Vaillant uniSTOR VIH GB SERIES, VIH GB 125 S, VIH GB 155 S, VIH GB 180 S, VIH GB 210 S Instructions For Installation And Use Manual

...
Instructions for Installation and Use
uniSTOR
Unvented hot water storage cylinder
VIH GB 125 S VIH GB 155 S VIH GB 180 S VIH GB 210 S VIH GB 260 S VIH GB 310 S
GB
Contents
Page
1 Description . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 DHW Temperature Control . . . . . . . . . . . . . . . . . 3
1.2 CH Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Immersion Heater . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 Typical applications . . . . . . . . . . . . . . . . . . . . . . . 3
2 Technical data . . . . . . . . . . . . . . . . . . . . 4
3 Instructions for use . . . . . . . . . . . . . . . . 6
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 How to use your uniSTOR hot water cylinder . 6
3.4 Immersion heater . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Important notes . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.6 Guarantee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Note To Installers . . . . . . . . . . . . . . . . . . 8
4.1 Secondary System . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2 Secondary Return . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Installation . . . . . . . . . . . . . . . . . . . . . . . 9
5.1 Installation requirements . . . . . . . . . . . . . . . . . . 9
5.1.1 Siting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.1.2 Mains Water Pressure . . . . . . . . . . . . . . . . . . . . . 9
5.1.3 Pipework – Primary Circuit . . . . . . . . . . . . . . . . . 9
5.1.4 Discharge Pipework . . . . . . . . . . . . . . . . . . . . . . . 9
5.1.4.1 High Level Termination . . . . . . . . . . . . . . . . . . . . 10
5.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.3 Functional diagrams . . . . . . . . . . . . . . . . . . . . . . . 12
5.4 Installation procedure . . . . . . . . . . . . . . . . . . . . . 14
5.4.1 Primary pipework . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.2 Secondary system Pipework . . . . . . . . . . . . . . . 14
5.4.3 Safety valve discharge pipework . . . . . . . . . . . . 15
5.4.4 Drain Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4.5 Electrical Connections and Controls . . . . . . . . . 16
5.4.5.1 Immersion Heater . . . . . . . . . . . . . . . . . . . . . . . 16
5.4.5.2 Electrical Connections to Cylinder Controls . 16
5.4.5.3 Connection details for control systems utilising 2 x 2 port motorised valves via
external wiring box . . . . . . . . . . . . . . . . . . . . . . . 17
5.4.5.4 Connection details for connection to
any UK standard boiler . . . . . . . . . . . . . . . . . . . 19
Page
6 Commissioning . . . . . . . . . . . . . . . . . . . . 20
6.1 Filling Secondary DHW Circuit . . . . . . . . . . . . . . 20
6.2 Filling the Primary Circuit . . . . . . . . . . . . . . . . . . 20
6.3 Operating the Boiler . . . . . . . . . . . . . . . . . . . . . . 21
6.3.1 Cylinder Commissioning Checklist . . . . . . . . . . 21
6.4 User’s Instructions . . . . . . . . . . . . . . . . . . . . . . . . 21
7 Maintenance . . . . . . . . . . . . . . . . . . . . . . 21
8 Fault finding . . . . . . . . . . . . . . . . . . . . . . 22
Appendix
Benchmark Cylinder Commissioning
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
We cannot accept responsibility for any damage which may occur as a result of non-observance of these instructions.
Subject to alteration.
uniSTOR GB2
Description 1
1 Description
The uniSTOR range of unvented hot water storage cylinders are indirectly heated cylinders which are designed for use with UK standard boilers in hot water supply systems.
uniSTOR cylinders are available in six sizes; 125, 155, 180, 210, 260 and 310 litre. The cylinders are of stainless steel construction, insulated with EPS and enclosed in a decorative casing. They are supplied with all necessary cold and hot water controls and a 2 port valve for control of domestic hot water.
The uniSTOR cylinders operate using a mains water pressure supply and do not require a feed from a cold water storage tank. The uniSTOR cylinders have 22 mm DHW outlet and cold water mains inlet connections for optimum flow rate. To achieve optimum performance from the uniSTOR an adequate cold water mains supply pressure and flow rate must be available (see section
5.1.2: Mains Water pressure).
1.1 DHW Temperature Control
The uniSTOR is supplied fitted with a user adjustable domestic hot water (DHW) thermostat which controls a 2 port motorised valve and hence the temprature of the water in the uniSTOR. The external electrical controls should be wired to the 2 port valve and cylinder thermostat in the normal way, as shown in the section Electrical Connections and Controls.
1.4 Applications
The Vaillant uniSTOR can be connected to any UK standard boiler.
1.5 Typical applications
– Single bathroom property:
uniSTOR 125
– Single bathroom property with an en-suite shower
room: uniSTOR 125 / 155
– Two bathroom property:
uniSTOR 155 / 180
– Two bathroom property with an en-suite shower room:
uniSTOR 180 / 210
– Larger properties:
uniSTOR 260 / 310
Commercial use: Size depending upon hot water requirements
Note: 1 Select the appropriate boiler to match the
heating load (with the normal allowance for heating up from cold) plus an allowance for heating the hot water cylinder. Typically it is practice to allow an additional 2-3 kW for the hot water production.
2 Consideration should be given to the use of a
larger size of cylinder than shown above where high water demands are likely.
1.2 CH Control
Central heating is controlled by a separatly fitted 2 port valve in conjunction with suitable external controls, such as a programmer, room thermostat or thermostatic radiator valves.
