Temperature PID Controller
TCY-MT-U Series Intelligent Temperature Controller
Features
• Temperature PID control for HVAC systems.
• Up to 2 modulating outputs for DC 0...10V with 10mV resolution.
• 1 internal temperature sensor and up to 2 external sensor inputs
• Multiple remote control functions on external input
• Password protected programmable user and control parameters
• Blue backlight
Applications
• Various temperature control applications
• Stand alone VAV control for pressure independent actuators
• Water Only Systems: Radiator, floor heating or chilled ceilings
• Individual room control for offices, residential, hotel rooms,
meeting rooms, etc.
General Description
The TCY-MT-U is a stand-alone electronic universal controller with one
temperature control loop. It may use up to 2 PID sequences. The TCYMT-U features one internal NTC temperature sensor, up to two external
sensor inputs and up to two analog outputs. The configuration has been
reduced to a minimum to allow for a simple and off the shelve usage.
For more advanced features and current in- and outputs the TCI product
range is recommended. The TCY-MT-U can be configured using the
standard operation terminal. No special tool or software is required.
TCY-MT-U
Name
T C Y
-
T
2
Housing: U = Vertical (2x4”) housing, Standard is square housing
Function: 2 = 2 = 2-Pipe, 4 = 4-Pipe
Input: T = Temperature, H = Humidity
Output: M = Modulating, B = Binary
Series: TCY
Ordering
Item Name Item code Control Type Key-data
TCY-MT2-U-W1 40-10 0044-1 Cooling only
TCY-MT2-U-W2 40-10 0044-2 Heating only
TCY-MT2-U 40-10 0044 2-Pipe system
TCY-MT4-U 40-10 0046 4-Pipe system 1 TI, 2 AO
Accessories
S-Tn10-2
SD-Tn10-12-2
SD-Tn10-20-2
SDB-Tn10-12
SDB-Tn10-20
SOA-Tn10
40-20 0001
40-20 0002
40-20 0003
40-20 0051
40-20 0004
40-20 0006
Flying lead sensor with 2 m cable
Flying lead duct sensor 12cm immersion depth, 2m cable
Flying lead duct sensor 20cm immersion depth, 2m cable
Duct sensor with housing, 12cm immersion depth
Duct sensor with housing, 20cm immersion depth
Outdoor sensor
Compact PID controller with:
2 TI, 1 AO
Selection of actuators and sensors
Temperature Sensors:
Use only our approved NTC sensors to achieve maximum accuracy. Recommended is SDB-Tn10-20 as Duct sensor, SRATn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.
Modulating Actuators:
Choose actuators with an input signal type of 0-10V DC or 2-10V DC.
Doc: 70-00-0176 V1.1, 20100908 © Vector Controls GmbH, Switzerland Page 1
Subject to alteration

Technical specifications
Power Supply
Signal inputs
Signal outputs
Environment
Standards
General
Operating Voltage 24 V AC/DC ± 10 %, 50…60 Hz
Power Consumption Max. 1.5 VA
Electrical Connection Terminal Connectors,
Temperature Input
Range 0…50 °C (32…122 °F)
Accuracy 0.5 K
Analog Outputs
Output Signal
Resolution
Maximum Load
Operation
Climatic Conditions
Temperature
Humidity
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
Product standards
Automatic electrical controls for
household and similar use
Special requirement on
temperature dependent controls
Degree of Protection IP30 to EN 60529
Safety Class III (IEC 60536)
Cover, back part
Mounting Plate
Dimensions (H x W x D) Front part: 112 x 73 x 15 mm (4.4” x 2.9” x 0.6”)
Weight (including package) 270 g (9.5 oz)
conform according to
EMC Standard
89/336/EEC
EMEI Standard 73/23/EEC
TCY-MT-U
Temperature PID Controller
wire 0.34…2.5 mm
AO1, For TCY-MT4-U AO2
DC 0...10 V
9.76 mV (10 bit)
2 mA
To IEC 721-3-3
class 3 K5
0…50 °C (32…122 °F)
<95 % r.H. non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25…70 °C (-13…158 °F)
<95 % r.H. non-condensing
class 2MT2
EN 61 000-6-1/ EN 61 000-6-3
EN 60 730 –1
EN 60 730 – 2 – 9
Fire proof ABS plastic (UL94 class V-0)
Galvanized Steel
Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)
2
(AWG 24…12)
Dimensions [mm] (inch)
73 (2.9)
112 (4.4)
Doc: 70-00-0176 V1.1, 20100908 © Vector Controls GmbH, Switzerland Page 2
Subject to alteration
32 (1.2
15
0.6
58 (2.3)

Connection diagram
24V AC/DC
COM
TCY-MT-U
Temperature PID Controller
X
T CO
IN
COM
X
T EXT
IN
0V (COM)
24V AC/DC
0V (COM)
Description:
G0 Power supply: 0V, -24VDC, internally connected to signal common
G Power supply: 24VAC, +24VDC
M Signal common: Common 0 potential for analog inputs and analog outputs.
X1 External temperature input: NTC 10kΩ @ 25°C (77°F)
TCY-MT2-U:
X2 Changeover input: NTC 10kΩ @ 25°C (77°F)
U1 Analog output: 0…10 V DC
TCY-MT4-U:
U1 Analog heating output: 0…10 V DC
U2 Analog cooling output: 0…10 V DC
2
G
1
G0
2
G
1
G0
5
M
3
G0
COM
3
Signal
COM
6
X2
4
U1
H/C
OUT
4
1
Heat
OUT
7
M
Signal
COM
7
M
5
Signal
COM
8
X1
X
T EXT
IN
8
X1
6
Cool
OUT
X
T INT
TCY-MT2-U
X
T INT
TCY-MT4-U
Mechanical Design and installation
The unit consists of two parts: (a) The power case with attached mounting plate and (b) the front part.
Mounting location
• On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of average temperature.
• Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical
equipment.
• Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.
• Location of mounting is less critical if external temperature sensors are used
Installation
1. Connect the wires to be connected to the terminals of the power case according to wiring diagram
2. Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is
facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the
surface of the mounting plate.
3. Ensure that the jumpers are set correctly.
4. Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.
5. Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle
way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is
normal. Do not use excessive force!
6. With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to
the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the
screw too much.
Doc: 70-00-0176 V1.1, 20100908 © Vector Controls GmbH, Switzerland Page 3
Subject to alteration