each position are identified and stored in memory. If a probe is removed
and reconnected to a different set of input terminals after programming, the system will not properly recognize the
data being received.
Wiring Assignments
1. Identify all probe wires according to their terminal block location using the self-adhesive numbering labels
furnished. Accurately record on the circuit directory in Figure 14 the location of each probe as you attach wires to the probe input terminal block.
2. Important! Once a device has been wired to certain terminals and the system has been programmed, the wires
from that device may not be relocated to other terminals without reprogramming the system.
16
Page 22
Probe InstallationPrecau t i on s To Follow When Conn ec ting Probe s to TL S- 50 Co ns ol e
consoles\tls50\prbtnk.eps
drain wire to grounding lug
Probe Number
PROBE 1 IN
TANK
TANK Number & Product
PROBE 2 IN TANK
PROBE 3 IN TANK
PROBE 4 IN TANK
PROBE 5 IN TANK
PROBE 6 IN TANK
Figure 14. Prob e Ins t al lation Dire ctory
Grounding Probe Shields and Drain Wires
Connect probe cable shields and drain wires to ground in the console only, not at the field junction boxes. Do not
ground both ends of the shield.
CONNECTING PROBES TO THE CONSOLE - OBSERVE POLARITY
Connect the two color-coded/marked wires from the each probe to the appropriate terminals of the Probe Terminal
Block as shown in Figure 15.
SW 1
SW1
WARNING
SUBSTITUTION OF COMPONENTS
MAY IMPAIR INTRINSIC SAFETY.
OPEN
J3
1234
SEC
SETUP
Attach probe cable shield and/or
NO REPAIRS SHOULD BE ATTEMPTED.
REFER SERVICING TO QUALIFIED
PERSONNEL ONLY.
PROBE 6
PROBE 5
PROBE 4
PROBE 3
PROBE 2
PROBE 1
AVERTISSEMENT
LA SUBSTITUTIONDE COMPOSANTS
PEUT COMPROMETTRE LA SECURITE
INTRINSEQUE.
+
+
+
+
+
+
Black wire from probe
connects to terminal
White wire from probe
connects to + terminal
consoles\tls50\50prbwir.eps
Figure 15. Connecting Probe Wiring to Console (TLS-50C has 3 probe inputs only)
17
Page 23
Probe InstallationSystem Setup Security
p
System Setup Security
To protect against unauthorized access to system operation DIP switch 4 of SW1 on the Power Supply board lets
you lockout setup and diagnostic menus after making initial programming (for consoles w/display only). Consoles
are shipped from the factory with this switch in the open (disabled) position.
See Figure 15 for location of this switch. Figure 16 shows the switch in the closed position, enabling setup
lockout. Switch 2 and Switch 3 are not used and can be in any position.
1 2 3 4
OPEN
Sw 4 - blocks access to
SETUP
setup/diag menus after setu
(consoles w/display only)
consoles\tls50\sw4.eps
Figure 16. DIP switch 4 in closed position to enable menu lockout
Overfill Alarm Relay
All consoles except those having form numbers 8469X0-060 and 8469X0-230 have one dry contact relay output
that closes when an overfill alarm is activated. You can connect an external audible/visual warning device to this
relay.
Important! Note these Output Relay Connection Restrictions:
1. Do not connect output relays to a device that draws more than 2 amperes of current. Output power: output
relay contact, resistive load - 120/240 Vac, 2 A max.
2. Alarm relays cannot be used for flow control. Alarm relays provide only a momentary closure and cannot
actuate flow control devices such as valves and pump motor relays for extended periods of time.
OFF
With power to the console turned Off, connect the two wires from the external warning device to the either of the
two overfill relay terminals (J5) [see Figure 17].
18
Page 24
Probe InstallationOverfill Alarm Relay
A
t
d
J
WARNING
SUBSTITUTION OF COMPONENTS
CONSOLE
POWER
RELAY RATING
120/240 VAC
2 A MAX
SW1
N
J4
L
J5
1234
OPEN
SEC
SETUP
MAY IMPAIR INTRINSIC SAFETY.
