Vaillant TURBOmax VUW 242/1 E, TURBOmax VUW 282/1 E, TURBOmax VUW 282 E Instructions For Installation And Servicing

TURBOmax VUW 242/1 E
TURBOmax VUW 282/1 E
Wall hung room sealed fan assisted
combination boilers
INSTRUCTIONS FOR INSTALLATION AND SERVICING
HEATING, CONTROLS, HOT WATER.
2
1. Introduction 3
2. Boiler Specification 4
2.1 Technical Data 4
2.2 Dimensions 5
2.3 Boiler connections 5
2.4 Function diagram 6
3. General Requirements 7
3.1 Related documents 7
3.2 Boiler location 7
3.3 Gas supply 8
3.4 Flue system 8
3.5 Air supply 10
3.6 Electricity supply 10
3.7 Guide to system requirements 10
4. Boiler installation sequence 13
4.1 General 13
4.2 Boiler delivery 13
4.3 Preparation of boiler location 14
4.4 Installing the flue system 16
4.5 Mounting the boiler 16
4.6 Connecting the flue assembly to the boiler 17
4.7 Electrical installation 19
4.8 Controls 20
5. Commissioning 22
5.1 Preliminary electrical checks 22
5.2 Gas supply 22
5.3 Water supply 22
5.4 Filling the heating system 23
5.5 Initial system flush ('cold') 23
5.6 Initial lighting 24
5.7 Gas inlet working pressure 25
5.8 Main burner pressure 25
5.9 Adjusting central heating
output (range rating) 26
5.10 Functional checks 27
5.11 Checking flame
supervision device 28
5.12 Final system flush ('hot') 28
5.13 Fitting case 28
5.14 Handing over to user 29
Page
6. Servicing 29
6.1 Initial inspection 29
6.2 Routine maintenance 30
6.3 Re-commissioning the boiler 31
7. Parts replacement 32
7.1 Initial preparation 32
7.2 Fan 34
7.3 Air pressure switch 34
7.4 Burner 35
7.5 Electrodes 35
7.6 Temperature sensor (NTC) 36
7.7 Gas valve 36
7.8 Main Heat exchanger 37
7.9 CH expansion vessel 38
7.10 Transformer 39
7.11 Overheat thermostat 39
7.12 Pump 39
7.13 Automatic air release 40
7.14 Automatic bypass 40
7.15 Diverter valve 40
7.16 Pressure and temperature gauge 41
7.17 Differential pressure switch 41
7.18 DHW microswitch 42
7.19 DHW heat exchanger 42
7.20 Circuit boards 43
8. Fault finding 44
8.1 Introduction 44
8.2 Logical fault finding procedure 44
8.3 Fault finding charts 45
9. Electrical diagrams 54
9.1 Functional flow diagram 54
9.2 Wiring diagram 55
9.3 Schematic appliance
circuit diagram 56
10. Short parts list 57
11. Supplementary LPG
information 59
Leave these instructions with the user when the installation is completed.
33
1. Introduction
Note: This boiler must be installed and serviced by a competent person in accordance with the Gas Safety (Installation and Use) Regulations
1994. In the UK 'CORGI' Registered Installers undertake the work to a safe and satisfactory standard.
The TURBOmax is a fully automatic, wall mounted, room sealed combination boiler for central heating and domestic hot water. Domestic hot water is supplied directly from the boiler, without requiring a copper cylinder, cold water tank, feed and expansion tank or associated pipework. Domestic hot water has priority over central heating.
The boiler has been designed for use with a sealed central heating system, and comes fully tested and assembled with a built-in circulating pump, bypass, expansion vessel and diverter valve.
TURBOmax boilers carry 'CE' Mark. This demonstrates that the boilers fulfill the essential requirements of the Gas Appliance Directive (90/396/EEC) and the Gas Appliance (Safety) Regulations 1992.
The 'CE' Mark also demonstrates that the boilers comply with the requirements of the Electromagnetic Compatibility Directive (Directive 89/336/EEC), the Low Voltage Directive (73/23/EEC), the Boiler Efficiency Directive (92/42/EEC) and the Boiler (Efficiency) Regulations
1993.
TURBOmax meets the requirements of Statutory Instrument ‘The Boiler (Effi­ciency) Regulations 1993 and therefore is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot-water boilers fired with liquid or gaseous fuels.