1.3 Immersion Heater
uniSTOR cylinders are also provided with an auxiliary back up 3 kW electric immersion heater, including operating thermostat and energy cut out. The immersion heater is fitted behind the front panel. It is designed for use in unvented installations and contains a safety overheat thermostat in addition to the operating thermostat. For the uniSTOR 260 and 310 an additional second immersion heater will be available as an accessory.
Note: Only the correct immersion heater containing a safety overheat thermostat may be used for replacement.
uniSTOR GB 3
2 Technical data
2 Technical data
VIH GB 125 S VIH GB 155 S VIH GB 180 S VIH GB 210 S VIH GB 260 S VIH GB 310 S Unit
Size 125 155 180 210 260 310 litres
Maximum water supply pressure 10 bar
Operating pressure 3.5 bar
Pressure reducing valve 3.5 bar
Expansion relief valve 6.0 bar
Expansion vessel charge pressure 4.0 bar
T/P valve 95 / 7.0 °C/bar
Net weight 28 30 33 39 44 49 kg
Weight (full) 145 175 205 245 310 340 kg
Height 969 1179 1339 1499 1789 2109 mm
Cylinder connections:
Cold mains inlet 22 mm compression
DHW outlet 22 mm compression
Balanced pressure cold water outlet 22 mm compression
Secondary return G 3/
Primary flow 22 mm compression
Primary return 22 mm compression
Electrical connections:
3 kW Immersion heater
(according ENBS 60335) 230/240 V, 50 Hz
Length of Immersion heater 430 mm
Two port valve 230/240 V, 50 Hz
Cylinder thermostat 230/240 V, 50 Hz
Coil Specifications:
Heat loss 1.4 1.7 1.8 1.9 2.1 2.4 kW/24h
Heat up time 21 23 24 27 35 47 min
Recovery 18 18.5 19 22 30 42 min
4
Note: Heat up time based on a primary flow rate of 9 l/min at 80 °C. Temperature rise is from 15 °C to 65 °C.
uniSTOR GB4
Technical data 2
VIH GB 310 S
VIH GB 260 S
70
VIH GB 210 S
60
VIH GB 180 S
50
VIH GB 155 S
40
VIH GB 125 S
30
Approximate cylinder heat up time 15 °C to 65 °C (minutes)
20
12
Fig. 1 Cylinder heat up times
Cylinder Heat Up Times
60
Reheat time for 70 % of cylinder contents (minutes)
50
40
30
20
10
15 20 25 30 3835
Heat input to cylinder (kW)
uniSTOR GB 5
3 Instructions for use
3 Instructions for use
3.1 Introduction
Your Vaillant uniSTOR unvented hot water cylinder together with a Vaillant boiler, provides you a modern, efficient, high performance heating and hot water system. Because your uniSTOR hot water cylinder is supplied with water directly from the mains, you get the benefit of mains pressure hot water at your hot taps, without the need for storage tanks in the loft and without a hot water pump. The uniSTOR is made from high quality stainless steel within an easy clean casing. The cylinder is fully insulated using environmental friendly EPS insulation to help keep your hot water running costs at a minimum, and protect the environment!
Your uniSTOR cylinder is tailor made to accompany a Vaillant boiler as well as any other UK standard boiler. All Vaillant boilers are equipped with 'built-in' energy saving technology, such as burner modulation, anti cycling control and high efficiency heat exchangers.
Please read these instructions carefully to ensure that you get the very best out of your Vaillant heating and hot water system.
Note! Your uniSTOR unvented hot water cylinder must be installed by a competent person in accordance with current Building Regulations. Do not remove or adjust any component part of this cylinder. In the unlikely event that your uniSTOR develops a fault, such as a flow of hot water from the discharge pipe, switch the boiler and immersion heater off and contact Vaillant Ltd or your installer.
Note! If the uniSTOR is installed in a cupboard used for airing purposes please ensure that clothing or other articles are not placed on the cylinder or its associated controls.
Note! Access should always be maintained to allow operation of the domestic hot water thermostat control.
3.3 How to use your uniSTOR hot water cylinder
Your boiler and uniSTOR unvented hot water cylinder will provide both central heating and mains pressure hot water.
3.2 Liability
Warning!
We can accept no liability whatsoever for damage or injury resulting from failure to observe these instructions.
Specified use
Vaillant uniSTOR unvented cylinders are made to fulfil the latest technical specification and official safety regulations. These cylinders are designed for use with UK standard boilers for use in hot water supply systems.
The term 'specified use' also covers observance of the operating and installation instructions, along with adherence to the servicing schedules. At the rear of this manual you will find a Benchmark Cylinder Commissioning Checklist which should be completed by the installer and/or commissioning engineer and handed to the user. All CORGI registered installers carry a CORGI ID card and have a registration number. Both should be recorded in your Cylinder Commissioning Checklist. You can check your installer by calling CORGI direct on 01256 372300.
Check that the boiler is operational as detailed in the instructions for use supplied with the boiler.
The domestic hot water thermostat on the uniSTOR can be set from 20 °C to 65 °C. The desired temprature will be set by the installer while commissioning the uniSTOR (normally a setting of 60 °C is adequate).
Note! In hard water areas the DHW temperature selected should not exceed this setting to avoid possible scale build-up.
If a programmer has been fitted to control the central heating and hot water, check that this is set to the desired on and off periods.
