TCI-W-U Universal Controller
OVERVIEW
Features
Universal PID and/or binary control for any analog input/output
signal and range
Multiple auxiliary functions: heat-cool auto changeover, automatic
enable, setpoint compensation
Averaging, min. and max. functions
Cascading of control loops (-W22 type)
Alarm monitoring of low and high limits on all inputs
Programmable reaction in case of alarm
Feedback function for inputs and set points
Functions for dehumidifying, set point shift, cascade control
Password protected programmable user and control parameters
TCI-W22-U also includes
Power Cap protected real-time clock with 48hr power backup
7-day programmable schedules, with options including change of
setpoints and direct position of manual outputs
Blue backlight
Fan coil units
Heat exchangers
Zoning
VAV
Air handlers
Fan, Pump control
Humidifiers
Dehumidifiers
Ventilation
Radiant heating
Radiant cooling
Pressurization
Housing Blank = square housing
In/Outputs: See table below
Control loops: 1 = 1 control loop, 2 = 2 control loops
Mounting: W = Wall mounted
TCI-W-U Universal Controller
Applications
General
TCI-W11-U: 1 independent control loop, 1 internal temperature sensor, 1 universal input (analog/binary/temp), 2
binary outputs, 1 analog output
TCI-W22-U: 2 independent control loops, 1 internal temperature sensor, 2 universal inputs, 2 binary outputs, 1
analog output.
Internal temperature sensor standard. Add replaceable humidity element as required: AES3-HT-A2 (2%), AES3-
HT-A3 (3%), or AES3-HT-A5 (5%)
Flexible application configuration is made with a parameter-setting routine using the standard operation terminal.
Name
Ordering
Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy:SDB-Tn10-20 (duct), SRA-Tn10
(room), SDB-Tn10-20 + AMI-S10 as immersion sensor.
Actuators: Choose modulating actuators with an input signal type of 0-10 V DC or 4-20 mA (Min. and max.signal
limitations may be set with parameters.3-pointpoint actuators with constant running time are recommended.
Binary auxiliary devices (e.g. pumps, fans, on/off valves, humidifiers, etc):Do not directly connect devices that exceed
specified limits in technical specifications – observe startup current on inductive loads.
Doc: 70-07-0140, V1.2, Date: 20170123 © Vector Controls GmbH, Switzerland Page 1
Subject to alteration
TCI-W-U Universal Controller
OPERATION
24 VAC ±10%, 50/60 Hz,Class 2, 2.0 A, 48 VA max.
24 VDC ±10%
Terminal Connectors
0.34…2.5 mm2 wire (AWG 24…12)
Universal Input
Input Signal
Resolution
Impedance
Setting for Voltage or Current
0–10 V or 0–20 mA
9.76 mV or 0.019 mA (10 bit)
Voltage: 98kΩ Current: 240Ω
Input configured to remote temperature (RT) or digital input (DI)
NTC (Sxx-Tn10 sensor): -40…140 °C (-40…284 °F)
-40…0 °C (-40…32 °F): 0.5 K
0…50 °C (32…122 °F): 0.2 K
50…100 °C (122…212 °F): 0.5 K
> 100 °C (> 212 °F): 1 K
Humidity Sensor AES3-HT-Ax:
Range
Measuring Accuracy
Hysteresis
Repeatability
Stability
Capacity sensor
0…100 % rH
See Figure to the right
1%
0.1%
< 0.5% / year
Analog Output
Output Signal
Resolution
Output Load
DC 0–10 V / 0–20 mA
9.76 mV / 0.019 mA
Voltage: ≥1kΩ Current: ≤250Ω
Relays Outputs
Type of disconnection
AC Voltage
DC Voltage
Micro-interruption
0…48 VAC, 2(1.2)A max. (Observe local regulation)
0…30 VDC, 2A max.
Insulation strength
between relays contacts and system
electronics:
between neighboring contacts:
2000V AC to EN 60 730-1
1250V AC to EN 60 730-1
Operation
Climatic Conditions
Temperature
Humidity
To IEC 721-3-3
class 3 K5
0…50 °C (32…122 °F)
<95 % r.H. non-condensing
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25…70 °C (-13…158 °F)
<95 % r.H. non-condensing
class 2M2
conforms to
EMC Standard 89/336/EEC
EMEI Standard 73/23/EEC
EN 61 000-6-1/ EN 61 000-6-3
Product standards
Automatic electrical controls for household
and similar use
Special requirement on temperature
dependent controls
EN 60 730 –1
EN 60 730 – 2 – 9
Degree of Protection
Material: Cover, back part
Mounting Plate
Fire proof ABS plastic (UL94 class V-0)
Galvanized Steel
Front part: 112 x 73 x 15 mm (4.4” x 2.9” x 0.6”)
Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)
Weight (including package)
TCI-W11-U = 255g (9.0 oz), TCI-W22-U = 265g (9.3 oz)
Max rH tolerance at 25°C (77°F)
Technical specifications
Warning! This device is intended to be used for comfort applications. Where a device failure endangers human life and/or
property, it is the responsibility of the owner, designer and installer to add additional safety devices to prevent or detect a
system failure caused by such a device failure. The manufacturer of this device cannot be held liable for any damage caused
by such a failure.