The TURBOmax range consists of models with outputs for domestic hot water of 24 and 28 kW. The boiler is easily sited on any internal wall and can be installed with either a horizontal or vertical RSF (Room Sealed Fan assisted) flue. Flue extensions and additional bends and elbows are available for increased siting flexibility. (The boiler is not suitable for external installation).
If desired an inhibitor may be used in the system. Guidance on the use of inhibitors is contained in these instructions.
Natural Gas and LPG versions of the boiler are available.
The boiler contains a domestic hot water heat exchanger. The temperature in the heat exchanger is limited by the boiler control system and it is not necessary to install a scale reducer on the cold mains inlet to the boiler. However, in exceptionally hard water areas to prevent scale formation in the property hot water system pipework, a scale reducer may be fitted.
The TURBOmax has built-in diagnostic indicator lights which illuminate in sequence giving information on the boiler status when operating and per­formance of key components to aid in commissioning and fault finding.
The data badge is fitted on the bottom of the combustion chamber.
See text of General Requirements for Installation Requirements or notes.
TURBOmax VUW 242/1 E VUW 282/1 E units
Countries of Destination GB, IE
Maximum CH heat input 29.3 34.2 kW
(100,000) (116,600) (Btu/h)
CH heat output range 9.6-24.0 11.2-28.0 kW
(32,800-81,900) (38,200-95,500) (Btu/h)
Maximum DHW heat input 29.3 34.2 kW
(100,000) (116,600) (Btu/h)
Maximum DHW heat output range 9.6-24.0 11.2-28.0 kW
(32,800-81,900) (38,200-95,500) (Btu/h) DHW flow rate @ 35 °C rise 10 11.5 l/min Mains water pressure required for max. flow rate 0.8 1.0 bar Minimum water flow rate 2.7 2.7 l/min Mains water pressure required for min flow rate 0.3 0.3 bar Maximum inlet water pressure 10 10 bar
Inlet gas working pressure required (Natural Gas) 20 20 mbar Gas supply (G20) Gross C.V. (s.t.) 37.8 37.8 MJ/m
3
Gas burner pressure max. rate 10.0 10.6 mbar Gas burner pressure ignition rate 2.0 2.0 mbar Gas rate max (DHW) 2.79 3.26 m3/h Main burner jet size 16 x 7/120 18 x 7/120 no. x size
CH flow temperature range 40-90 40-90 °C Minimum CH water flow (for 20 °C rise) 1,032 1,204 l/h Pump pressure available 0.25 0.25 bar 8l expansion vessel pre-charge pressure 0.75 0.75 bar Maximum CH system pressure 3.0 3.0 bar
Connections Heating flow / return 22 22 mm Cold water inlet 15 15 mm DHW outlet 15 15 mm Gas inlet 15 15 mm Pressure relief discharge pipework (min) 15 15 mm
Weight 47 48 kg Primary water content 0.7 0.7 litres
Electrical supply Voltage 230/50 230/50 V~/Hz 2 x internal fuses 2 2 A 1 x internal fuse 1.25 1.25 A external fuse 3 3 A Power input 130 130 W
4
2. Boiler specification
2.1 Technical data
Supplementary LPG information on page 59.
55
1021
880
95.5
480
120
max. 995*
max. 995 *
1a
1a
190
1b
2
765438
35
50
380
120
GW 547/1
fig. 1
2.3 Boiler connections
1 Compression union (flow of
heating system)
2 Service valve (flow of heating
system) 3 Domestic hot water connection 4 Compression Union (gas) 5 Gas service valve (supplied with
the boiler) 6 Cold water connection with
shut-off valve 7 Service valve (return of heating
system) 8 Compression union (return of
heating system) 9 Pressure relief valve
200
124
50
35
70
25
12 3456789
GW 546/1
fig. 2
2.2 Dimensions
(All dimensions in mm)
1a Air/flue duct to the rear 1b Air/flue duct to the side 2 Appliance bracket 3 Heating system return (22 mm) 4 Cold water connection (15 mm) 5 Gas connection (15 mm) 6 Hot water connection (15 mm) 7 Heating system flow (22 mm) 8 Pressure relief valve outlet
(3/4 in BSP)
* with standard horizontal flue
accessory.