The boiler will then operate automatically to heat the cylinder contents at the desired times to the temperature selected. When domestic hot water is used, the boiler will operate to re-heat the cylinder as required.
uniSTOR GB6
Instructions for use 3
3.4 Immersion heater
The electric immersion heater behind the front panel is provided as a back up means of water heating and is not intended for use at the same time that the boiler is heating the cylinder.
3
ON/OFF
2
1
3.5 Important notes
Shutting down the uniSTOR cylinder
To shut down the heating and hot water system for short periods, simply turn off the boiler as shown in the instructions supplied with the boiler.
Frost protection
Please ensure that if you are absent during a period of frost the central heating system remains in operation and the rooms and uniSTOR cylinder are kept above freezing point.
Alternatively you can drain the central heating system, boiler and uniSTOR cylinder. Please contact your Installer.
Care and Maintenance
The casing of the uniSTOR cylinder may be cleaned with a damp cloth and a little soap. Do not use any abrasive or solvent material which could damage the case or fittings. It is important that your hot water cylinder is serviced annually by a competent person. Please contact your installer or Group Service (0870 - 6060777) for further details.
Fig. 1a
1 Immersion heater 2 Switch (Immersion heater ON/OFF) 3 Additional immersion heater for uniSTOR 260 and 310
(as accessory)
3.6 Guarantee
Vaillant offers a guarantee of 25 years for the stainless steel vessel against faulty materials or manufacture. The following information is important as without it your guarantee may be invalid.
1. The warranty will become invalid if the damage is due to frost or freezing, transient voltages, lightning strikes or any act of vandalism or misuse
2. The proof of purchase must be produced in the event of any warranty claim (bill of sale)
3. The uniSTOR must be installed by a competent person to the prevailing standards, installation book and building regulations at the time of installation
4. The Benchmark Cylinder Commissioning Checklist must be completed on installation and kept up to date
5. The uniSTOR must be serviced annually
6. The installation must be in an appropriate location and its use is restricted to potable water (chloride levels less than 200 mg/l)
7. Tampering or modification will invalidate the warranty
8. The guarantee card must be completed and returned to Vaillant Ltd. within 30 days of purchase
9. This guarantee does not cover the effects of scale.
For all other Vaillant parts (electrical, thermal controls, valves and design elements) Vaillant carry a 2 year guarantee.
uniSTOR GB 7
4 Note To Installers
4 Note To Installers
This product has been assessed and found to comply with the requirements of the Building Regulations for unvented hot water storage systems and must not be altered or modified in any way.
The installation must be carried out by a competent person and be in accordance with the relevant requirements of the Local Authority, Building Regulations, Building Regulations (Scotland), Building Regulations (Northern Ireland), and the bye-laws of the local Water Undertaking. The installation is subject to Building Regulation approval, notify the Local Authority of intention to install. In the event of parts replacement, use only genuine spare parts supplied by Vaillant Ltd.
4.1 Secondary System
The uniSTOR is provided with all necessary safety and control devices for unvented DHW operation.
These are as follows: A A prefitted temperature and pressure relief valve
(95 °C, 7 bar).
B A Thermal cut set at 90 °C which when wired to the
2 port valve will isolate the heat source in the event of failure of the cylinder thermostat.
C A cylinder thermostat (20 °C - 65 °C) D Expansion relief valve (6.0 bar) incorporating a non
return valve.
E Pressure limiting valve (3.5 bar) incorporating a line
strainer.
Accessory:
- Additional immersion heater 3 kW No. 0020006765
- VR 65 Control Center for new
Vaillant boilers No. 307 215
Prior to installation, ensure that the cylinder is stored upright in dry conditions.
Please also refer to “General Requirements“ in the installation instructions supplied with the boiler.
4.2 Secondary Return
A secondary return connection is provided in the water control pack. Remove the 3/4 BSP blanking plug from the water control group. Connect onto the control group using an appropriate fitting. Using a WRAS approved circulation pump which incorporates a check valve to prevent backflow (see fig. 6). The secondary connection can be made.
Check that the cylinder has been supplied with the following:
– Packed inside cylinder carton
- Water control pack (pressure reducing valve, expansion relief valve; connections for: balanced cold water, secondary return, expansion vessel)
- Motorised 2 port valve
- Tundish
- Cylinder drain valve
- 4 Compression fittings
- Installation and user instructions
- Mounting kit for expansion vessel
- Expansion vessel:
- 12 litre for VIH GB 125/155
(max. storage volume by 3,5 bar = 155 l)
- 18 litre for VIH GB 180/210
(max. storage volume by 3,5 bar = 255 l)
- 25 litre for VIH GB 260/300
(max. storage volume by 3,5 bar = 315 l)
uniSTOR GB8
Installation 5
5 Installation
5.1 Installation requirements
5.1.1 Siting
Locate the uniSTOR in the building in the most convenient position ensuring that: – The discharge pipe from the tundish can be installed
with a minimum fall of 1:200 and must be terminated in a safe and visible position (see section 5.1.4 Discharge pipework).
– The base chosen for the unit is level and capable of
supporting the weight of the cylinder when full (see section 2: Technical Data).
– The installation site is frost-free. If necessary provide
a frost protection thermostat.
– Access is available for user operation of the DHW
temperature control under the front panel.
– Suitable clearances exist to allow installation, checking
and repressurising of the expansion vessel.
– The installation site chosen does not result in
excessive ”dead leg” distances, particularly to the point of most frequent use.