NO REPAIRS SHOULD BE ATTEMPTED.
REFER SERVICING TO QUALIFIED
PERSONNEL ONLY.
PROBE 1
PROBE 2
PROBE 3
PROBE 4
PROBE 5
PROBE 6
+
+
+
+
+
+
ttach the two wires from
he remote overfill warning
evice to the two terminals
5 (no polarity)
J3
AVERTISSEMENT
LA SUBSTITUTION DE COMPOSANTS
PEUT COMPROMETTRE LA SECURITE
INTRINSEQUE.
consoles\tls50\50ovrrly.eps
Power
Side
Intrinsically
Safe Side
Figure 17. Connecting I/O Devices to Console
19
Page 25
Applying Power to System
Cold Boot - Initial Power Up (Consoles w/Display)
Once all devices are connected to the console, attach the console power wires to the appropriate power panel
connections. Close the front panel of the console. Switch on the AC power breaker. The system will automatically
run a cold boot self-diagnostic program when you power up the console for the first time:
Tes t P a ss e d
RAM TEST - OKRAM FAILReplace CPU board
ROM TEST - OKROM FA IL“““
COLD BOOT
EEPROM TEST - OKEEPROM FAIL
STARTUP COMPLETE
Following a cold boot the display will read:
NO TANKS CONFIGURED
Follow the Setup instructions in the TLS-50 Setup and Operation Manual to program the system.
Test Failed Action (If Failed)
“““
Cold Boot - Initial Power Up (Consoles w/o Display)
Once all devices are connected to the console, attach the console power wires to the appropriate power panel
connections. Close the front panel of the console. Switch on the AC power breaker. The system will automatically
run a cold boot self-diagnostic program when you power up the console for the first time. Wait 30 seconds and
then follow the Setup instructions in the TLS-50 Setup and Operation Manual to program the system.
Test Failed
Unit fails to communicate Check “RS-232 Serial Communication Setup” on page 24. If comm settings are
correct, replace CPU board.
Action (If Failed)
Cold Boot - RAM Clear
If the system has previously been setup, a cold boot can be initiated and the system reset (such as for a software
upgrade) as follows:
CONSOLES WITH DISPLAY
Move the RAM clear jumper (J3 in Figure 5) off of pins 1 and 2 and onto pins 2 and 3. The display will
acknowledge the RAM clear request with the message: RAM CLEAR, then turn the power Off. Move the jumper
back onto pins 1 and 2.
CONSOLES WITHOUT DISPLAY
Turn off the power to the unit, move the RAM clear jumper (J3 in Figure 5) off of pins 1 and 2 and onto pins 2 and
3. Turn on the power for 5 seconds, then turn the power off. Move the jumper back onto pins 1 and 2.
20
Page 26
Applying Power to SystemWarm Boot
Warm Boot
CONSOLES WITH DISPLAY
Once the system is setup, every time power to consoles is switched Off and On, the software will run a selfdiagnostic warm boot program and display the test results:
Test Passed
RAM TEST - OKRAM F AILReplace CPU board
ROM TEST - OKROM F AI L“““
WARM BOOT
STARTUP COMPLETE
Te s t Fa il e d Action (If Failed)
If a fault is detected an error message will be displayed and the system will halt. When the warm boot completes
the display returns to the top level status message.
CONSOLES WITHOUT DISPLAY
Once the system is setup, every time power to the console is switched Off and On, the software will run a selfdiagnostic warm boot program. Wait 30 seconds and the system should return to normal operation with previous
setups intact.
21
Page 27
RS-232 Communications
The RS-232 port, provided with consoles having form numbers 8469X0-260, -230, and -460, connects to a userselected serial printer, modem or terminal.
RS-232 Peripheral Equipment Requirements
Any peripheral equipment connected to an RS-232 serial port must meet the following criteria:
1. Peripheral equipment must be UL listed.
2. The equipment must have an EIA standard RS-232C or RS-232D communications protocol.
3. The equipment must NOT be installed over or in a hazardous location.
RS-232 Connections
TO A DEVICE LESS THAN 50 FEET FROM THE CONSOLE
Veeder-Root recommends that you use a null-modem cable no longer than 50 feet for direct connections between
the console and a remote device. Cable runs longer than 50 feet can result in data errors, component damage, or
both.
