The TCX2 is a programmable electronic universal controller with communication capabilities. Each control loop may use 2 PI
sequences and 6 binary stages. The TCX2 comes with a built in RS485 communication interface that allows peer to peer
communication with an operation terminal e.g. OPU2-(2TH)-VC or a PC.
Communication plug-ins allow for integration of the controller into a network. These modules are described in their own
manual. Currently available are plug ins for BACnet and MODBUS.
Flexible application configuration is made with a parameter-setting routine using the standard operation terminal.
Complete parameter sets may be copied by use of an accessory called AEC-PM1 or exchanged with a PC using an RS485-USB
This device is for use as operating controls. It is not a safety device! Where a device failure endangers human life and/or property, it is the
responsibility of the client, installer and system designer to add additional safety devices to prevent a system failure caused by such a device failure.
Ignoring specifications and local regulations may cause equipment damage and endangers life and property. Tampering with the device and
misapplication will void warranty.
Jumpers are located on the backside of the controller
Installation
See installation sheet no. 70-000599 (www.vectorcontrols.com).
Selection of actuators and sensors
Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy: SDB-Tn10-20 (duct), SRA-Tn10 (room),
SDB-Tn10-20 + AMI-S10 as immersion sensor.
Actuators: Choose modulating actuators with an input signal type of 0-10 V DC or 4-20 mA (Min. and max. signal limitations
may be set with parameters. 3-point point actuators with constant running time are recommended.
Binary auxiliary devices (e.g. pumps, fans, on/off valves, humidifiers, etc.): Do not directly connect devices that exceed
specified limits in technical specifications – observe startup current on inductive loads.
Electrical connections
Use only twisted pair copper conductors for input connections. The operating voltage must comply with the requirements for
safety extra-low voltage (SELV) as per EN 60 730.
Use safety insulating transformers with double insulation. They must be designed for 100% ON-time. When using several
transformers in one system the connection terminal 1 must be galvanically connected. The TCX2 is designed for operation by AC
24 V, max. 10 Amp, safety extra-low voltage that is short-circuit-proof. Supplying voltages above AC 24 V may damage or
destroy the controller or any other connected devices.
Additionally, connections to voltages exceeding 42 V endanger personnel safety. Observe limits mentioned in the technical
specifications. Local regulations must be observed at all times.
Occupied: (Comfort) All control functions operating per set points.
Heating (reverse) active
Unoccupied: (Standby, Economy) If enabled, alternative setpoints are
used with the intention to reduce energy consumption.
Cooling (direct) active
OFF
OFF: (Energy Hold Off, EHO) Normal control functions are inactive,
inputs are monitored for alarms.
Schedule set
Manual override,
delay on enable function
Fan active
Left (ESC)
parameter setting)
Center (POWER)
UP
and parameters)
DOWN
Loop indication
Mode
Display of operation
mode
Large Digits
Display of input or
parameter value.
Indicators
Idle display: Active
digital output (at 1
to 6)
Parameter setting:
8,9,10 indicate
changing mode.
Vertical Bar
resolution)
Small Digits
Right (OPTION)
Display and Operation
Idle display (no button pressed for 30
sec.): Not visible.
Loop display: Bar at 1 = Loop 1, Bar at
2 = Loop 2, etc
Display of
setpoint, clock
or parameter
number.
Display of
output value.
(Scrolls
up/down, 10%
Increase SET POINT
(Parameter setting:
SCROLL menu options
Select Control Loop
(Parameter setting: ESCAPE
menu option, discard
Press < 2 sec.: Toggle OccupiedUnoccupied mode or switch from
OFF to ON
Press > 2 sec.: Turn unit OFF.
(Parameter setting: ENTER to
select menu option, accept
parameter change)
Press < 2 sec.: Select Control Loop
Press > 2 sec.: Enter set-up
CLOCK, SCHEDULES, H/C
(Parameter setting: ENTER to
select menu option, accept
parameter change)
Decrease SET POINT
(Parameter setting: SCROLL menu
options and parameters)
Idle display
The idle display is activated when no key has been pressed for 30 seconds.