– A suitable cold mains water supply pipe can be
provided to the uniSTOR direct from the main water stop valve of the building.
– The uniSTOR is factory equipped with adjustable feet
to allow unevent floor surfaces.
5.1.2 Mains Water Pressure
The DHW performance of an unvented cylinder installation will depend on the available mains water supply pressure and flow rate. To achieve optimum performance from the uniSTOR a suitable cold mains water supply must be available, i. e. the measured static pressure from the incoming mains water supply should be at least 2.0 bar. A corresponding flow rate at least 20-25 l/min should be available.
Note: Mains water pressure will be reduced during periods of peak demand. Ensure that measurements are taken during these periods.
Example:
If the measured cold mains supply pressure is 2 bar static and the cold mains flow rate available is 30 l/min, the available flow rate of mixed water at 40 °C will be 25 l/min (from 15 l/min hot water from the uniSTOR at 60 °C together with 10 l/min cold water at 10°C).
In order to minimise frictional losses minimum 22 mm bore is recommended for new cold mains supply pipework into the dwelling although satisfactory performance can be achieved with 15 mm bore pipework.
5.1.3 Pipework – Primary Circuit
The primary circuit pipework between the Vaillant boiler and the uniSTOR should be installed using copper tube of minimum size 22 mm.
If the distance between the boiler and the cylinder is excessive, a larger pipe diameter may be necessary. It is not necessary to install a circulating pump in this pipework because all Vaillant wall mounted boilers contain a built-in circulating pump (except ecoMAX pro open-vented boilers). If the uniSTOR cylinder is used with any other UK Standard boiler a suitable circulation pump must be fitted into the primary circuit.
5.1.4 Discharge Pipework
The outlet connections of both the temperature and pressure relief valve and expansion relief valve should be connected in 15 mm copper tube to the tundish supplied.
The tundish should be installed vertically, as close to the uniSTOR as possible and within 500 mm of the temperature and pressure relief outlet. It must be positioned away from any electrical components and installed in the same space as the uniSTOR cylinder, so that it is visible to the user.
The D1 discharge pipe from the T&P Valve/Expansion valve can be teed together upstream of the tundish (see fig 6). The discharge pipework must be installed using minimum 22 mm copper pipework from the 22 mm connection on the tundish to a safe and visible discharge point. There must be a vertical section of pipe at least 300 mm long, below the tundish before any bends or elbows in the pipework. Increase the diameter of the pipework if the total resistance of the discharge pipework exceeds the figures shown in the table below. The installation of the discharge pipework must be in accordance with G3 (see fig. 2).
Minimum size Maximum total resistance Resistance created
of discharge allowed expressed as a by each elbow
pipework length of straight pipe or bend
from Tundish (i. e. no elbows or bends)
22 mm up to 9 m 0.8 m
The uniSTOR will operate satisfactorily with water supply pressures below 2 bar although flow rates will be reduced. If the supply pressure is below 1 bar the uniSTOR unvented storage cylinder should not be installed. Contact Vaillant Ltd. for details on alternative hot water supply systems.
uniSTOR GB 9
28 mm up to 18 mm 1.0 m
35 mm up to 27 mm 1.4 m
5 Installation
y
Example
22 mm discharge pipe having 4 elbows and a length of 7 m from the tundish to the discharge point:
Resistance for 4 elbows at 0.8 m each = 3.2 m Resistance of discharge pipe = 7.0 m Total Resistance = 10.2 m
The total resistance of the discharge pipework is greater than the maximum allowed for 22 mm pipework (9 m). Therefore calculate the next largest size.
28 mm discharge pipe with 4 elbows and 7 m length from tundish to discharge point.
Resistance for 4 elbows at 1.0 m each = 4.0 m Resistance of discharge pipe = 7.0 m Total Resistance = 11.0 m
The total resistance of the discharge pipework is less than the maximum allowed for 28 mm pipework (18 m) therefore the discharge pipework size is acceptable.
metal discharge pipe from temperature relief valve to tundish
safety device (e.g. temperature relief valve)
500 mm maximum
300 mm minimum
tundish
Discharge below fixed grating
providing that where children may play or otherwise come into contact with discharges a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility. Do not fit any valves or taps to the discharge pipework. Ensure the pipework has at least 1:200 fall continuously from the tundish to the discharge point. The discharge pipe from the pressure relief valve of the Vaillant boiler may be teed-into the discharge pipework from the uniSTOR downstream of the tundish in the horizontal pipework.
5.1.4.1 High Level Termination
Providing that the point of termination is such that persons in or around the building will not be endangered should discharge take place, the method of termination shown in fig. 3 is satisfactory. Examples of points to consider when deciding whether a location for the high level discharge is suitable are: – The possibility, taking into account wind effect, that
someone may be in the path of the water being discharged and if so, whether the temperature of the discharge water will have been sufficiently reduced to not be dangerous. Thermal conductivity of the structure’s surface, climatic conditions and location and orientation of the discharge pipe may or may not have an effect on reducing the temperature of the
discharge water. – The location of windows and similar openings. – The likelihood of a pram being left beneath the point
of discharge. – The ability of the structures surface to withstand near
boiling water. – The possibility of ice formation if water is discharged
onto pedestrian walkways.
metal discharge pipe from tundish with continuous fall.