TO A DEVICE MORE THAN 50 FEET FROM THE CONSOLE
If cable runs longer than 50 feet are needed, two short-haul modems should be used, one at the console and one
at the remote device. We recommend an asynchronous short-haul modem, Black Box model ME800A, or
equivalent at the console and at the remote device. For more information, you can contact Black Box by phone:
724-746-5500, Fax: 724-746-0746, or web: http://www.blackbox.com
Figure 18 illustrates how to connect two short-haul modems between the console RS-232 Interface Module’s or
Auxiliary RS-232 Interface Module’s DB-25 connector and the remote device.
22
Page 28
RS-232 Co mmunicationsSurge P rotection for Communication Devices
Computer
or
consoles\tls50\shmodm.eps
DCE
S1
DTE
DB-9
Connector
To
Available
Port
DB-25
Connector
Color 1
Gnd
TX-
Color 2
TX +
RX-
Color 1
Color 2
RX+
DB-25 Connector
EN
DIS
RTS/DTR
CONTROL
Console
ALL FUNCTIONS NORMAL
T1 VOL: 9889 GAL
TLS-50
DB-9 Connector
2 Twisted Pairs (24 - 26 AWG)
DB-25 Connect
Color 1
Color 2
Color 1
Color 2
DCE
S1
S2
DTE
Gnd
TX-
TX +
RX-
RX+
EN
DIS
RTS/DTR
CONTROL
S2
TDRD
Flash red & green
Black Box Model: ME800A
Loopback
Normal
= Required selection
TD
Flash red & green
RD
Black Box Model: ME800A
Loopback
Normal
Figure 18. Console Connected to a Remote Device via Short-Haul Modem
Surge Protection for Communication Devices
In locations that are subject to high levels of noise and power surges, the use of a surge protector is
recommended. The following models are available from B&B Electronics by phone: 1-815- 433-5100, or web:
http://www.bb-elec.com:
•
Telephone Line Surge Protector, model TLSP
•
RS-232 Surge Protector, model 232DSP
23
Page 29
RS-232 Co mmunicationsSystem Serial Securit y
s
System Serial Security
To protect against unauthorized access to system operation DIP switch 1 of SW1 on the Power Supply board lets
you enter a 6-digit security code before the system will respond to a serial command (only applies to consoles
having form numbers 8469X0-260, 230, & -460). If enabled, the default serial security code is 000000. The
security code itself can be changed with a serial command (see “Function Code: 504” on page 31). Consoles are
shipped from the factory with this switch in the open (disabled) position.
See Figure 15 on page 17 for location of this switch. Figure 19 shows the switch in the closed position, enabling
the security feature.
Switch 2 and Switch 3 are not used and can be in any position.
COMM
1234
Sw 1 - Security
OPEN
consoles\tls50\50switch.ep
Figure 19. Console Dip Sw itch Setting s
RS-232 Serial Communication Setup
Table 2 shows the available RS-232 setup options and defaults by console form number.
T able 2.- RS-232 Setup Options and Defaul ts
SetupOptionsConsole Form NumbersDefault
Interface mode typePrinter, modem, or serial8469X0-260Printer
8469X0-230, -460Serial
Baud rate300, 600, 1200, 2400, 4800, or 96008469X0-260, -4609600
8469X0-2302400
ParityNone, odd, or Even8469X0-260, -460None
8469X0-230Even
Data length8 or 78469X0-260, -4608
8469X0-2307
Stop bits1 or 28469X0-230, -260, -4601
24
Page 30
RS-232 Co mmunicationsDB-9 Connector Pin-Outs
Console
or
c
T able 2.- RS-232 Setup Options and Defaul ts
SetupOptionsConsole Form NumbersDefault
HandshakingNone, XON/XOFF, or hardware8469X0-260XON/XOFF
8469X0-230, -460None
Printer page ejectYes or no8469X0-260No
8469X0-230, -460N/A
Answer on options0 to 98469X0-260No
8469X0-230, -460N/A
Serial languageEnglish, French, Spanish, or Port uguese8469X0-230, -260, -460English
DB-9 Connector Pin-Outs
Communicating with the Console from a remote computer is done through a RS-232 serial port (DB-9 connector)
on the bottom of the console.
