Vector TCY3-T0121R, TCY3-T0121R-D, TCY3-T0121R-U-D, TCY3-T0121R-H, TCY3-T0121R-H-U User Manual

...
TCY3-T0121R Series Intelligent Compact Controller

Features

Temperature control for 2-pipe, 4-pipe HVAC
-H version: Humidity control with integrated
humidity sensor
Universal PID and binary control for any
analog input/output signal and range
4 independent PID sequences, 12
independent binary sequences
1 modulating output for DC 0...10V or 0…20
mA actuators with 10 bit resolution.
1 Input for DC 0…5V, 0…10V or 0…20 mA
sensors with 10 bit resolution
1 internal temperature sensor and 1 external
sensor input
Multiple functions on external input: auto
changeover, remote control
Monitoring of low and high limits on all inputs.
Programmable reaction in case of alarm.
Feedback function for internal sensors and
set points.
Special functions for dehumidifying, set point
shift and VAV control
Transformation of display value according to
analog sensor range
Password protected programmable user and
control parameters
Blue backlight
Deluxe Version only:
o Power Cap protected real time clock with 24h
power backup
o 16 switching times, grouped in 4 time
schedules.
o Infrared remote control
TCY3-T0121R

Applications

Air Only Systems: Constant or Variable Air Volume systems for single or dual duct systems with options of:
Air/Water Systems:
Water Only Systems: Radiator, floor heating or chilled ceilings
Individual room control for hotel rooms, meeting rooms, etc.
o up to two reheat stages o supply air, extract air cascade control o humidity control o Control for variable speed fans
o Fan Coil units for 2-pipe or 4-pipe systems with options of:
Humidity control Pressure control
o radiator control, chilled ceiling

General Description

The TCY3 is a stand-alone electronic universal controller with two autonomous control loops. Each control loop may use up to 2 PID sequences and 6 binary sequences. The TCY3-T0121R features 1 NTC temperature sensor and 1 analog input, 2 binary outputs and one analog output. The outputs need to be assigned to the control sequences by parameters. A detailed configuration is possible by following a simple setup routine. The TCY3 can be configured using the standard operation terminal. No special tool or software is required.
Doc: 70-000002 V1.0, 20101115 © Vector Controls GmbH, Switzerland Page 1 Subject to alteration
)
(
)
(
)

Name

TCY3-T0121R Technical Data
C YT T 0 1 2 1 H(- ) U(- ) D(- )-3

Ordering

Model Stock code Variant Mounting size Type Key-data
TCY3-T0121R 40-10 0021 Standard TCY3-T0121R-D 40-10 0022 Deluxe TCY3-T0121R-U 40-10 0023 Standard TCY3-T0121R-U-D 40-10 0024 Deluxe TCY3-T0121R-H 40-10 0025 Standard TCY3-T0121R-H-D 40-10 0026 Deluxe TCY3-T0121R-H-U 40-10 0027 Standard TCY3-T0121R-H-U-D 40-10 0028 Deluxe

Dimensions [mm] (inch)

88 (3.5) 32 (1.2
R
88mm x 88mm
2” x 4”
88mm x 88mm
2” x 4”
21
(0.8)
Deluxe version 2” x 4” housing Integrated Humidity sensor Relays for binary outputs Number of analog outputs (AO) = 1 Number of binary output (DO) = 2 Number of analog inputs (AI) = 1 Number of binary inputs (DI) = 0 With external temperature input (RT) Series (TCY3)
No humidity sensor
With humidity sensor
Compact PI controller with: 1 TI int or ext 1 AI 2 DO (Relay) 1 AO
88 (3.5)
73 (2.9)
112 (4.4)
32
1.2 15
0.6
58 (2.3)
58 (2.3)
Doc: 70-000002 V1.0, 20101115 © Vector Controls GmbH, Switzerland Page 2 Subject to alteration