Fig. 2 Typical discharge pipe arrangement
Under fault conditions, the discharge warning pipe can emit water at near boiling temperature. Ensure the discharge pipe terminates at a safe position where there is no risk of contact with hot water by persons in or about the building (save and visible). A suitable position for the discharge point is ideally below a fixed grating and above the water seal in a trapped gully. Downward discharges at low level, i. e. up to 100 mm above external surfaces such as car parks, hard standings, grassed areas, etc. are acceptable
fixed grating
trapped gull
Fig. 3 High level termination
tundish
300 mm minimum
discharge pipe
metal hopper head
uniSTOR GB10
5.2 Dimensions
Installation 5
1
7
2
b
3
4
h
g
5
a
6
f
c
d
e
550
600
45°
1 DHW outlet 2 Temperature and pressure relief valve 3 Immersion heater 4 Primary flow 5 Cold water mains inlet 6 Primary return 7 Additional immersion heater
(for uniSTOR 260 and 310; as accessory)
Fig. 4 (all dimensions in mm)
abcdefgh
VIH GB 125 S 938 969 421 351 281 556 728
VIH GB 155 S 1148 1179 454 384 314 589 903
VIH GB 180 S 1308 1339 454 384 314 589 1038
VIH GB 210 S 1468 1499 454 384 314 589 1118
VIH GB 260 S 1758 1789 454 384 314 589 1408 1376
VIH GB 310 S 2078 2109 454 384 314 589 1648 1376
uniSTOR GB 11
5 Installation
5.3 Functional diagrams
DHW
2
4
Fig. 5
1 Boiler 2 uniSTOR cylinder 3 2 port motorised valve (provided with the boiler) 4 Immersion heater 5 2 port motorised valve
M
3
1
AB
5
M
A Boiler flow B Boiler return
uniSTOR GB12
10
Installation 5
12
7
45
1
11
6
3
2
8
9
Fig. 6
1 Temperature and pressure relief valve 2 Expansion relief valve 3 Pressure limiting valve combined with strainer 4 Connection to expansion vessel 5 Balanced pressure cold water outlet 6 Cold water mains inlet 7 DHW outlet 8 Tundish 9 Cylinder drain point 10 Expansion vessel 11 Secondary return connection 12 Adjustable feet
uniSTOR GB 13
5 Installation
5.4 Installation procedure
Unpack the uniSTOR cylinder and check the contents
(detailed in section 4: notes to installers). Position the uniSTOR in accordance with section 5.1.1:
Siting
5.4.1 Primary pipework
To prevent the uniSTOR from overheating the 2 port motorised valve supplied with the boiler must be fitted to the primary flow to the indirect coil (see figure 5).
AB
Install the drain valve in the cold mains supply
between the uniSTOR cylinder and the cold water
control valves at the lowest point.
Install the assembled cold water control valves (fig. 8)
in the cold mains supply at a convenient position
adjacent to the uniSTOR cylinder, ensuring adequate
space exists for service access and allow for connection
of the discharge pipe from expansion relief valve.
If the discharge pipes are to be tied together the expansion valve must be within 500 mm of the temperature and pressure relief valve (fig 6).
453 1
´B´ Port ´A´ Port
Fig. 7
5.4.2 Secondary system Pipework
Connect the two cold water control valves together as
shown in fig. 8, ensuring that the orientation of the valves, when installed in the cold mains supply, allows the 15 mm outlet of the expansion relief valve to be connected to the tundish. Install the discharge pipe from the expansion relief
valve so that it has a contimous fall to outside in a safe and visible position where it will be unaffected by frost. Never cap or block the outlet of the expansion relief valve. Activate the expansion relief valve regularly to prevent
from calcification. Provide a cold water mains supply to the uniSTOR.
To ensure optimum performance from the uniSTOR, and particularly in installations where the balanced pressure cold water outlet (5, fig. 8) is to be used, the pipework provided from the building mains stop valve to the uniSTOR cylinder should be minimum 22 mm copper tube.
A 2 B
Fig. 8
A Mains Cold water inlet B Connection to cylinder 1 Secondary return connection 2 Expansion relief valve 3 Pressure limiting valve combined with strainer 4 Connection to expansion vessel 5 Balanced pressure cold water outlet
Important No isolation valve shall be installed between the assembled cold water control valves and the cylinder.
uniSTOR GB14
Installation 5
The Vaillant uniSTOR is provided with an external expansion vessel.
Connect the expansion vessel to the installed water
controls by either: i. Screwing the vessel directly into the control assem-
bly at the purpose provided connection (1, fig. 8) or,
ii. Connecting the vessel to the control assembly via
copper pipe or a suitable approved flexible connec­tion hose (4, fig. 8), ensuring that the vessel is adequately supported. Use the supplied Expansion Vessel Mounting Bracket for wall installation.
Connect the balanced pressure cold water supply (if
required) to the cold water control pack (see fig. 8).
Note: In areas where the mains water pressure is high (4 bar or above) the cold water supply to a bath or shower mixer valve can be taken from the balanced pressure cold water outlet (5, fig. 8) of the cold water controls. This will ensure that both hot and cold supplies to the mixer valve are at approximately the same pressure. The cold water supply for all other terminal fittings should be teed into the cold water supply pipework to the uniSTOR upstream of the cold water controls.
Connect the DHW outlet pipework to the 22 mm
domestic hot water outlet on the uniSTOR. Continue with 22 mm size pipe to the first tee fitting after which 15 mm pipework should be adequate. If the pipe runs are of excessive length or there are several terminal fittings supplied, extend the length of pipework in 22 mm. Connect the secondary return if required as shown in
4.2: Secondary Return.