The contents of the idle display are selectable through parameters UP08 to UP14.
Setting UP08 to OFF will disable idle display. Last active control loop or manual output will remain displayed.
Display of control loop
Active when changing set points. Large digits show input value. Small digits show set point. Horizontal bars top left show which
loop is being displayed.
Override of secondary set point in cascade control
If cascade control is active (with VAV for example) the user can override the primary loop and manually select the set point of the
secondary loop (the loop is then changed to constant air volume mode). This function is helpful for tuning the VAV system. This
feature may be disabled by setting UP02 to OFF.
While the secondary loop is displayed change the set point with UP/DOWN. The hand symbol appears.
Change setpoint again to cancel cascade override. The hand symbol disappears.
Delay on enable function
During a pending delay the hand symbol will be shown. For example the condition to activate the controller with 1FU is met, but a
startup delay is specified. The controller will remain switched off and show the hand symbol until the delay expired.
Press OPTION > 2 sec. SEL and current time displayed
Press OPTION < 2 sec. to change time,
Minutes blink: UP/DOWN to change, OPTION to save,
Hours blink: UP/DOWN to change, OPTION to save,
DAY1 blinks: UP/DOWN to change, OPTION to save weekday
Day of month blinks, UP/DOWN to change, OPTION to save
Month blinks, UP/DOWN to change, OPTION to save
Year blinks, UP/DOWN to change, OPTION to save
Press ESC or POWER to return
SEL
00:00
DAY1 (Mon)
01.01.
2014
Press OPTION > 2 sec. current time and SEL displayed
Press UP:
PRO and SEL displayed
Press OPTION:
Time schedule status displayed OFF or ON ()
Press OPTION to toggle OFF/ON
SEL
PRO
Pro
OFF/ON
Press UP while PRO-ON displayed:
Press UP or DOWN to SCROLL Pr01 through Pr12,
Press OPTION to select desired schedule (e.g. Pr01),
00:00 blinks
Press UP/DOWN to select Pr01 switching time from 00:00–23:45
Press OPTION to save switching time (bar appears indicating step 1 complete): DAY 1 blinks
08:00
Pr01
While Pr01 is displayed and DAY1 is blinking: If 365 is shown, press DOWN key. After this DAY 1 will show.
Press UP:
Activate Pr01 switching time for DAY1 (triangle appears on 1),
Press DOWN:
Deactivate Pr01 switching time for DAY1 (triangle disappears)
Press OPTION to save Pr01 DAY1 (2nd bar indicates step 2 complete):
Repeat for DAY2 – DAY7
DAY1
Pr01
1 2 3 4 5 6 7
The selection of switching time and weekdays for this time schedule is now completed.
Press POWER to come to desired action for Pro1. The following options appear in this order:
no = switching time not active
OP = operation mode (ON, OFF, OCCUPIED, UNOCCUPIED)
LP = set point
AO = Position of analog output (output must be in manual mode by parameter setting)
FAN = Fan state (output must be in manual mode by parameter setting)
do = Position binary output – digital, 3-point or PWM (output must be in manual mode by parameter
setting).
Hday/ON = Annual time schedule: Holiday starts
Hday/OFF = Annual time schedule: Holiday ends
Press UP/DOWN to scroll through the possible events(3nd bar indicates step 3 complete)
LP
Pr01
Status LED
A status LED is located on the upper left side of the controller housing. During normal operation the LED blinks briefly once every
5 seconds. It will blink every second in case there is an alarm or fault condition.
Power Failure
All parameters and set points are memorized and do not need to be re-entered.
Upon return of power: Based on UP05 the controller will start in OFF, occupied or the same mode as before.
Clock and time schedule settings are retained for 48 hours (after being powered for at least 10 hours).
Error messages
Err1: Communication error
Err2: Internal data corrupt. Replace product.
Err3: Initial power up after firmware update or internal error. Re-start product. If error reappears, replace product.
Err4: Configuration error. Parameter settings are conflicting. Verify control setup; make sure all assigned inputs are enabled
and functioning.