Technical specifications

Power Supply
Signal inputs
Signal outputs
Environment
Standards
General
Operating Voltage 24 V AC/DC ± 10 %, 50…60 Hz
Power Consumption Max. 3 VA
Electrical Connection Terminal Connectors,
Internal rectification: Signal ground = power ground
Clock backup 24 hours (Deluxe version only)
Analog Input Input Signal Resolution
Temperature Input
Range Int. NTC: 0…50 °C (32…122 °F)
Accuracy -40…0 °C (-40…32 °F): 0.5 K
Humidity Input: (-H Version only) Range Accuracy at 55 % r.H. Hysteresis Repeatability Stability
Analog Outputs Output Signal Resolution Maximum Load in voltage mode
Relays Outputs AC Voltage DC Voltage
Operation Climatic Conditions Temperature Humidity
Transport & Storage Climatic Conditions Temperature Humidity Mechanical Conditions
Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls
Degree of Protection IP30 to EN 60 529
Safety Class III (IEC 60536)
Cover, back part Mounting Plate
Dimensions (H x W x D) Front part: 88 x 88 x 21 mm (3.5” x 3.5” x 0.8”)
Dimensions (H x W x D), U-version Front part: 112 x 73 x 15 mm (4.4” x 2.9” x 0.6”)
Weight (controller only) 180 g (6.3 oz)
Weight (including package) 260 g (9.2 oz)
conform according to EMC Standard 89/336/EEC EMEI Standard 73/23/EEC
TCY3-T0121R Technical Data
wire 0.34…2.5 mm
Half wave rectified Security transformer required
AI1
0...10 V or 0...20 mA
9.76 mV or 0.019 mA (10 bit)
Ext. NTC (Sxx-Tn10 sensor): -40…140 °C (-40…284 °F)
0…50 °C (32…122 °F): 0.2 K 50…100 °C (122…212 °F): 0.5 K > 100 °C (> 212 °F): 1 K
H1 Thermoset Polymer-Based Capacity 0…100 % r.H.
± 3.0 % at 25 °C (77 °F) ± 3 % between 15…90 % r.H. ± 0.5 % ± 0.5 % / year if used within 0…50 °C (32…122 °F)
AO1 DC 0...10 V or 0...20 mA (250 max.)
9.76 mV resp. 0.019 mA (10 bit) 10 mA
DO1, DO2 0…48 VAC, 2 (1.2) A max. each output 0…30 VDC, 2 (1.2) A max. each output
To IEC 721-3-3 class 3 K5 0…50 °C (32…122 °F) <95 % r.H. non-condensing
To IEC 721-3-2 and IEC 721-3-1 class 3 K3 and class 1 K3
-25…70 °C (-13…158 °F) <95 % r.H. non-condensing class 2M2
EN 61 000-6-1/ EN 61 000-6-3
EN 60 730 –1
EN 60 730 – 2 – 9
Fire proof ABS plastic (UL94 class V-0) Galvanized Steel
Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)
Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)
2
(AWG 24…12)
Doc: 70-000002 V1.0, 20101115 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration
TCY3-T0121R Technical Data

Selection of actuators and sensors

Temperature Sensors:

Use only our approved NTC sensors to achieve maximum accuracy. Recommended is SDB-Tn10-20 as Duct sensor, SRA­Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.

Modulating Actuators:

Choose actuators with an input signal type of 0-10 V DC or 4-20 mA. Minimum and maximum signal limitations may be set in software.

Floating Actuators:

Actuators with constant running time are recommended. Observe power limits on binary devices.

Binary auxiliary devices:

E.g. pumps, fans, on/off valves, humidifiers, etc. Do not directly connect devices that exceed 48 VAC, 2(1.2) A. Observe startup current on inductive loads.