(max. = 2965 mm with extensions)
66
1
9
2
3
4
5
6
7
8
1
9
2
3
4
5
6
7
8
υ
0
0
60
90
120
4
321
30
1
2
3 4 5
7
6
8 9
10
11
12 13
14
15
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
GW 573/2GB
fig. 3
2.4 Function diagram
1 Air duct 2 Air pressure switch 3 Combustion chamber 4 Temperature sensor (NTC) 5 Ignition electrodes 6 Modulating burner 7 Overheat thermostat 8 Fully modulating automatic gas
valve
9 DHW heat exchanger 10 Indicator lights (LEDs) 11 Maximum radiator temperature
control
12 Maximum hot water temperature
control
13 Central heating control and
lockout reset 14 Main on/off control 15 CH flow service valve 16 Gas service valve 17 Flue gas duct 18 Fan 19 High efficiency heat exchanger 20 Flame sensing electrode 21 Differential pressure switch 22 Expansion vessel charging valve 23 Expansion vessel 24 Automatic air vent 25 Circulating pump 26 Diverter valve 27 Water switch (DHW) 28 Water section 29 Temperature and Pressure gauge 30 Automatic bypass valve 31 Pressure relief valve 32 CH return service valve 33 Cold water shut off valve
7
3. General requirements
3.1 Related documents
The installation of the boiler must be in accordance with the relevant requirements of Gas Safety (Installation and Use) Regulations 1994, Health and Safety Document No. 635 (The Electricity at Work Regulations 1989), BS7671 (IEE Wiring Regulations) and the byelaws of the local Water Undertaking. It should also be in accordance with the relevant requirements of the Local Authority, Building Regulations, Building Standards (Scotland) Regulations and the relevant recommendations of the following British Standards:-
BS 5440: Flues and ventilation of gas fired boilers not exceeding 60 kW:
- Part 1: Flues
- Part 2: Ventilation
BS 5449: Specification for forced circulation hot water for domestic premises.
BS 5546: Specification for gas hot water supplies for domestic premises.
BS 6700: Services supplying water for domestic use within buildings and their curtilages.
BS 6798: Specification for installation of gas fired boilers not exceeding 60 kW input.
BS 6891: Specification for installation of low pressure gas pipework up to 28 mm (R1) in domestic premises (2nd family gas).
BS 7593: Treatment of water in domestic hot water central heating systems.
BRITISH GAS PUBLICATION DM2: Guide for Installation in Timber Framed Housing
Important
The appliance must be installed and serviced by a competent person as stated in the Gas Safety (Installation and Use) Regulations 1994
3.2 Boiler location
The location chosen for the boiler must permit the provision of a satisfactory flue termination. The location must also provide adequate space for servicing and air circulation around the boiler. The boiler may be installed in any room, although particular attention is drawn to the requirements of BS7671 (I.E.E. Regulations) and, in Scotland, the electrical provisions of the Building Standards (Scotland) Regulations,inrespect of the installation of a boiler in a room containing a bath or shower.
(Note: Where a room sealed boiler is installed in a room containing a bath or shower, any electrical switch or boiler control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower).
Where the installation of the boiler will be in an unusual location, special procedures may be necessary and BS 5546 and BS 6798 give detailed guidance on this aspect.
The boiler must be mounted on a flat, vertical wall, which must be sufficiently robust to take the weight of the boiler. The boiler may be installed on a combustible wall, subject to the requirements of the Local Authorities and Building Regulations.
A compartment used to enclose the boiler must be designed and constructed specifically for this purpose. (An existing cupboard or compartment may be used provided that it is modified for the purpose). Details of essential features of cupboard/compartment design including airing cupboard installations are given in BS 6798.
If the boiler is to be fitted in a timber framed building, it should be fitted in accordancewithBritish Gas Publication DM2 'Guide for Gas Installations in Timber Framed Housing'.
8
3.3 Gas supply
The gas supplier should ensure the availability of an adequate supply of gas.
A gas meter may only be connected to the service pipe by the supplier of gas or their contractor.
An existing meter should be checked to ensure that it is capable of passing the rate of gas supply required.
Installation pipes should be fitted in accordance with BS 6891.