Err5: Parameter copy mode: Copy error – if external module is addressed, communication error with external product.
Err6: Parameter copy mode: Check sum mismatch of eeprom data. Data in external eeprom corrupt.
Err7: Lead/Lag function error. At least one assigned lead/lag module is not assigned or failed.
Clock operation
The controller contains a quartz clock with battery back-up. Up to 12 schedules based on time and day of the week may be
programmed (Pr01 through Pr12). Schedules may change controller operation mode (on, off, occupied, unoccupied), change fan
state, directly position an output, or change a loop set point. A blinking clock indicates that the time has not been set or the unit
was without power for longer than 48 hours. The time needs to be set to allow time schedules to operate. Summer / winter time
changeover may be activated using user parameters.
Clock setup
Enable/disable time schedules
Creating weekly time schedules
Step 1: Select a switching time (Up to 12, Pr01–Pr12)
Step 2: Apply selected switching time (Pr01) to DAY1 (Mon) – DAY 7 (Sun) or 365 days (Annual schedule)
Step 3: For weekly schedules: Select action for switching time (Pr01+Days)
For all non-operation mode changes, it is required to select the output or control loop in this step.
For example for setpoint LP1, LP2, etc. or for an output the number of the output that should be changed.
Press UP/DOWN to select, OPTION to complete
LP01
Pr01
Choose operation mode, setpoint or position of output
Characteristics of action (e.g. 0–100% for A1) appear (5th bar indicates step 5 complete)
Press UP/DOWN to select, OPTION to complete
25%
Pr01
Press UP while PRO-ON displayed:
Press UP or DOWN to SCROLL Pr01 through Pr12,
Press OPTION to select desired schedule (e.g. Pr01),
00:00 blinks
Press UP/DOWN to select Pr01 switching time from 00:00–23:45
Press OPTION to save switching time (bar appears indicating step 1 complete): DAY 1 blinks
08:00
Pr01
This parameter is not used for annual time schedules.
While Pr01 is displayed and DAY1 is blinking:
Press OPTION repeatedly to step through this mode or on TCX2-OP, press POWER.
Day1
Pr01
1 2 3 4 5 6 7
Press POWER to come to desired action for Pro1. The following options appear in this order:
no = switching time not active
OP = operation mode (ON, OFF, OCCUPIED, UNOCCUPIED)
LP = set point
AO = Position of analog output (output must be in manual mode by parameter setting)
FAN = Fan state (output must be in manual mode by parameter setting)
do = Position binary output – digital, 3-point or PWM (output must be in manual mode by parameter
setting).
Hday/ON = Annual time schedule: Holiday starts
Hday/OFF = Annual time schedule: Holiday ends.
Press UP/DOWN to scroll through the possible events(3nd bar indicates step 3 complete)
Press Option to complete selection of event
Hday
Pr01
Select month 1 for January and 12 for December. Month is blinking.
Press UP/DOWN to select, OPTION to complete
24.08
Pr01
Select day of month to complete event (1-31). Day is blinking.
Press UP/DOWN to select, OPTION to complete
5th bar indicates step 5 complete.
24.08
Pr01
Step 4: Select ID (For example: LP01 or FAN2)
Step 5: Complete switching event
Creating annual time schedules (only for V1.3 and later)
Annual schedules have priority over other schedules. While an annual schedule is active, the weekly schedules will be inactive.
Step 1: Select a switching time (Up to 12, Pr01–Pr12)
Step 2: Apply selected switching time (Pr01) to DAY1 (Mon) – DAY 7 (Sun)
Step 3: For annual schedules: Select start or end of holidays
Press OPTION > 2 sec. SEL and current time displayed
Press UP/DOWN
Until small digits display H-C:
Press OPTION
Currently active Heat or Cool optional with fan symbol or Auto are displayed:
Press OPTION again to toggle Heating only, cooling only, fan only in heating mode or cooling mode or auto in
the following order:
Auto: heating and cooling change automatically based on demand. This must be setup with FU3.