5.4.4 Drain Valve
The drain valve supplied with the uniSTOR has to be fitted in the cold water mains supply between the uniSTOR cylinder and the cold water control valves as low as possible (see fig. 6) We recommand to fit a hose pipe in the outlet of the drain valve approximately 1 meter below the bottom of the cylinder (this can be achieved by connecting a suction hose to the outlet of the drain valve).
Flow rates from uniSTOR, hot 60 °C.
40
30
20
10
flow out (litres/min) of the system
0
40
30
10
flow available (litres/min) at entry to system
Mixed water @ 40 °C, mixed from 60 % hot water @ 60 °C and 40 % cold water @ 10 °C
20
Flow rates from uniSTOR, hot cold mixed.
30
8 bar* 4 bar*
3 bar* 2 bar*
1 bar*
40
8 bar* 4 bar* 3 bar* 2 bar*
1 bar*
5.4.3 Safety valve discharge pipework
Connect the temperature/pressure relief and
expansion relief valves to the tundish using 15 mm pipe and install the discharge pipework from the tundish in accordance with section 5.1.4: Discharge Pipework.
uniSTOR GB 15
20
10
flow out (litres/min) of the system
0
Notes:
1) flow rates shown apply to situations where the supply is capable of supplying an adequate dynamic pressure.
3) where static water pressures are less than 1 bar, consult Vaillant Ltd.
* static supply pressure of incoming water supply.
Fig. 8a
10
flow available (litres/min) at entry to system
20
30
40
5 Installation
5.4.5 Electrical Connections and Controls
All electrical connections conform to BS 7671 and 6759-1. The position of the discharge pipes (tundish), drain valves and motorised valves etc. shall be positioned away from any electrical components.
Warning: The cylinder must be earthed.
5.4.5.1 Immersion Heater
The uniSTOR VIH 125 - 310 cylinders are equipped with a factory fitted immersion heater. All internal wiring is factory mounted.
Warning: The immersion heater must be earthed.
Install a separate electrical supply to the immersion heater in accordance with the current IEE wiring regulations (BS 7671). The immersion heater must be wired in 3 x 2.5 mm pole isolating switch. The circuit must be protected by a 13 amp fuse. The connection details for the immersion heater are shown in fig. 9.
2
heat-resisting cable from a double
230 V AC 3 kW
Important: The immersion heater incorporates an energy cut-off device and must not under any circumstances be replaced by a standard immersion heater.
Only a correct genuine Vaillant spare part is permitted. All uniSTOR cylinders with a volume of 260 l or 310 l are provided with an additional boss to fit a second immersiom heater. The immersion heater can be ordered as accessory (No. 0020006765)
5.4.5.2 Electrical Connections to Cylinder
Controls
To Wiring box:
1 7 2 10 3
L
N
a
b
3
2
1
2
1
1
2
3
Fig. 9 Immersion heater electrical connections
a Cylinder Controls 1 Thermostat (adjustable) b Immersion heater 2 Thermal cut out (with Reset button)
L
N
a
3 Sensor
b
3
2
1
2
1
Fig. 10 Electrical Connections to Cylinder Controls
Note: In case you do not wire the immersion heater then connect the earth wire to the terminal marked E on the immersion heater connector block.
Warning: The uniSTOR cylinder must be eartherd.
The Vaillant uniSTOR and accompanying Vaillant boiler may be controlled using various programmers and room thermostats, details of which are given in section: Control Options. The uniSTOR cylinder has a prefitted cylinder thermal cut out and thermostat.
uniSTOR GB16
Installation 5
All internal wiring is factory mounted. The thermostat which controls the DHW temperature (1, fig. 10) is adjustable between 20 and 65 °C. The built in safety thermal cut out operates at 90 °C. Should the thermal cut out be brought into operation, the motorized 2 port valve will be operated and shut the
Connect the 2 port valve flying lead to the terminals
of the wiring box. Connect the terminals of the programmer and room
thermostat to the terminals of the wiring box. Connect a 3 amp fused mains supply to the terminals
of the wiring box. primary flow to the cylinder. Press the reset button (2, fig. 10) to reset thermal cut out and motorised valve.
Note:
All wiring must be carried out in accordance with Important: Before resetting the thermal cutout or changing
BS 7671: Requirements for electrical installations
(IEE Wiring Regulations, 16th edition). the temperatur setting of the thermostat, switch off the electrical supply.
Check that the sensors from the immersion heater
and the cylinder are positioned correctly in the tubes.
Connections to wiring box
Provide a wiring box adjacent to the cylinder to make
the electrical connections. Connect the boiler terminals to the corresponding
terminals of the wiring box. Connect the uniSTOR cylinder controls to the wiring
Note:
A special accessory is offered for the electrical
connections between the uniSTOR and an
ecoEURO appliance (No. 307 215).
box as shown in figure 10.