Failure to follow specifications and local regulations may endanger life, cause equipment damage and void warranty.
Doc: 70-07-0140, V1.2, Date: 20170123 © Vector Controls GmbH, Switzerland Page 2
Subject to alteration
TCI-W-U Universal Controller
OPERATION
Warning:
Live Electrical
Components!
During installation,
testing, servicing and
troubleshooting of
Vector Controls
products, it may be
necessary to work
with live electrical
components. Have a
qualified licensed
electrician or other
individual who has
been properly trained
in handling live
electrical components
perform these tasks.
Failure to follow all
electrical safety
precautions when
exposed to live
electrical components
could result in death
or serious injury.
Installation
Install the controller on an easy accessible interior
wall, approx. 1.5 m above the floor in an area of
average temperature.
Avoid direct sunlight or other heat sources, e.g. the
area above radiators and heat emitting equipment.
Avoid locations behind doors, outside walls and below
or above air discharge grills and diffusers.
Location of mounting is less critical if external
temperature sensors are used.
Ensure adequate air circulation to dissipate heat
generated during operation.
Observe local regulations.
Do not mount in a wet or condensation prone
environments.
Dimensions, mm (inch)
Connection
Terminal Description
G0 Power supply: 0V, -24VDC; common for power supply, analog in- and outputs
G Power supply: 24VAC, +24VDC
Q.. Binary outputs: Potential free relays contacts (see technical specification)
Yb1,b2 Binary output common
X
Universal input: NTC 10kΩ @ 25°C (77°F), 0…10 V or 0…20 mA(selectable by jumper)
U1, u2
Ym1 Analog output: 0…10 V or 0…20 mA
XT1 Internal temperature input
XH1 Internal humidity input if AES3-HT is inserted
Use copper, twisted pair, conductors only. The operating voltage must comply with the requirements for safety extra-low
voltage (SELV) as per EN 60 730. Use safety insulating transformers class II with double insulation as per EN 60 742; they
must be designed for 100% ON-time. When using several transformers in one system, the connection terminal 1 must be
galvanic connected. TCI is designed for operation of AC 24 V safety extra-low voltage and is short-circuit-proof. Supplying
Doc: 70-07-0140, V1.2, Date: 20170123 © Vector Controls GmbH, Switzerland Page 3
Subject to alteration
*
TCI-W-U Universal Controller
OPERATION
Comfort (occupied): All control functions operating per set points
Economy (unoccupied): Set points shifted according to 1L07, 2L07
Energy Hold Off: Outputs are off, inputs monitored for alarms
Left (POWER)
Press < 2 sec.: Toggle STANDBYCOMFORT mode or switch from OFF
to ON
Press > 2 sec.: Turn unit OFF. Text
OFF displayed with current time
(deluxe) temperature (standard)
(Parameter setting: ENTER to
select menu option, accept
parameter change)
Up
Increment SET POINT
(Parameter setting:
SCROLL menu options
and parameters)
Down
Decrement SET POINT
(Parameter setting: SCROLL menu
options and parameters)
Loop indication
Standard display (no button pressed
for 30 sec.): Not visible.
Loop display: Bar at 1 = Loop 1, Bar at
2 = Loop 2
Mode
Display of operation
mode
Large Digits
Display of input or parameter
value.
Indicators
Standard display:
Active digital
output (at 1, 2)
Loop display:
Active digital stages
(at 8,9,10)
Vertical Bar
(scrolls up/down, 10% resolution)
Small Digits
Display of setpoint, clock or
parameter number.
Right (OPTION)
Press < 2 sec.: Select Control Loop
Press > 2 sec.: Enter set-up
CLOCK, SCHEDULES, H/C
(Parameter setting: ENTER to
select menu option, accept
parameter change)
voltages above AC 24 V to low voltage connections may damage the controller or other devices. Connection to voltages
exceeding 42 V endangers personnel safety.
Display and Operation
Standard display (Parameters UP08, UP09, UP10)
Active whenno key has been pressed for 30 seconds.
Contents may be chosen with parameters.
Loop display
Active when changing set points. Large digits show input value. Small digits show set point. Vertical bars show analog
output value. Arrows in position 1, 2 and/or 3 show active binary (digital) output stages
Override of secondary set point in cascade control
If cascade control is active, withvariable air volume (VAV) for example,the user can override the primary loop and
manually select the set point of the secondary loop-the loop is now changed to constant air volume (CAV). Typically for
tuning the VAV system.This feature may be disabled with UP02.
While the secondary loop is displayed change the set point with UP/DOWN. Override Cascade symbol appears.
Press OPTIONto move back to the temperature loop and cancel cascade override.