Pipework from the meter to the boiler must be of an adequate size. Do not use pipes of a smaller size than the boiler gas connection (15 mm).
The complete installation must be tested for soundness and purged as described in BS 6891.
3.4 Flue system
The standard horizontal flue system (Art. No. 300 807) is suitable for installations up to 995 mm measured from the centre of the boiler flue outlet to the outside face of the wall (A, fig.
4). Flue extensions (Art. No. 300 802) are available to extend this length up to 2965 mm. Both 90° elbows (Art. No. 300 808) and 45° bends (Art. No. 300 809) are also available to increase siting flexibility.
A vertical flue system is also available (Art. No. 300 800).
TURBOmax boilers may also be used in SE- duct applications (SE- duct flue system available Art. No. 300810)
Refer to the flue installation instructions for full details.
A
max
= 2965 mm
GW 579/2
fig. 4
3.4.1 Flue Termination
1. The terminal must be positioned such that the combustion products can disperse freely at all times.
2. In certain weather conditions a plume of water vapour may be visible from the flue terminal. Positions where this could be a nuisance should be avoided.
3. If the terminal is fitted less than 2m above a balcony, above ground or above a flat roof to which people have access, then a suitable guard must be provided and fitted (available from Tower Flue Components, Tonbridge, TN9 1TB: reference TFC type K3).
Table 1:
Terminal position for fan-assisted flue (minimum distance - see fig. 5)
A- Directlybelow an openable mm
window or other opening (e.g. air brick) 300
B- Below gutters, soil pipes
or drain pipes 25 C- Below eaves 25 D- Below balconies 25
(below car port roof 200) E- From vertical drain pipes
and soil pipes 25 F- From internal or external
corners 25 G-Above ground or balcony
level 300 H- From a surface facing a
terminal 600 I- From a terminal facing a
terminal 1200 J- From an opening in a
car port (e.g. door, window)
into a dwelling 1200 K- Vertically from a terminal
on the same wall 1500 L- Horizontally from a
terminal on the same wall 300 M-Distance from adjacent
wall for Vertical Flue 500
9
A
BCD
A G
H, I
F
J
B
F
M
L
L
K
K
G
G
F
F
E
fig. 5
GW 595/1
Where a terminal is fitted less than 1m below a plastic gutter or less than
0.5 m below painted eaves or any other painted surface then a suitable shield at least 1m long should be fitted to protect the surface.
Note: Vertical flues mustnot terminate within 600 mm of an openable window, air vent or any other ventilation opening.
10
3.5 Air supply
Detailed recommendations for air supply are given in BS 5440: Part 2.
It is not necessary to have an air vent in the room or internal space in which the boiler is installed.
3.5.1 Cupboard or compartment air supply
TURBOmax Room Sealed Combination Boilers are very high efficiency appliances. As a consequence the heat loss from the appliance casing during operation is very low. For cupboard and compartment installations it is therefore not necessary to provide any high or low level permanent air vents for cooling purposes.
3.6 Electricity supply
A 230 V~ 50Hz single phase electricity supply fused to 3 amps must be provided in accordance with the latest edition of BS7671 (I.E.E. Wiring Regulations) and any other local regulations that may apply.
THIS APPLIANCE MUST BE EARTHED. The method of connection to the mains electricity supply must provide a means of completely isolating the boiler and its ancillary controls. Isolation is preferably by the use of a fused three pin plug and unswitched shuttered socket outlet, both complying with the requirements of BS 1363. Alternatively, a 3 Amp fused double-pole switch with a 3mm contact separation on both poles may be used.
3.7 Guide to system requirements
3.7.1 Water circulation system
Detailed recommendations for the water circulation system are given in BS 6798 and BS 5449: Part 1 (for small bore and micro bore central heating systems).
Pipework not forming part of the useful heating surface should be insulated to help prevent heat loss and possible freezing, particularly where pipes are run through roof spaces and ventilated underfloor spaces.
Draining taps must be located in accessible positions which permit the draining of the whole system including the boiler and the hot water system. Draining taps should be at least 1/2 in. BSP nominal size and be in accordance with BS 2879.
The boiler is suitable for use with minibore or microbore systems. Copper tubing to BS 2871: Part 1 should be used for water carrying pipework. All capillary joints in the DHW pipework must be made with lead free solder.