5.4.5.3 Connection details for control systems utilising 2 x 2 port motorised valves via external wiring box
Diagram only applies to the specific controls mentioned
3 amp fused main supply
LN
E
ecoTEC
terminal strip
LN
345
Programmer for programmer connections see fig. 12
N L
CENTRAL HEATING ON
HOT WATER ON
LN
uniSTOR Cylinder
EARTH BLUE BROWN GREY ORANGE
Hot water 2 port motorised valve
Fig. 11 Connection details for control systems utilising 2 port motorised valve
LN
External wiring box
(Do not use pre-wired printed circuit board type)
NNL
7
10
231
345
345678910
L
not used
Room thermostat
ACL Drayton Digistat 2, 3, 4
ACL Drayton RTS 1, 2
Danfoss Randall RX-1
Danfoss Randall RMT 230
Danfoss Randall RET 230
Tower SS
Honeywell T6360
Horstmann HRT 1
Siemens-Landys & Staefa RAD 1
Sunvic TLX 2000 series
4EN 310
EARTH BLUE BROWN GREY ORANGE
Central heating 2 port motorised valve
NL67
5 9 6 L N E
3
N
3
3
4
2
N
3
4
2
2
3
4
2
2
4
1
1
L
2 1
L 1
1 1
1 3
CB
E
E
E E
4EN 39
Vaillant Room Thermostat VRT 30
9 6 N
L in N
L out
uniSTOR GB 17
5 Installation
Lifestyle LP241, LP 522, LP 722
Tempus 6, Tempus 7
Danfoss Randall CP 715, FP715
Note: *Earth not required
Danfoss Randall Set 2E, Set 3E
Note: *Earth not required Link L - 2 - 5
Grässlin Towerchron QE2
Honeywell ST699B, ST799A
Note: Link L - 5 - 8
Honeywell ST6200, ST6300, ST6400
Horstmann Channel Plus H21, H27
Note: *Earth not required Link L - 2 - 5
Siemens-Landis & Staefa RWB2, RWB9
1
NL
53 64
NL
E
53
NL
E
*
53
NL
E
*
53
NL
53
N3
L
3
56
NL
53
NL
E
*
53 7
NL
234
not used
1
234
not used
1
not used
1
76
1
234
not used
4
not used not used
234
1
not used
1
1
234
76
234
76
23456
not used not used
76
567
7
76
234
not used not used
8
56
6
Potterton Myson EP 2002, EP 3002, EP 6002
Note: Link L - 5
Sunvic Select 207
Fig. 12 Connection details between programmer and wiring box.
53
NL
E
53
NL
53
not used
1
not used
1
234
not used
76
234
76
76
5
uniSTOR GB18
5.4.5.4 Connection details for connection to any UK standard boiler
Installation 5
3 Amp Fused
LN
External wiring box
(Do not use pre-wired printed circuit board type)
1
N
EBLBRGR OR
Central Heating 2 Port Motorised Valve
Boiler TerminalMain Supply
LN
LN
2
345678910
L
69EN
L in L outN E
Room Thermostat
SL
not used
E4101/N 2/LE 49N L
EBLBRGR OR
Hot Water 2 Port Motorised Valve
uniSTOR VIH GB ...
2 Channel Programmer
HWONCH
LN
ENL4EE 1/N 2/L
4 NE
LN
Pump
Cylinder Stat
ON
76
7 10
123
Fig. 13 2 x 2 port valve system
Boiler Terminal Designation:
L, 1: Mains Live RS, 2: Room Thermostat FS, 3: Frost Stat N, 4: Mains Neutral E, 5: Mains Earth PE, 6: Pump Earth PN, 7: Pump Neutral PL, 8: Pump Live CE: Chassis Earth
BR Brown BL Blue GR Grey OR Orange W White
DHW Domestic Hot Water HTG Heating
Important: 1-10 must go to the corresponding number in the wiring box.
uniSTOR GB 19
6 Commissioning
6 Commissioning
6.1 Filling Secondary DHW Circuit
Note: Do not manually open the temperature and pressure relief valve or expansion relief valve for venting purposes (any foreign matter in the pipework may cause damage to the valve seats).
Ensure that the cylinder drain valve (9, fig. 6) is
closed. Open all the hot and cold water taps or other terminal
fittings. Open the mains water supply to the uniSTOR and
continue filling until water runs freely from the terminal fittings, ensuring all air pockets are purged.
• Close the terminal fittings and check the system for
leaks. Specially check the connection of the immersion heater for leaks.
The system should now be thoroughly flushed.
Open hot water taps at opposite ends of the system
and allow water to discharge for at least 5 minutes. Close the hot water taps.
6.2 Filling the Primary Circuit
Note: Do not use boiler pressure relief valve for venting purposes.
The complete primary CH system must be flushed out
with both cold and hot water. Fill and vent the central heating system as detailed in the boiler installation instructions. To assist with this operation set the manual override lever on the 2 port diverter valve (fig. 7) to the MANUAL position, and lock in this position by pushing the lever into the valve head. Completely drain the CH system, then refill and vent.
Reset the lever on the 2 port valve to the ”AUTO”
position by releasing the manual operating lever from the valve head (pull outwards). For commissioning purposes and to reduce the time for the cylinder contents to reach temperature, set the cylinder hot water thermostat knob (1, fig. 14) to setting middle position (approx. 40 °C).
heater
immersion
L
N
3
2
cylinder
control
1
Fig. 14 Electrical Connections to Cylinder Controls
Operate the boiler as in section 6.3 until both the
cylinder has reached temperature and all radiators in the system are hot. Then once again drain the complete CH system to remove residues from the pipework and refill and vent again as above. Reset the manual operating lever on the 2 port valve
to the ”AUTO” position once the system has been refilled and vented.
1
uniSTOR GB20
6 Commissioning Maintenance 7
6.3 Operating the Boiler
Ensure the boiler mains switch is turned on.