Heat: Heating only. The controller stays in heating mode and will not switch to cooling.
Heat & Fan: The controller is in fan only mode. The fan will activate based on heating sequence.
Cool: Cooling only. The controller stays in cooling mode and will not switch to heating.
Cool & Fan: The controller is in fan only mode. The fan will activate based on cooling sequence.
H-C
SEL
Press OPTION > 2 sec. SEL and current time displayed
Press UP/DOWN
Until small digits display SEL, Large digits show:
UI = universal inputs
AO = Analog outputs
FAN = Fan outputs
do = Binary, 3-point or PWM outputs
Press OPTION to display state of In- or Output
UI
SEL
Press UP/DOWN to step through the number of available in- or outputs
Large digits show in-output type & number, Small digits show value
UI 01
25%
While in binary output mode,
Press OPTION key to display the total number of hours the binary output has been ON.
Large digits show in-output type & number, Small digits show running time in hours.
If the running time is larger than 9999 hours, 10000 hours are shown as level on the vertical bar.
The example on the right equals 50345h running time.
(Maximum runtime is 65535h = 7.5 years)
do 01
345h
New Feature with V1.3: Heat – Cool - Fan only – Auto selection
Enable manual control in cascade and for fan speeds
ON/OFF
ON
UP 03
Enable change of heating/cooling mode
ON/OFF
ON
UP 04
Enable access to time programs:
ON/OFF
ON
UP 05
State after power failure:
0= off, 1= on, 2= state before power failure
0, 1, 2
2
UP 06
Enable unoccupied Mode: Shift the setpoint to a lower temperature in winter or higher
temperature in summer in order to save energy. Unoccupied mode may be activated through
the POWER button, or with the external input (typically for key card switches, occupancy
sensors in combination with door contacts for hotels or meeting rooms.)
ON/OFF
OFF
UP 07
Celsius or Fahrenheit: ON= Fahrenheit, OFF= Celsius
ON/OFF
OFF (Celsius)
UP 08
Show idle display while no key is pressed
ON/OFF
ON
UP 09
Select type of content for large digits (00= OFF):
0–6
1
00 = OFF
01 = Input
02 = Control loop setpoint
03 = Analog output
04 = Fan
05 = Binary output
06 = Clock
Select type of content for small digits (same options as UP09)
0–6
2
UP 12
Select content source for small digits (same options as UP10)
0–10
1
UP 13
Select type of content for vertical bar display (same options as UP09)
0–6
3
UP 14
Select content source for vertical bar (same options as UP10)
0-10
1
UP 15
OFF = Do not show heating & cooling state, ON = Display heating & cooling state
ON/OFF
ON
UP 16
OFF = Alarms display only while active, ON = Alarms display until confirmed,
ON/OFF
ON
UP 17
Clock display type (12/24): OFF= 24-hr ON= 12-hr (AM/PM)
ON/OFF
OFF(24hr)
UP 18
Reset timer for manual override in time schedule mode.
0 = Reset of override mode is not active. Time schedules overridden manually will be switched
back to scheduled mode at next switching event.
1…255 = Delay for the controller to go back to the scheduled OFF or unoccupied operation
mode if the operation mode is changed manually to occupied.
0–255 Min
60(Min)
UP 19
Constant backlight for display:
OFF = The backlight is only on when a key has been pressed
ON = The backlight is constantly on
ON/OFF
OFF
UP 20
New Feature: Do not show input value in loop display
OFF = Input value is shown
ON = Only setpoint is shown. Input value is not visible in loop display
ON/OFF
OFF
UP 21
New Feature: Enable daylight savings mode. If enabled, internal real time clock will be
advanced by one hour in summer and delayed one hour in winter
ON/OFF
OFF
UP 22
New Feature: TCX2 is in no-reply-mode for OPU2-VC communication
OFF = TCX2 is in normal mode for communication with OPU2-VC
ON = TCX2 is in no-reply-mode for communication with OPU2-VC
No-reply-mode: This mode allows connecting one operation terminal to multiple controllers.