Doc: 70-07-0140, V1.2, Date: 20170123 © Vector Controls GmbH, Switzerland Page 4
Subject to alteration
TCI-W-U Universal Controller
OPERATION
For TCI-W11-U: Press OPTION > 2 sec. SEL and H-C is displayed.
For TCI-W22-U: Press OPTION > 2 sec. SEL and current time is displayed.
Press UP key twice. SEL and H-C is displayed.
Press OPTION again to toggle H or C.
For TCI-W11-U: Press OPTION > 2 sec. SEL and H-C is displayed.
Press UP key once: UI1 and its value are displayed
For TCI-W22-U: Press OPTION > 2 sec. SEL and current time is shown.
Press UP key three times. UI1 and value are displayed.
Press UP key again to step through the next active input
Note: disabled inputs will not be shown.
Power Failure
All parameters and set points are memorized and do not need to be re-entered.
Upon return of power: SetParameter UP05to keep the unit off, switch on, or operation mode before power failure.
Clock and time schedule settings retained for 48 hours (after powered for at least 10 hours).
Error messages
Err1: An assigned input is not enabled or missing. All control loops, functions and outputs tied to this input will be disabled.
Err3: A function refers to a disabled input. Disable the function or enable the input.
Err4: Internal failure. Product must be replaced.
Verify input connections, jumper settings and parameter settings for the input involved.
Manual heat – cool change
To manually change heating or cooling mode press the OPTION key for more than 2 seconds. Access to manual heat – cool
change may be disabled with parameter UP03.
Display input values
Doc: 70-07-0140, V1.2, Date: 20170123 © Vector Controls GmbH, Switzerland Page 5
Subject to alteration
TCI-W-U Universal Controller
OPERATION
Press OPTION > 2 sec. SEL and current time displayed
Press OPTION< 2 sec. to change time,
Minutes blink: UP/DOWN to change, OPTION to save minutes,
Hours blink: UP/DOWN to change, OPTION to save hour,
Press OPTION to save time,
DAY1 blinks: UP/DOWN to change, OPTION to save day
Press OPTION > 2 sec. SEL and current time displayed
Press UP:
SEL and PRO displayed, clock symbol blinks
Press OPTION:
Time schedule status displayed OFF or ON:
Press OPTION
OFF/ ON blinks, UP/DOWN to change, OPTION to save
Press UP while PRO-ON displayed:
Large digits display Pr01, small digits display 00:00
Press OPTION:00:00 blinks
Press UP/DOWN to select Pr01switching time from 00:00–23:45
Press OPTION to save switching time (bar appears indicating step 1 complete):
DAY 1 blinks
While Pr01 is displayed and DAY1 is blinking:
Press UP: Activate Pr01 switching time for DAY1 (triangle appears on 1),
Press DOWN:
Deactivate Pr01 switching time for DAY1(triangle disappears)
Press OPTION to save Pr01 DAY1 (2nd bar indicates step 2 complete):
Repeat for DAY2 – DAY7
Pr01
DAY1
1 2 3 4 5 6 7
After Pro1, DAY1–DAY7 is completed (Pro1 switching time activate or deactivate on desired days), press
OPTION again to come to desired action for Pro1. The following options appear in order:
No = switching time not active
OP = operation mode (select ON, OFF, COMFORT, ECONOMY)
L1 = set point of loop 1 (select set point)
L2 = set point of loop 2 (select set point)
d1 = ON/OFF status of do1 (output must be in manual mode)
d2 = ON/OFFstatus of do2 (output must be in manual mode)
A1 = set point (0-100%) of ao1 (output must be in manual mode)
After repeatedly pressing OPTION through DAY7:
First available action No appears, blinking:
Press UP/DOWN to scroll through the 8 possible actions (3nd bar indicates step 3 complete)
Available actions blink as you scroll through them, Press OPTION to select one:
Characteristics of action (e.g. 0–100% for A1) appear (4th bar indicates step 4 complete)
Press UP/DOWN to select, OPTION to complete
Clock operation
TCI-W22-Ucontains a quartz clock with battery back-up (not available in TCI-W11-U). Up to 8 mode changes based on time
and day of the week may be programmed. Also position an output or select a set point directly with a time schedule. A
blinking clock indicates that the time has not been setor thatthe unit has beenwithout power for longer than 48 hours. The
time needs to be set to allow time schedules to operate.
Clock setup
Enable/disable time schedules
Creating time schedules
Step 1: Select a switching time (Up to 8, Pr01–Pr08)
Step 2: Apply selected switching time (Pr01) to DAY1 (Mon) – DAY 7 (Sun)
Step 3: Select action for switching time (Pr01+Days)
Step 4: Complete switching event (e.g. Pro1 = 08:00, DAY 1, Comfort mode)
Doc: 70-07-0140, V1.2, Date: 20170123 © Vector Controls GmbH, Switzerland Page 6
Subject to alteration