Particularly where a new boiler is to be fitted to an existing system, it is good practice that the system is thoroughly cleansed. This cleasing should take place prior to the fitting of the new boiler and be in accordance with BS 7593.
For advice on the application of system cleansers contact Sentinel, Grace Dearborn Ltd, Widnes, Cheshire, WA8 8UD. Tel: 0151 4951861.
11
Heating circuit return
Double check valve assembly
Hose unions
Temporary Hose
Test valve
Stop valve
Mains water supply
fig. 6
GW 400/1
3.7.2 Filling and make up
The system should be filled with water via a separate filling point fitted at a convenient position on the heating circuit. Where local Water Authority Regulation allows, a temporary connection to the mains may be used (fig. 6). The connection must be removed when filling is completed. Where local Water Authority Regulation does not allow temporary connection, a sealed system filler pump with break tank must be used. The heating system will not be filled automatically from the domestic hot water side.
(Alternative methods of filling sealed systems are given in BS 5449).
3.7.3 Pressure relief valve
A pressure relief valve is provided ready assembled within the boiler (5, fig. 7). This safety device is required on all sealed C.H. systems and is pre-set at 3 bar and provided with a3/4 in. BSP connection for a discharge pipe, which must be of no less than 15 mm diameter.
3.7.4 Pressure and temperature gauge
This is factory fitted to the boiler and indicates the primary circuit pressure to facilitate filling and testing, as well as showing the temperature of the central heating system water.
11
8
1
4
10
7
9
5
6
2
3
fig. 7
GW 609/1
12
Safety valve setting (bar) 3.0
Initial system pressure (bar) 1.0 1.5
Total water content of system VESSEL VOLUME (L)
litres
25 2.7 3.9
50 5.4 7.8 100 10.9 15.6 125 13.6 19.5 150 16.3 23.4 175 19.1 27.3 200 21.8 31.2 225 24.5 35.1 250 27.2 39.0 275 30.0 42.9 300 32.7 46.8 325 35.7 50.7 350 38.1 54.6 375 40.9 58.5 400 43.6 62.4 425 46.3 66.3 450 49.0 70.2 475 51.8 74.1 500 54.5 78.0
For system volumes other than those given above, multiply
0.109 0.156
the system volume by the factor across
13,3 400
ft mbar
10 300
6,7 200
3,3 100
0
0 200 400 600 800 1000 1200 1400 1600 l/h
Q
fig. 8
GW 402/2
3.7.5 Expansion vessel
An expansion vessel is incorporated into the boiler suitable for a sealed heating system with a maximum water content of 100 litres.
If the nominal capacity of the built in expansion vessel is not sufficient for the heating system (for instance in case of modernisation of old open systems) an additional expansion vessel can be installed external to the boiler. It should be fitted in the return pipe as close as possible to the boiler in accordance with BS 5449: Part 1.
Guidance on the sizing of an additional expansion vessel is given in Table 2.
3.7.6 Circulating pump
The circulating pump is included in the boiler. The pump head available for the heating system is shown in fig. 8.
3.7.7 System by-pass
An automatic system by-pass is included within the boiler. The boiler is suitable for use in systems with thermostatic radiator valves and no additional by-pass is required.
3.7.8 Venting
The boiler is fitted with an automatic air vent. Additional provision should be made to enable the heating system to be vented during filling and commissioning either by automatic air vents or manually.
3.7.9 DHW expansion vessel accessory
A DHW expansion vessel kit (Art. No.
8070) is available as an optional
accessory from Vaillant Ltd. This expansion vessel kit should be fitted to the boiler whenever either a stop valve of the loose jumper type or a non return valve are present in the cold water mains supply to the boiler (fig. 9).
Table 2: Sizing of Additional Expansion Vessel
D.H.W. expansion vessel fitted to the boiler
Non return valve
Stop valve
Mains water supply
fig. 9
GW 494/1
4. Boiler installation sequence
4.1 General
The boiler should be mounted on a flat and vertical area of wall of sufficient area for the boiler plus the required minimum clearances for installation and servicing (fig. 10). These are shown on the installation template supplied with the boiler and are:
5 mm either side of the boiler 100 mm below the boiler* 165 mm on top of the boiler 500 mm in front of the boiler **
* 150 mm where optional pre-
installation connecting group (Art. no. 8015) is used.