Ensure that the programmer and thermostats are
calling for heat. Check that the boiler fires and heats the cylinder
contents and the radiators according to the DHW and room thermostat settings. Carry out the commissioning and testing procedures
detailed in the installation instructions supplied with the boiler. Upon completion of the commissioning procedures,
set the DHW thermostat knob on the uniSTOR to approx. 60 °C, and set the back up immersion heater (fig. 9) thermostat to 60 °C.
6.3.1 Benchmark Cylinder Commissioning
Checklist
Complete the Benchmark Cylinder Commissioning Checklist included in the instructions.
6.4 User’s Instructions
Hand these instructions for use to the user for retention and instruct in the safe operation of the boiler and cylinder. Advise the user of the operation of the cylinder thermostat and the immersion heater thermostat, and that normally a setting of max, which gives a stored water temperature of approximately 60 °C is adequate.
7 Maintenance
The following maintenance work has to be carried out annually by the competent installer or Vaillant Service Solutions.
Inspection of pressure/temperature relief valve and
expansion relief valve. Manually operate each valve by twisting the operating cap, and check if water flows unobstructed via the tundish to the discharge point. Ensure that both valves re-seat satisfactorily. Check pressure of expansion vessel.
Turn off mains water supply and open nearest hot water tap to depressurise the secondary water system. Check the expansion vessel charge with a pressure gauge at the test point. If the pressure is below
3.0 bar, top up with suitable air pressure pump. Complete service section of Cylinder Commissioning
Checklist.
Note: In the event that parts require replacement, use only genuine spare parts supplied by Vaillant Ltd.
Note: In hard water areas the DHW temperature setting should not exceed this setting to avoid possible scale build-up.
Advise the user of the precautions necessary to prevent damage to the system and to the building if the system does not remain operative during frost conditions.
Advise the user that the immersion heater is provided as a back up means of water heating and is not intended for use at the same time that the boiler is heating the cylinder.
Finally, advise the user that for continued efficient and safe operation, the boiler and uniSTOR cylinder should be serviced at least once a year by a qualified servicing company. It is important and strongly recommended that arrangements are made for a maintenance agreement with a qualified servicing company to ensure regular servicing of the boiler and cylinder.
Please contact Group Service (0870 - 6060777) for further details.
Note: Leave installation, servicing and user instructions with the user.
uniSTOR GB 21
8 Fault finding
8 Fault finding
Note: Only genuine spare parts supplied by Vaillant Limited must be used.
Fault A:
The water from the cylinder is cold.
Does boiler operate?
YES
Is 2-port valve in correct position? (DHW position).
Vent heating coil of air (H, fig. 4).
NO
NO NO
Do external controls function?
NO
Does cylinder thermostat operate?
YESYES
YES
Check/reset Thermal cut out
Remedy fault according to boiler instructions.
Remedy fault according to controls instructions.
Replace cylinder thermostat.
Check/replace 2-port valve.
NO
Fig. 15
Is operation now OK?
YES
Fault remedied.
uniSTOR GB22
Fault B:
Fault finding 8
Water discharging from expansion relief valve.
Manually reset / seat expansion relief valve. Is discharge still occuring?
Is the discharge occuring only when the cylinder is being heated?
YES
Check pressure charge in expansion vessel
OK
Exchange expansion relief valve.
YES
NOT OK
Reset pressure in expansion vessel Does pressure hold?
YES
NO
NO
NO
Turn off boiler and
NO
immersion heater. Is discharge still occuring?
YES
Is pressure downstream
YES
of pressure limiting valve less than 3.0 bar?
NO
Is operation now OK?
Fault remedied.
Fig. 16
uniSTOR GB 23
YES
Exchange pressure limiting valve.
Exchange expansion vessel.
NO
8 Fault finding
Fault C:
Water discharging from temperature/ pressure relief valve (TPRV).
Manually reset the TPRV. Is discharge still occuring?
YES
Is discharge occuring only when the boiler is in use?
NO
Is discharge occuring only when the immersion heater is in use?
YES
NO
Replace TPRV. Replace immersion heater.
Are immersion heater thermostat and cut out faulty?
NO
YES
NO
YES
Check temperature control of boiler.
Does 2-port valve change to heating position when cylinder reaches temperature?
Check operation of cylinder thermostat and thermal cut out
NOT OK
OK
NO
NOT OK
OK
Check operation of 2-port valve.
Remedy fault according to boiler instructions.
YES
Reset thermal cut out/ Replace cylinder thermostat.
Replace
NOT
2-port valve.
OK
NOT OK
Fig. 17
Is operation now OK?
Fault remedied.
OK
NO
OK
Is discharge still occuring?
YES
Replace TRPV.
uniSTOR GB24
Fault D:
Fault finding 8
Deteriorating water pressure and flow from hot water terminal fittings.
Check incoming main water pressure.
OK
Check line strainer (in pressure limiting valve).
OK
Check pressure limiting valve.
OK
Check sytem for blockage.
OK
Symptoms still persisting?
YES
NO
Poor
Dirty
Faulty
Blocked
Inform customer to have water service checked by water undertaker.
Clean / replace strainer.
Replace faulty valve.
Replace / clear blocked components.
Check system as for discharge from temperature or expansion relief valve.
Fig. 18
uniSTOR GB 25
Fault remedied.
0020005468_02 GB 042008 • Subject to alteration • Printed in Germany
Loading...