Vaisala CARBOCAP GMM112, CARBOCAP GMM115 Quick Reference Manual

ELECTRICAL CONNECTIONS
MOUNTING AND DIMENSIONS
Quick Reference Guide
Vaisala CARBOCAP® Carbon Dioxide Module GMM112 and
– GMM112 compact diffusion
aspirated CO applications
module for OEM
2
mA Signal 4 ... 20 mA V Signal (+) 0 ... 10 V 0 Signal (-) B RS-485 Signal B A RS-485 Signal A 0 Power supply (-) 24V Power supply (+) 24 VDC/VAC
Dimensions
mA
mA
V
Ø3.2
V
0
0
B
B
A
A
0
0
24V
24V
96
25656
See Figure 3 for wire terminals.
Powering
The products require a nominal 24 VDC/VAC power supply maintaining a voltage of 18 ... 30 VDC or 20 ... 26 VAC for all load conditions and all mains voltages. Although the power input includes a half-wave rectifier, it is recommended to use a DC supply to avoid current peaks.
Connections to 24 VAC Power Supply
Connecting more than one transmitter to a single 24VAC transformer forms a common loop and increases the risk of a
Figure 3 GMM112 Module Connections and Dimensions
30
60
0601-004
66.3 60
short-circuit. Therefore, a separate floating supply for each transmitter is recommended (see Figure 1).
If several transmitters share a common transformer, the phase (~) must always be connected to the 24 V connector in each transmitter (see Figure 2).
85.2
83.4
85.
3
1
.
2
R
2
4.
Ø
60
66.7 124
120.9
– GMW115 CO
transmitter for wall
2
mounting
– Measurement range 0 ... 2000 ppm or
0 ... 5000 ppm CO
2
– Ideal for HVAC applications
0601-001
25.8
Figure 1 Connection of Separate AC Supplies (Recommended)
Figure 4 GMW115 Transmitter Dimensions
0601-002
Figure 2 Connection of Single AC supply to Several Transmitters
R3
.
5
84
0601-005
Mounting the GMW115 Transmitter
Mount the back plate onto a wall using screws. Make sure the back plate is mounted in with the same orientation as in Figure 4.
GMW115 Cover Opening/Closing
0601-006
Figure 5 Opening the GMW115 Cover
0601-007
Figure 6 Closing the GMW115 Cover
SERIAL COMMUNICATION INTERFACES
The modules support RS232 or RS485 communication. RS232 is set as factory default. The RS485 interface is selected by serial command. The communication settings for both interfaces are: 9600, N, 8, 1.
RS485 Interface
The interface is non-isolated two-wire interface with no internal bus termination. If termination is needed, use RC termination (100 resistor in series with 1 nF capacitor) at both ends of the bus. See serial commands list below to activate the RS485 interface.
RS232 Interface
Use the RS-232 interface for setting the operating parameters. The connection cable between PC and module (a serial COM adapter for maintenance purposes) is available from Vaisala (order code: 19040GM).
www.vaisala.com Ref. M210746EN-D
SERIAL COMMANDS
Serial commands are the same for RS232 and RS485 interface. <cr> stands for pressing ENTER.
Polling command for CO
SEND <cr>
Setting the interval for the RUN (continuous output) mode:
INTV X Y<cr>
X = 0 (default) ... 255 Y = S/MIN/H
Starting the continuous mode printing:
R<cr>
Stopping the continuous mode printing:
S<cr>
Saving the parameters into the memory:
SAVE<cr>
Enabling/disabling the RS485 interface:
RS485 X<cr>
X = ON/OFF
Changing the operation mode:
SMODE X<cr>
X = STOP (default) / RUN / POLL
Giving the device address:
ADDR X<cr>
X = 0 (default) ... 99
Opening the polling line:
measurement (ppm):
2
TECHNICAL DATA
Property Description / Value Performance
Measurement ranges 0 ... 2000 ppm CO
Measurement accuracy (incl. repeatability, non­linearity and calibration uncertainty)
Long-term stability ± 5 % of range / 5 years Response time 1 min Temperature dependence of
reading Pressure dependence of
reading Warm-up time 1 min 10 min full specification Product lifetime > 10 years Operating environment Operating temperature
range Operating humidity range 0 ... 85 %RH Operating pressure range 700 hPa ... 1200 hPa Inputs and outputs Operating voltage 24 V (±20 %) AC/DC Power consumption < 2 W Connections Screw terminals, wire size
OPEN addr<cr> addr = 0 (default) ... 99
Closing the polling line:
CLOSE<cr>
Outputs
analog 0 ... 10 V, 4 ... 20 mA serial RS-485, 2-wire, non-isolated
Recommended external
SERVICE, CALIBRATION AND ADJUSTMENT
These products are designed to operate their lifetime without maintenance The transmitters are calibrated before shipping from the factory. For technical questions, contact the Vaisala technical support; by e-mail helpdesk@vaisala.com
Repair and calibration services are provided by Vaisala Service Centers:
, or by fax +358 9 8949 2790.
load
current output < 500 voltage output > 1 k
Electromagnetic compatibility
Materials Weight GMM112: 34 g GMW115: 105 g
GUARANTEE
Vaisala issues a guarantee for the material and workmanship of this product under normal operating conditions for one (1) year from the date of delivery. Exceptional operating conditions, damage due to careless handling and misapplication will void the guarantee.
0 ... 5000 ppm CO2
2
±(2.5 % of range + 3 % of reading)
-0.35 % of reading / °C (typical)
+ 0.15 % of reading / hPa (typical)
-5 … +45°C
2
0.5 ... 1.5 mm
EN61326-1: Generic Environment