** This clearance is only required to
enable easier access to the boiler for servicing and may be provided by an openable door, etc.
Note: If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with British Gas publication reference DM2 'Guide for gas installations in timber framed housing.'
4.2 Boiler delivery
The TURBOmax is delivered in two packs:
a. the carton containing the boiler b. separately boxed flue accessory,
either:
1m horizontal flue accessory (Art. No. 300 807); or
vertical flue accessory (Art. No. 300 800)
13
5mm 5mm
165mm
*100mm
fig. 10
GW 403/2
Standard Accessories Art. No.
1. Air/flue duct and terminal accessory 300 807
Optional Accessories Art. No.
1. Vertical air / flue duct (including terminal) 300 800
2. Pitched roof adjustable roof tile (for use with vertical air/flue duct) 9076
3. Flat roof penetration collar (for use with vertical air/flue duct) 9056
4. 1 m air /flue duct extension 300 802
5. 2 m air / flue duct exension 300 803
6. Additional 90° elbow for air / flue duct 300 808
7. Additional 45° bends (pair) for air / flue duct 300 809
8. Additional air / flue duct joint clamps (pair) 300 806
9. Se- duct flue kit 300 810
10. Internal flue fixing kit 8098
11. Pre - installation connecting group (includes 300 813) 8015
12. Vaillant boiler replacement connection accessory 300 813
13. Pipe cover accessory 8099
14. Plug in 24 hour central heating timeclock 300 820
15. Plug in 7 day central heating timeclock 300 821
14
4.2.1 Installation accessories
Table 3 lists the standard and optional accessories which are available for the TURBOmax combination boilers.
4.2.2 Unpack the boiler (fig. 11)
Open the boiler carton and remove: a. protective cardboard sheet
b. top and bottom decorative panels c. polystyrene packaging
Note: Care should be taken not to scratch the white surface of the boiler casing.
Packed in the boiler carton are the following:
boiler installation template
boiler hanging bracket
gas service valve
fixing screws and wallplugs
installation and user instructions
flue restrictor
domestic hot and cold water connections and straddle bracket
4.3 Preparation of boiler location
4.3.1 Select position of boiler.
Refer to Section 3.2 'Boiler Location' for information regarding siting the boiler. In general the boiler must be positioned such that:
there is adequate space around the boiler for service and maintenance
the boiler can be correctly flued, i.e. the flue terminal position is sited in accordance with Section 3.4.1 and the air / flue duct can be installed in accordance with the flue installation instructions supplied.
all necessary pipework can be connected, including the pressure relief valve discharge pipe.
fig. 11
GW 601/1
Table 3: Installation Accessories
15
4.3.2 Using the boiler template (fig. 12)
4.3.2.1 Once a suitable location has
been chosen, fix the paper installation template on the wall ensuring that the centerline of the template is vertical using a spirit level or plumb line.
The template shows the positions of the fixing holes for the boiler hanging bracket (2) and the optional pre-installation connection group (3). The template also shows the position of the flue exit hole, for use where the air flue duct is to be installed directly to the rear of the boiler, e.g. where the boiler is installed on an outside wall and the flue terminates directly behind.
4.3.2.2 A Pre - installation connection
group (Art. No. 8015) is available as an optional accessory. It is used to allow the installation of the central heating and domestic hot water pipework without the need to have the boiler in position. Where an old existing Vaillant boiler is to be replaced, the boiler replacement accessory (Art. No. 300 813) can be used to allow easy connection on the new boiler to the existing connecting group. Refer to the instructions supplied separately with these accessories.
4.3.2.3 Mark on the wall the positions
of the hanging bracket fixing holes (2). Drill two holes Ø10 mm for the hanging bracket. (Note: Use the alternative fixing holes where necessary).
4.3.2.4 Rear exit flue.
Mark the position of the centre of the flue duct and its circumference, e.g. by drilling through the template (1, fig. 12).
4.3.2.5 Other flue options.
Refer to the installation instructions supplied with the flue accessory for detailed instructions on other flue options such as vertical RSF flues, flue runs to the side of the boiler and the use of additional flue elbows and bends etc.
4.3.2.6 Remove the template from the
wall and plug the drilled holes using the wallplugs supplied.