One controller must be in normal operation mode and all the others must be set to no-replymode. The controllers set to no-reply-mode will follow each command issued by the operation
terminal. They will not send responses and their alarm conditions are not monitored by the
operation terminal.
Setting a controller with only one operation terminal to no-reply-mode will result in
communication error on the operation terminal. In this case parameter UP22 can still be
changed to 0 through the operation terminal.
ON/OFF
OFF
UP 23
New Feature: Wink function: the LED on top lights up constantly if ON
OFF = LED has normal function ON = LED is constantly active
UP 24
New Feature: Summer / winter mode. Used for control loops, to select the corresponding
setpoint limits. Set in xL28
OFF = Summer mode (cooling), ON = Winter mode (heating)
ON/OFF
OFF
Module
Description
PW
UP
User and display parameters
009
LP
Control loops Lp1 to Lp4
241
UI
Input configuration: 1U to 8U,
AL
Alarm configuration: 1AL to 8AL
FU
Special functions Fu1 to Fu5
AO
Analog output configuration, AO1 to AO3
FAN
Fan output configuration FAN1 to FAN2
DO
Binary output configuration, do1 to do6
Co
Communication setup (refer to separate communication brochure)
COPY
copy mode to copy full parameter sets between run, default and external memory
with up to 4 saving locations (AEC-PM1)
Setting parameters to configure the controller
TCX2 is an intelligent controller with the flexibility to fit a wide range of applications. The control operation is defined by
parameters set using the standard operation terminal. There are two levels:
1. User/display parameters (password 0009)
2. Control parameters (password 0241)
Recommended set-up procedure:
1. Set jumpers on the back of the controller for inputs and outputs
2. Connect power supply and inputs
3. Make sure Celsius – Fahrenheit settings are correct (UP07)
4. Program input parameters
5. Program control parameters
6. Program output parameters
7. Program auxiliary functions and user settings
8. Test function of unit
9. Switch off power
10. Connect outputs
11. Reconnect power
12. Test control loop
Parameters are grouped according to modules:
How to change parameters
1. Press UP/DOWN buttons simultaneously for three seconds. The display will show firmware version and revision number.
Press the OPTION button to start login.
2. CODE is shown in small display. Select 241 or the number provided by your supplier using the UP or DOWN button. These
are the default access numbers, your supplier may have changed those numbers or blocked access to the parameters
completely. Parameters should only be changed by authorized personnel.
3. Press OPTION after selecting the correct code. The user/display parameters are displayed immediately.
4. Once logged in with 241 control modules are displayed (UI, AL, LP, AO, FAN, DO, CO etc.) – select with UP/DOWN and open
with OPTION. Then select the ID with UP/DOWN keys: 1U, 2U, 3U etc., open with OPTION. As soon as the module is open its
parameters are displayed.
5. Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. Three arrows are
displayed to indicate that the parameter may be modified. Use UP/DOWN buttons to adjust the value.
6. After you are done, press OPTION to save the new value and return to the selection level (arrows disappear when selection is
saved). Pressing left hand POWER button without pressing OPTION will discard the value and return without saving.
7. Press POWER to leave parameter selection and return to control module selection.
8. Press the POWER to leave the menu. The unit will return to normal operation, if no button is pressed for more than 5
minutes.
How to select active alarms on outputs and special functions
1. Select the parameter as described above
2. Press OPTION to start selecting alarms. AL 1 is now shown in the large digits.
3. Press UP to select the alarm 1, press DOWN to deselect the alarm 1. A selected alarm is visible by a dark triangle on the
bottom line of the LCD. The output or function will activate if the corresponding alarm is triggered.
4. Press OPTION to step to alarm 2. Repeatedly press OPTION key to step through all available alarms and select or deselect
them by pressing UP or DOWN.
5. Press POWER to leave the alarm selection routine and return to the parameter selection level.
It is possible to backup and refresh the entire parameter set to a second onboard memory (default memory) or a plug-in memory.
This simplifies substantially the programming of multiple controllers with identical parameter sets.
