Intelligent Fan Coil controller
Features
Deluxe Version:
TLC-FCR-2 Engineering Manual
• Low power energy consumption: < 1W per unit
• Relays switching for outputs each up to 300W
• Temperature control for 2 or 4-pipe fan coil systems.
• Large temperature range from –40°C to 70°C (-40°F to 158°F).
• Choose between one 3-point actuator and two binary
heating/cooling stages
• Automatic fan control for three stage fans.
• Cost saving option with Economy functionality and set point
limitations
• Control for single stage heating, cooling and fan only operation
modes
• Password protected programmable user and control parameters
o Setpoint range limitation
o Access control for setpoints, fan speeds and mode
change
o Access control for heat/cool change and time programs
o Select your display contents
o Selectable behavior after return from power failure
• Temperature display in Celsius or Fahrenheit
• Clock and time schedule functions
• Blue backlight for LCD
• Infrared remote controller option:
With special features for Boost and delayed switching on or off
Applications
• Air Only Systems:
o Constant Air Volume systems with thr ee stage fans for single or dual duct systems
• Air/Water Systems:
o Fan Coil units for 2-pipe or 4-pipe systems
o radiator control, chilled ceiling
• Simple individual room control for hotel rooms, meeting rooms, etc.
General Description
The TLC-FCR-2 is a stand-alone electronic fan coil controller with one control loop. The TLC-FCR-2 features 1 NTC
temperature sensor input and four binary outputs (Relays).
A detailed parameterization is possible with the use of a simple configuration routine. The TLC-FCR-2 can be
configured using the standard operation terminal. No special tools or software is required.
Ordering
Item Name Item code Variant Features
TLC-FCR-2
TLC-FCR-2-W01
TLC-FCR-2-D
TLC-FCR-2-D-W01
40-10 0017
40-10 0017-01
40-10 0018
40-10 0018-01
Standard
Cooling only
Deluxe
Cooling only
Fan coil controller with:
1 TI int
3 DO (Relay) Fan control
2 DO (Relay) Binary valve control
Selection of valve actuators and fans
Binary auxiliary devices: E.g. fans, on/off valves, etc. Do not directly connect devices that exceed 2(1.2)A. Observe
startup current on inductive loads! Do not connect more than one fan coil unit to one controller.
Doc: 70-00-0081, Date: 20081219 © 2008 Vector Controls Ltd. Page 1

TLC-FCR-2 Engineering Manual
Technical Specification
Power Supply Operating Voltage 210 – 240 V AC 50/60 Hz
Power Consumption Max 1W, 1.5 VA
Electrical Connection Terminal Connectors
Deluxe type only:
Signal Inputs Temperature Inputs
Signal Outputs Digital Switching Outputs
Environment Operation
Transport & Storage
Standards
General Dimensions (H x W x D) Front part: 21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.)
Weight (including package) 260g
Power backup for real time clock
Range
Resolution
Accuracy
Switching type
AC Switching power
Climatic Conditions
Temperature
Humidity
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
conform according to
EMC Standard 89/336/EEC
EMEI Standard 73/23/EEC
Product standards
Automatic electrical controls for
household and similar use
Special requirement on
temperature dependent controls
Degree of Protection IP30 to EN 60 529
Safety Class II (IEC 60536)
Mechanical Design and Installation
The unit consists of three parts:
1. The mounting plate made of galvanized steel.
2. The power case made of fire proof ABS plastic.
3. The front part made of white fire proof ABS plastic.
Installation
1. Arrange the wires to be connected and cut them to equal length.
2. Connect them to the terminals of th e power case according to wiring diagram
3. Clip the power case to the mounting plat e, pull the connection cable through the large central opening of the
mounting plate. Insert the power case into the flush mounting box. Carefully arrange power wires.
4. Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is
facing to the ground. Make sure the screw heads do not stand out more than 5 mm of the surface of the
mounting plate.
5. Connect the connection cable to the plug located on the back of the front part.
6. Slide the two latches located on the to p of the front part into the hooks of the mounting plate.
7. Lower the front part until located flat on the wall and the mounting plate is not visible anymore. Make sure
the connection cable does not get into the way.
8. Tighten the front holding screw to secure the front par t to the mounting plate.
Mounting location
• On an easy accessible interior wall, approx. 1.5 m above the floor in an area of average temperature.
• Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical
equipment.
• Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.
• Location of mounting is less critical if external temperature sensors are used.
Min 48h if charged for 24h
RT Internal
-40°C…70°C (-40°F to 158°F)
0.1°C (0.1°F)
0.5°C (1°F)
DO1…DO5
Relays
2(1.2) A, 250VAC (max fan power 300W)
To IEC 721-3-3
class 3 K5
0°C …50°C (32°F…122°F)
<95% R.H. non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25°C…0°C (-13°F…158°F)
<95% R.H. non-condensing
class 2M2
EN 61 000-6-1/ EN 61 000-6-3
EN 60 730 –1
EN 60 730 – 2 - 9
Power case: 60 x 50 x 30mm (2.4 x 2.0 x 1.2 in.)
Doc: 70-00-0081, Date: 20081219 © 2008 Vector Controls Ltd. Page 2

Dimensions
Wiring Diagram
43 (1.7)
88 (3.5)
TLC-FCR-2 Engineering Manual
Space required in flush mounting box:
(H x W x D)
60 x 50 x 30mm (2.4 x 2.0 x 1.2 in.)
30 (1.2)
88 (3.5)
30 (1.2) 21 (0.8)
Distance for mounting screws:
Horizontal and vertical:
45 to 63mm (1.8 to 2.5 in.)
Front part
Plug
CPU
RT
Connection terminals
1
0V AC 2 220V AC
3
Fan Low 4 Fan Med 5 Fan High 6 Open / H 7 Close / C
!
Attention: Switching power is
TLC-FCR-2
Attention: Switching power
is limited to 230VAC, 300W
1
N
2
~
3
DO1
4
DO2
5
DO3
6
DO4
7
DO5
Legend
1: 0V AC Neutral Power Supply
2: 230V AC Power Supply
3: DO1 = Fan Speed Low
4: DO2 = Fan Speed Medium
5: DO3 = Fan Speed High
6: DO4 = Heat for binary actuators
OPEN for 3-point actuators
7: DO5 = Cool for binary actuators
CLOSE for 3-point actuators
N
Fan Low
Fan Medium
Fan High
Heat, OPEN
Cool, CLOSE
Connection Diagram
230V AC L
230V AC L
2
2
1
3 4 5
FAN
1-3
6 7
HEAT
COO
1
3 4 5
FAN
1-3
6 7
3-point
actuator
0V AC N
Subject to alteration
Doc: 70-00-0081, Date: 20081219 © 2008 Vector Controls Ltd. Page 3
0V AC N