1
2
3
fig. 12
GW 426/1
4.3.3 Fitting the boiler hanging bracket.
Secure the hanging bracket to the wall using the screws supplied. (If the condition of the wall is poor it may be necessary to use additional or alternative fixings to ensure adequate support).
NOTE: If the boiler is to be fitted in a timber framed building ensure that the brackets are secured to a substantial part of the timber frame capable of taking the weight of the boiler.
4.4 Installing the flue system
At this stage install the flue system (refer to separate installation instructions supplied).
4.5 Mounting the boiler
4.5.1 Preparation
Remove the boiler from the carton. Lay the boiler on the floor and
remove the white boiler bottom cover by removing two screws (1, fig. 51) and slackening two screws (2, fig.
51). Do not remove boiler side panels. Remove the two plastic sea­ling caps from the domestic water connections.
Fit the pre-assembled cold water inlet and hot water outlet pipes with straddle bracket (1,2,3, fig. 15) to water connections on boiler (4, fig.
15) using washers provided.
4.5.2 Fitting the boiler (fig. 13)
Lift the boiler up to the wall so that it is slightly above the hanging bracket.
Note: Lift the boiler from under the front edge of the side panels. Do not lift the boiler by the control box. Do not attempt to lift the boiler without the side panels or side casing fitted.
Lower the boiler slowly onto the hanging bracket so that the cross member at the top rear of the boiler fully engages into the hanging bracket.
4.5.3 Pipework connections (fig. 14)
Figure 14 shows the central heating, domestic hot water, mains cold water, gas and pressure relief valve connections.
4.5.3.1 Central heating flow and return
Before connecting the heating circuit to the appliance, all pipework and radiators must be thoroughly flushed to remove any installation debris. Connect the flow and return pipes to the central heating service valves (8) and (9) on the appliance using the 22 mm compression connections.
4.5.3.1.1 Top pipework connection
If it is desired to run heating and water pipework to above the boiler, the purpose provided voids in the left and right sides of the boiler casing may be used (see fig. 16).
Note: To allow fitting of the bottom boiler cover, the left hand tab (2, fig.
16) should be folded upwards where pipes are fitted in the left hand void.
Where pipes are installed in these voids, a method of disconnection e.g. a compression connector (1, fig. 16) must be provided to allow easy removal of the boiler from the wall, if required.
4.5.3.2 Cold mains water inlet and hot water outlet (fig. 14)
Flush out all foreign matter from the mains supply pipe before connecting to the boiler.
Connect the mains water supply (3) and hot water outlet pipes (4) to the 15 mm compression connections.
Note: The boiler has a maximum domestic water working pressure of 10 bar. If the cold mains supply pressure exceeds 10 bar, a pressure reducing valve must be fitted to the cold water inlet.
4.5.3.3 Pressure relief valve discharge
The appliance contains the pressure relief valve required for a sealed system (5). Connect a discharge pipe not less than 15 mm diameter to the outlet of thisvalve.
This discharge pipework should be as short as possible and installed with a continuous fall away from the boiler. The pipe should terminate in a position which ensures that any discharge of water or steam from the valve cannot create a hazard to persons in or about the premises, or cause damage to any electrical components or external wiring, and the point of discharge should be clearly visible. The discharge must not terminate above a window, an entrance or any type of public access. The installer must consider that the pipe could discharge boiling water.
16
fig. 13
GW 608/1GB
11
8
1
4
10
7
9
5
6
2
3
fig. 14
GW 609/1
1
3
2
4
fig. 15
GW 706/1
2
1
fig. 16
GW 1001/1
4.5.3.4 Gas supply The boiler is supplied with a 20 x 15
mm gas service valve (10, fig. 14). Fit the 20 mm compression fitting to the boiler gas inlet (11, fig. 14) and tighten. Install a gas supply pipe not less than 15 mm diameter and connect to thegas service valve. (Ensure the gas supply pipework is adequately sized such that a 20 mbar - (8" w.g.) ­gas pressure is available at the boiler inlet at full flow rate). Tighten all union connections.
4.6 Connecting the flue assembly to the boiler
Note : A flue restrictor ring is sup­plied packed with the users and installation instructions. The restrictor should be used under the following circumstances : -
Horizontal flues
Where a horizontal flue less than 1 m
in length is used.