Removable plug-in memory AEC-PM1
The plug-in memory is an accessory that can be plugged in on the right side of the TCX2. Once connected, the power LED on the
AEC-PM1 lights up. The memory can hold up to 4 individual parameter sets. It is easy for a site engineer to update a variety of
standard installations or for an OEM to program his standard setup based on application.
Auto-load
While copying a parameter set to eeprom, the user may choose the auto-load feature. With this feature set, the parameters load
automatically when powering up the controller. It is thus possible for a non-technical person to perform a parameter update by
simply powering up the controller with the AEC-PM1 plugged in.
Procedure to copy parameter sets
1. Login to engineering parameters as described above.
2. Press UP or DOWN until COPY is selected
3. Press the OPTION key. Select copy source: These are the options:
4. Press OPTION key. Now select copy destination: These are the options:
5. Press OPTION key. Your selection is shown on the large digits: source ID to target ID. For example run time memory to
6. Press the OPTION key to conclude the selection. The Data LED on the AEC-PM1 plug-in blinks to indicate data
Exchanging parameter sets with a computer
Through a USB/RS485 converter it is possible to read and write parameter sets to a computer by the use a free program called
EasySet. The EasySet tool may be downloaded from the vectorcontrols.com website.
To exchange parameter sets, install the EasySetTM configurator program and plug in the USB/RS485 converter to your computer.
Connect the RS485 converter to the OP3 (+) and OP4 (-) terminal of the TCX2 using a twisted pair wire. If an OPU2-VC is
connected, you must first unplug it. In order to use EasySet, select the port of your USB converter first.
Parameter sets may now be read out from the TCX2 to the PC and written back to the TCX2. This makes it possible to keep a
parameter library on computer, exchange parameter sets through emails or keep a log file of all the projects completed.
0. CLR The copy destination will be erased
1. RUN Run time memory
2. DFLT Default: On board backup memory
3. EEP1 External memory folder 1 on AEC-PM1
4. EEP2 External memory folder 2 on AEC-PM1
5. EEP3 External memory folder 3 on AEC-PM1
6. EEP4 External memory folder 4 on AEC-PM1
1. RUN Run time memory
2. DFLT Default: On board backup memory
3. EEP1 External memory folder 1 on AEC-PM1
4. EEP2 External memory folder 2 on AEC-PM1
5. EEP3 External memory folder 3 on AEC-PM1
6. EEP4 External memory folder 4 on AEC-PM1
eep1 is shown as 1to3. After confirming the selection, choose YES or AUTO to start the copy process. Select NO to abort.
AUTO s only available if the target is the external plug in. By selecting AUTO: The parameters will load automatically
when the controller is powered up while the AEC-PM1 is plugged in. If one plug-in has several parameter folders with the
AUTO flag set the one with the smallest index will be loaded.
New Feature for products with a communication plug-in. Selecting CO15 = 01 will write back an increased address
to the AEC-PM1 after a successful copy. This way it is easier to configure large projects.
communication in case it is copied to or from. PEND is shown while the copy process takes place.
There are several possibilities for the result:
Good: The copy process was successful
Fail: Err5, Communication problem. The plug in module is either damaged or missing
Fail: Err6, Checksum mismatch. The checksum of the source data was incorrect. Data corruption. This may
happen if the plug-in has not been written to before or data corruption took place.
For universal inputs: 1U to 8U: Signal type (0= not active):
1= 0-10V or 0-20mA
2= 2-10V or 4-20mA
3= NTC
4 = open contact direct (contact open = 100%, closed = 0%)
5 = open contact reversed (contact open = 0%, closed = 100%)
6 = potentiometer input, assign to setpoint selection of control loop
7 = light control mode: toggle and dimmer switch
8 = pulse counting input.
0–8
1
01 u1
Display minimum value. See note below about display resolution.
For potentiometer input: lower range limit of potentiometer in 100 Ohm steps
New feature: only if xxu0 = 1, 2 or 6:
if minimum value is higher than maximum value, the input signal is reversed. 0%
input = 100% signal, 100% input = 0% signal
-50–205
0
01 u2
Display maximum value. See note below about display resolution.