Pin layout to connect the Console’s Serial Interface DB-9 connector to a 25-pin computer terminal connector are
shown in Figure 20. These connections are standard for “AT” style modem cables.
6.NN - Number of eight character Data Fields to follow (Hex)
7.FFFFFFFF - Probe Data (ASCII Hex IEEE float)
8.&& - Data Termination Flag
9.CCCC - Message Checksum
57
Page 63
Troubleshooting
Print key will be blank on consoles without Serial Package option
consoles\tls50\dkey.eps
This section contains information to help diagnose system problems.
•
Probe troubleshooting
•
CPU/Power board replacement
•
System specifications
•
System compatible probes
Dual-Function Front Panel Keys (consoles w/Keypads Only)
Two of the six front panel keys have dual functions [Figure 21].
1
Back
1
Dual function keys
2
1
SelectEnter
SilentPrint
2
Tank
Figure 21. D ual-Functi on Keys
Pressing the Enter key down for an extended period (longer than 2 seconds) will change the system language to
the next available language queued in software. Repeat this procedure until the desired language is displayed.
Pressing the Back key down for at least 2 seconds will change the system setup units Repeat this procedure until
the desired units are displayed.
A short beep from the console beeper will inform the operator that these keys have been held in long enough to
select the alternate function. When the operator is ready to return to the originally programmed language and/or
units, switch the console power off and then back on. The system will perform a warm boot and return to the
originally programmed language and units.
Probe Troubleshooting
CONSOLES W/O DISPLAY
Probe troubleshooting can be performed using the appropriate RS-232 serial commands (see appropriate section
in this manual).
CONSOLES W/DISPLAY
The Diagnostic Menu is accessed from the front panel of the console. From the Top Level menu press the Select
key until the display reads DIAGNOSTICS, then follow the key presses shown in Figure 22. Figure 23 contains an
general explanation of the diagnostic displays.
58
Page 64
TroubleshootingProbe Troubleshooting
DIAGNOSTICS
PRESS <ENTER>
SOFTWARE VERSION
XXXXXX-XXX Y
T1: PROBE TYPE:
GLB01
T1: SERIAL NUMBER
XXXXX
T1: PROBE ID
0XD011
T1: PROBE LENGTH
96.0
T1: GRADIENT
0180.0000
Prints out the Diagnostic Report if your console has the Serial Package option,
you have made the correct communication setup selections, and you have
a serial printer connected.
T2: PROBE TYPE:
GLB01
T1: SERIAL NUMBER
XXXXXX
T2: COUNTS
18 XXXXX
T6: PROBE TYPE:
GLB01
T6: SERIAL NUMBER
XXXXXX
T6: COUNTS
18 XXXXX
T1: NUMBER SAMPLES
20
T1: SAMPLES READ
XXXXXX
T1: SAMPLES USED
XXXXXX
T1: COUNTS
00 XXXXX 01 XXXXX
T1: COUNTS
16 XXXXX 17 XXXXX
T1: COUNTS
18 XXXXX
consoles\tls50\50diag.eps
Figure 22. Diagnostic Menu - Overview
59
Page 65
TroubleshootingProbe Troubleshooting
t
DIAGNOSTICS
PRESS <ENTER>
SOFTWARE VERSION
XXXXXX-XXX Y
T1: PROBE TYPE:
GLB01
T1: SERIAL NUMBER
XXXXX
T1: PROBE ID
0XD011
T1: PROBE LENGTH
XXX
T1: GRADIENT
XXX.XXXX
T1: NUMBER SAMPLES
20
T1: SAMPLES READ
XXXXXX
Console's current software version: XXXXXX-XXX
Options: Y= 1 Alarm package, Y= 2 Serial and Alarm Package).