Connection diagram

0...48 V
0...30 V
AC
DC
24V AC/DC ±10%
0V (GND)
Description:
Binary output 1: 0…48 VAC or 0…30 VDC
Y
B1
Y
Binary output 2: 0…48 VAC or 0…30 VDC
B2
X
Analog input 1: 0…5 V, 0…10 V or* 0…20 mA
A1
Y
Analog output 1: 0…10 V or* 0…20 mA
M1
R
Temperature input 1: NTC 10k @ 25°C (77°F)
T
23
145678
0V
*
) selectable by jumper
TCY3-T0121..
Y
B1
Y
B2
Y
M1
X
A1
R
T
!
U
WARNING:
Power supply is half-wave rectified:
Signal ground = Power ground
Connect through a safety isolation transformer
Doc: 70-000002 V1.0, 20101115 © Vector Controls GmbH, Switzerland Page 4 Subject to alteration
TCY3-T0121R Installation

Connection terminals and jumpers

Terminal-description:

1. Connection for power-supply (24 V AC/DC, ±10%).
In case of DC, connect the negative power­terminal. Common connection for analog in- and outputs.
2. Connection for power-supply (24 V AC/DC, ±10%).
In case of DC, connect the positive power-terminal
3. Common for relays
4. Switched contact “DO 1” (Max. 2 (1.2A)
5. Switched contact “DO 2” (Max. 2 (1.2A)
6. Analog-output “AO 1” (Jumper-selectable between
0…10 V or 0…20 mA)
7. Analog input “AI 1” (Jumper-selectable between
0…10 V or 0…20 mA)
8. Thermistor input “RT” (Thermistor Sxx-Tn10)

Jumper-settings (standard version shown):

Jumpers are mounted vertically only.
1. AO - Selection of output type: a. Left position: voltage output (0…10 V),
factory default
b. Right position: current output (0…20 mA)
2. AI - Selection of input type: a. Left position: voltage input (0…10 V),
factory default b. Middle position: current input (0…20 mA) c. Right position: RT or dry-contact input

Mechanical Design and installation

The unit consists of two parts: (a) The power case with attached mounting plate and (b) the front part.

Mounting location

On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of average temperature.
Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical
equipment.
Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.
Location of mounting is less critical if external temperature sensors are used

Installation

1. Connect the wires to be connected to the terminals of the power case according to wiring diagram
2. Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is
facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the surface of the mounting plate.
3. Ensure that the jumpers are set correctly.
4. Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.
5. Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle
way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is normal. Do not use excessive force!
6. With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to
the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the screw too much.
Doc: 70-000002 V1.0, 20101115 © Vector Controls GmbH, Switzerland Page 5 Subject to alteration
TCY3-T0121R Operation

Display and Operation

The operation terminal uses an LCD display and four operation buttons.
1
5 6
7

Legend:

1. 4-digit display of current value, time, control parameter or set point
2. Unit of displayed value, °C, °F, % or none
3. Graphical display of output or input value with a resolution of 10%
4. 4-digit display of current value, time, control parameter or set point
5. Operation modes: Comfort mode, Standby mode, Energy Hold Off
6. Symbols:
Heating Active Cooling Active Schedule Set Direct Acting
7. POWER button: Standard function: Pressing the button less than 2 sec toggles standby and comfort mode.
Pressing the button for more than 2 seconds switches the unit off. Programming function: ESC function, to return to previous level or ignore changed value
8. UP buttons: increment set points and parameters, select menu options
9. OPTION button: Standard function: If pressed less than 2 sec access for different control modes
If pressed for more than 2 sec starts operation level for advanced users. Change of time schedules, offsets and heat – cool settings. Programming function: Acts as Enter to select menu option or accept changed parameter value.
10. DOWN buttons: decrement set points and parameters, select menu options
Active
2 3 4
8 9 
Reverse Acting
Active
Cascade Override

Operation Modes

Comfort: The unit is in full operation mode. All the control functions are operating according to their setpoints.
The unit displays occupied mode.
Standby: The set points are shifted according to parameters 1L00 or 2L00. The heating parameter is shifted
down and cooling parameter up. The unit displays unoccupied mode. Outputs are limited to OP04 standby maximum. For two stages heating or cooling the second stage will not operate while in standby mode. Standby operation may be disabled with UP06.
Energy Hold-Off (EHO): The unit is turned off, and "Off" is displayed. However, the inputs are still monitored and
the alarm functions will operate normally.