(DO NOT fit the restrictor where the
horizontal flue is more than 1 m in length).
Vertical flues
Where a vertical flue less than 1 m (e.g. 1 m between the top of the boiler and the bottom of the vertical air / flue duct assemly) is used
(DO NOT fit the restrictor where the vertical flue is more than 1 m in length).
4.6.1 Horizontal Flue
Remove two screws (1, fig. 18) and take off one half ring (2, fig. 18). If necessary, fit the flue restrictor ring (Note : It will be necessary to remove both half rings if the flue restrictor ring is to be fitted. The flue restrictor ring should be placed on top of flue outlet directly below the two half rings see fig. 18a. One half ring should be replaced immediately).
Place a 63 mm diameter x 35 mm wide flue duct clamp (4, fig. 19) loosely over the flue duct (1, fig. 19). Place the 63 mm diameter x 25 mm wide flue duct clamp (5, fig. 19) over the flue gas connection on the boiler.
17
3
2
1
fig. 18a
GW 705/1
12
fig. 18
GW 592/1
54123
fig. 19
GW 593/1
3
4
5
6
1
2
fig. 17
GW 823/1
Loosen screws on the 95 mm diameter x 55 mm wide clamp (6, fig. 21) and push over the air duct. Remove screws and sealing washer on the 95 mm diameter x 25 mm wide clamp (3, fig. 21) and push onto the flue elbow on the side to be connected to the appliance. Ensure the clamp is clear of the end of the elbow. Push the flue elbow into the clamp (2, fig. 20) connected to the appliance flue gas duct and tighten the securing screws lightly. Ensure that the elbow and air/flue duct line up and are closely butted together. Pull the clamp (4, fig. 20) over the joint between the flue gas duct and flue elbow. Ensure that the air/flue duct and terminal are correctly positioned. Tighten the securing screws on both clamps.
Note : Excessive tightening of these screws is not necessary. Ensure that the air / flue duct and terminal assembly is not displaced though the wall. Check that the air duct of the terminal still projects by 90 mm through the wall.
Refit the half ring 2, fig. 21. Pull the 95 mm diameter x 25 mm wide clamp (3, fig. 21) over the joint between the flue elbow and half rings. Refit the screws and sealing washer and tighten lightly. Pull the 95 mm diameter x 55 mm wide clamp (6, fig. 21) over the joint between the flue elbow and air/flue duct. Tighten the securing screws on both clamps. Drill two holes, 3 mm diameter through both air duct clamps into the air ducts at the most convenient positions (5, fig. 21). Take care not to penetrate the inner flue duct. Screw the clamps to the air ducts using the self tapping screws provided.
4.6.2 Vertical Flue
Remove the two half rings (2, fig. 18) and, if necessary, fit the flue restrictor ring. (Note: It will be necessary to remove both half rings if the flue restrictor ring is to be fitted. The flue restrictor ring should be placed on top of flue outlet directly below the two half rings (see fig. 18A). One half ring should be replaced immediately). Fit the 63 mm diameter x 68 mm wide flue duct sleeve (2, fig. 22) over the flue gas duct of the air/flue duct assembly.
Loosen the screws of the 95 mm diameter x 55 mm wide clamp (1, fig.
22) and push over the air duct of the air/flue duct assembly.
Lower the flue assembly until a gap of about 25 mm exists between the air duct of the air/flue duct and terminal assembly and the half rings on the appliance. The two ducts must not butt together.
Pull the sleeve (2, fig. 22) down over the flue connection of the appliance against the stop. Align the holes in the sleeve and boiler flue gas connector and secure with a self tapping screw (1, fig.23).
Note : The sleeve must not be screwed to the bottom of the flue gas duct of the air/flue duct assembly. This duct must be able to slide in order to absorb small movements of the roof structure.
Refit the two half rings. Pull the 95 mm diameter x 55 mm wide clamp down over the joint between the air/flue duct assembly and the half rings. Tigh­ten the clamp screws (1, fig.24).
18
123
4
567
fig. 21
2341
fig. 20
GW 616/1
GW 594/1
3
1
2
fig. 22
GW 558/1
1
232
fig. 24
GW 602/1
12
fig. 23
GW 560/1
Loading...
+ 42 hidden pages