Probe's serial number.
Probe's manufacturing code.
Probe calibration factor used to calculate water height and product height.
Number of probe measurement sets made before posting water height,
product volume, and product temperature. (A measurement set consists of
probe counts 00 - 18 discussed below.)
Historical total of probe measurements read.
T1: SAMPLES USED
XXXXXX
T1: COUNTS
00 XXXXX 01 XXXXX
T1: COUNTS
16 XXXXX 17 XXXXX
T1: COUNTS
18 XXXXX
Historical total of probe measurements used.
Probe counts used to calculate water height, product volume, and
product temperature. Counts 00 - 18 constitute one probe measuremen
set.
consoles\tls50\50dgex.eps
Figure 23. Diagnostic Menu - Explanation
60
Page 66
TroubleshootingReplacing the CPU Board
Probe Diagnostic Report
The Diagnostic Report example below is a printout of probe information, for all tanks. The probe functions are
discussed in Figure 23.
The CPU board in the console must be replaced when:
•
A system self-test failure occurs during a warm or cold boot, or
•
The display (on certain models) contains garbled messages and/or the voltage between the GND and 8V test
points on the back of the CPU board is within 7 - 9 Vdc; or,
•
The voltage between the GND and 5V test points [Figure 24] on the back of the CPU board is not within 4.75 -
5.25 Vdc.
OFF
1. Turn Off power to the system.
61
Page 67
TroubleshootingReplacing the CPU Board
C
S
ps
HANDLING THIS BOARD!
5V
able to Power
upply Board
GND 8V
LED1
J1
These voltage test points are on the back of
the CPU board (directly behind this upper left
corner)
+
PROM chip
C5
STATIC SENSITIVE - WEAR
GROUNDED ANIT-STATIC
WRIST STRAP BEFORE
U5
Figure 24. CPU Board Voltage Test Points (Keypad/Display version shown)
Y2
TLS-50 CPU
consoles\tls50\cpu.e
2. Attach the anti-static strap to your wrist and to a good ground.
3. Disconnect the CPU cable from the Power Supply board.
4. The CPU board snaps securely into place in the door of the console without the use of screws. There are two
tabs on the top of the board that fit into two slots in the top edge of the door. The bottom of the CPU board
snaps in place between two pairs of detents protruding from the bottom edge of the door. The CPU board is
removed by inserting a straight-slot screwdriver into one of the two indents on the bottom of the board and
then gently prying against the door until the board clears the upper detents, then rotating the board up slightly
and toward you to clear the top tabs from the slots in the door.
5. Replace the CPU board reversing the above steps.
6. Follow the cold boot instructions beginning on page 20.
The PROM chip is replaced when a software upgrade is installed. This procedure requires that you perform a
RAM clear.
1. If possible, record the current setup information. Turn off power to the system.
OFF
2. Open the front door of the console. The CPU board is installed in the door.
3. Attach anti-static strap to your wrist and to a good ground.
4. Disconnect the CPU board cable from the Power Supply board. Remove the CPU board following the
instructions in “Replacing the CPU Board” on page 61.
5. Locate the PROM chip on the board [Figure 24].
6. Remove the PROM chip following instructions in Figure 25.
7. Replace the PROM chip following instructions in Figure 26.
8. Replace the CPU board in the front door of the TLS-50. Connect the CPU board cable to J1 on the Power
Supply board.
9. Follow the cold boot instructions for your console type beginning on page 20.
These voltage test points are on the back of
the CPU board (directly behind this upper left
corner))
J1
PROM chip
socket
consoles\tls50\50cpurm.eps
+
C5
U5
Y2
1) Orient PROM so that the small indented dot on
top of the chip is on the same side with the small
triangle embossed in the socket's base; or,
2) If the chip is covered with a label you can also orient
STATIC SENSITIVE - WEAR
GROUNDED ANIT-STATIC
WRIST STRAP BEFORE
HANDLING THIS BOARD!
the chip correctly if you insert the chip in the socket
with its angled corner in the same angled corner of the
socket.