Activation of operation modes

Via operation terminal
Clock (Deluxe version only): Operation modes may automatically be switched according to daytime and weekday.
The clock symbol will be indicated if time programs are activated.
Infrared Remote Controller (Deluxe version only): use OPR-1 to control the unit remotely
Doc: 70-000002 V1.0, 20101115 © Vector Controls GmbH, Switzerland Page 6 Subject to alteration
TCY3-T0121R Operation

Operation of the Terminal Unit

Switching ON

The unit is switched on by pressing the POWER button. It will start up in comfort mode.

Changing between COMFORT and STANDBY

Pressing the POWER button for less than 2 seconds toggles between STANDBY and COMFORT modes. Standby mode may be disabled with UP06.

Switching OFF

Pressing the POWER button for more than 2 seconds, will switch the unit off. OFF and current time will be displayed in the LCD for the deluxe unit. Current temperature and OFF is displayed for the basic unit.

Standard display

Standard display is enabled with parameter UP08. This display mode is active if no UP/DOWN or OPTION key has been pressed during the previous 30 seconds. The contents of the large and small digits may be chosen with parameters UP09 to UP10. Should Standard display be disabled, the selected loop setpoint will be displayed in the small digits, the associated input in the large digits and the output in the right hand scale.

Changing of set points

If two control loops are enabled, step through loop 1 and loop 2 by pressing the OPTION/RIGHT button. The large digits show Lp1 and Lp2 alternately with the set point of that loop shown in small digits. With the desired control loop displayed change its set point with the UP/DOWN buttons. If only one control loop is enabled press the OPTION/RIGHT button to display set point in small digits and adjust with UP/DOWN buttons (Lp1 or Lp2 is not shown). Changing of setpoints may be disabled with UP01.

Override of secondary set point in cascade control

If cascade control is active (for example VAV control), it is possible to override the primary loop and manually set the set point of the secondary loop. While the secondary loop is displayed change the set point with UP/DOWN keys. The manual indication will show on the display. (For VAV this would mean the loop is now changed to CAV. This is especially useful while tuning the VAV system) Pressing the OPTION key to move back to the temperature loop will cancel manual override. Manual override may be disabled with UP02.

Power Failure

All the parameters and set points are memorized and do not need to be reentered. Depending on UP05 the unit will remain switched off, switch on automatically or return to the operation mode it was in before the power failure. Deluxe version only: Timer operation and daytime setting will be retained for 24h. The controller has to be connected to a power supply for at least 10 hours for the backup function to operate accordingly.

Clock Operation (Deluxe Version)

The TCY3 contains a battery backed up quartz clock. Up to 16 mode changes (STANDBY, COMFORT, OFF) based on weekdays and time may be programmed. See chapter operation on how to program and assign switch times to the corresponding loops. A blinking clock indicates that the time has not been set. This may occur if the time was never set or if the unit was without power for longer than 24 hours. The time needs to be set in order to allow time programs to operate. See chapter operation, advanced settings for instructions on how to set the time.

Error messages

The TCY3 may display the following error condition:
Err1: Temperature sensor faulty or missing. The connection to the temperature sensor may be interrupted or the
Err2: The internal humidity sensor is damaged or missing. All outputs connected to this sensor will be set to off mode.
Err3: Problem with the internal real-time clock. Time schedule programs are not operating, time related functions will
temperature sensor is damaged. All outputs connected to this sensor will be set to off mode. Sensor feedback signals will be set in alarm mode.
Sensor feedback signals will be set in alarm mode.
not be accurate. Clear the error message with OPTION key. If error reappears, replace product.
Doc: 70-000002 V1.0, 20101115 © Vector Controls GmbH, Switzerland Page 7 Subject to alteration
Loading...
+ 16 hidden pages