For potentiometer input: Upper range limit of potentiometer in 100 Ohm steps
New feature: only if xxu0 = 1, 2 or 6:
if minimum value is higher than maximum value, the input signal is reversed. 0%
input = 100% signal, 100% input = 0% signal
-50–205
100
01 u3
Range of universal inputs (For analog inputs only: 1u0 = 1,2)
0 – 5
0
0 = x1
1 = x10
2 = x100
3 = square root
4 = square root x 10
5 = square root x 100
01 u4
Analog input unit: 0= no unit, 1= %, 2= °C /°F, 3= Pa
0–3
1
01 u5
When 01u0 = 1-5: Select number of samples taken for low pass filter: Filtering
prevents unwanted fluctuation of sensor signals. The controller measures signal inputs
every second and calculates the input signal based on a number of measured values
and a digital low pass filter. Take into account that signal reaction delays as the number
of samples taken for the filter increases.
Note: changing this value will as well change 01u8
0–100
3
01 u6
Sensor calibration
Per input range
0.0
01 u7
Calculate mathematical function over multiple inputs (0=not active):
1= average, 2= minimum, 3= maximum, 4= differential UI(n) – UI(n-1)
0–4
0
01 u8
New Feature:
When 01u0 = 7 (light switch), select auto switch off time. Set to 0, if output should not
automatically switch off.
Note: Shared value: changing this value will as well change 01u5
00:00s...15:10h
MM:SS...HH:MM
00:15
MM:SS
Input & alarm/interlock configuration
Universal inputs (analog, binary or passive)
Set jumpers on the back of the controller: 0–10VDC (default), 0–20mA, or RT/DI (passive temperature or binary)
Match sensor range to input display. With a differential pressure transmitter having 0–200 Pa measuring range set 01U1
display minimum to 0 and 01U2 display maximum to 200. The allowable range value of -50–205 may be adjusted with
multipliers in 01U3. The largest displayable values are -990–9999.
Passive temperature input is NTC 10k@25°C (77°F). Specified accuracy can only be guaranteed using Vector Controls Sxx-
Tn10 sensors. Range values described above also apply to temperature inputs.
Display resolution (01u1 and 01u2)
Limiting the display range increases set point resolution. A range <25 provides set point steps of 0.1°C (0.2°F). A range
<125 provides set point steps of 0.5°C(0.1°F). Larger ranges increase by 1 step. Square root input range (0xu3) has no
influence.
Note: Fahrenheit and differential steps are doubled.
New Feature: open contact as input type (01u0 = 4 or 5): For an open contact input set the jumper to RT/DI and
parameter 01u0 to open contact (4 or 5). If set to 4 (open contact direct), an open contact reads as a high value (100%), a
closed contact as a low value (0%). If set to 5 (open contact reversed), an open contact reads as low value (0%) and a
closed contact as high value (100%). Note: sensor calibration does not work for binary inputs.
New Feature: potentiometer input (01u0 = 6). A potentiometer may be connected to a passive input to control the
setpoint of a control loop. With the input display minimum and maximum values the range of the potentiometer can be
defined in 100 ohms steps. For example setting the 1u01 to 50 and 1u02 to 120 represents a potentiometer from 5k to 12k
Ohm. The resistance is measured and calculated into a 0-100% value. Based on the potentiometer input, the setpoint will
now be moved between the upper and lower setpoint limits of the control loop. There are other uses for the potentiometer
input. For example, the controller can be enabled and disabled remotely with a potentiometer using an input in
potentiometer mode assigned to the Auxiliary Function Enable/Disable (1FU). Or use Alarm/Interlocks assigned to the
potentiometer input to activate or deactivate outputs. With the potentiometer fully on, for example, another interlock could
activate a boost mode. The potentiometer could then read OFF (65°F) to Full (85°). Add one more wire connected to a 10k-2
resistor and measure the room temperature as well. Thus with 3 wires in total ( potentiometer, common, room temperature)
a well-functioning low cost operation terminal may be realized.