3) Carefully align the chip's pins with the socket's pins.
(If you have the pins aligned correctly, the chip will seem to
drop into the socket.) Then push down firmly and evenly
on the chip until it snaps into the socket.
4) Check to see that all pins are in place and none are bent.
Figure 26. Replacing PROM Chip (Keypad/Display version shown)
65
Page 71
TroubleshootingReplacing the Power Supply Board
Replacing the Power Supply Board
The Power Supply board must be replaced when:
•
Probe data is not being processed, or
•
The voltage between the GND and 8V test points [Figure 24] on the back of the CPU board is less than 7 Vdc.
OFF
1. Turn Off power to the system.
2. Disconnect the CPU cable from the Power Supply board.
3. Tag and disconnect probe, power, and overfill alarm relay wiring to the Power Supply board.
4. The Power Supply board is secured by two T-15 Torx screws in the top of the board. For consoles with the com
option (see Table 1 on page 1), the two screw locks which go through the bottom of the console into the DB-9
connector must also be removed before you can lift out the board.
After removing the Torx screws (and screw locks), slowly lift up on the board until the lower tabs on the board
clear the slots in the bottom of the console, then continue to lift the board out.
5. Replace the board by reversing the above steps.
6. Turn on power to the system. The system will perform a warm boot procedure [page 21] and the display will
return to the top level status screen. You do not have to reprogram the console after replacing the Power
Supply board.
66
Page 72
Console Specifications
PHYSICAL SPECIFICATIONS
•
Width (door closed): 7.6”, open 9.6”) Depth (door closed 2.6”, open 9”))
•
Height: 6.7” Weight: 3.5 lbs.
•
Two PC boards in console: CPU (in door) and Power Supply (in unit)
ENVIRONMENTAL SPECIFICATIONS
•
Console storage and operation: indoor, climate controlled.
ELECTRICAL SPECIFICATIONS
•
Console operating voltage: 120/240 Vac, 2 A max.
•
The Power Supply board fuses F1 and F2 are NOT field replaceable The rating for both fuses is 2 A, Type T
[Time Lag].
SIGNAL INPUT SPECIFICATIONS
•
Up to 6 probes monitored with TLS-50, or 3 probes monitored with TLS-50C
•
Probe data: 0.15 A at 12 volts
SIGNAL OUTPUT SPECIFICATIONS
•
One dry contact Relay Output: 120 Vac, 2 A
FRONT PANEL USER INTERFACE (CONSOLES W/DISPLAY)
•
Two line, graphic LCD display
•
Visible annunciator (bi-color LED)
Green - all functions normal
Flashing red - alarm active
•
Push keys
Select
Enter
Print (optional)
Back
Silence
Tan k
•
Audible annunciator: internal beeper
67
Page 73
Console SpecificationsProbe Circuit Codes
Probe Circuit Codes
Table 2 lists the probes that can be used with various TLS-50 Console Form Nos. Probe Form Nos. 8990 are only
compatible with Console Form Nos. 846910-XXX.
All 8990 probes are Nepsi appr oved. The standard configuration for an 8990 probe is stainless steel with a 5foot (1. 524 m ) cable.
Probe
TypeProbe Description
Water
Float Type
Temperature
Measurement
No. of
Floats
68
Page 74
Appendix A: TLS-50 and TLS-50C Safety Instructions
1. Refer to Veeder-Root Descriptive System Document 331940-003 for system installation requirements. This drawing
can be found on the Veeder-Root Tech Docs CD-ROM shipped with your console.
2. Refer to the site preparation procedures in this manual for general instructions on safe installation, use, and
replacement.
3. The TLS-50 and TLS-50C systems do not require periodic maintenance or calibration.
4. The TLS-50 and TLS-50C systems are serviceable. If a failure occurs, the unit should be repaired in accordance with
the requirements in the Troubleshooting section of this manual. Note: There are no replaceable components within
the encapsulated protective circuits. If a protective circuit fails, it must be replaced in its entirety.
A-1
Page 75
Page 76
For technical support, sales or
other assistance, please visit:
www.veeder.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.