Vaillant TURBOmax VUW 242 E, TURBOmax VUW 282 E Instructions For Installation And Servicing

Supplied By www.heating spares.co Tel. 0161 620 6677
INSTRUCTIONS FOR INSTALLATION AND SERVICING
TURBOmax VUW 242 E
G.C. No 47-044-25
TURBOmax VUW 282 E
G.C. No 47-044-26
Wall hung room sealed fan assisted
combination boilers
HEATING, CONTROLS, HOT WATER.
Supplied By www.heating spares.co Tel. 0161 620 6677
Page
1. Introduction 3
2. Boiler Specification 4
2.1 Technical Data 4
2.2 Dimensions 5
2.3 Boiler connections 5
2.4 Function diagram 6
3. General Requirements 7
3.1 Related documents 7
3.2 Boiler location 7
3.3 Gas supply 8
3.4 Flue system 8
3.5 Air supply 10
3.6 Electricity supply 10
3.7 Guide to system requirements 10
4. Boiler installation sequence 13
4.1 General 13
4.2 Boiler delivery 13
4.3 Preparation of boiler location 14
4.4 Installing the flue system 16
4.5 Mounting the boiler 16
4.6 Connecting the flue assembly to the boiler 17
4.7 Electrical installation 19
4.8 Controls 20
Page
6. Servicing 29
6.1 Initial inspection 29
6.2 Routine maintenance 30
6.3 Re-commissioning the boiler 31
7. Parts replacement 32
7.1 Initial preparation 32
7.2 Fan 34
7.3 Air pressure switch 34
7.4 Burner 35
7.5 Electrodes 35
7.6 Temperature sensor (NTC) 36
7.7 Gas valve 36
7.8 Main Heat exchanger 37
7.9 CH expansion vessel 38
7.10 Transformer 39
7.11 Overheat thermostat 39
7.12 Pump 39
7.13 Automatic air release 40
7.14 Automatic bypass 40
7.15 Diverter valve 40
7.16 Pressure and temperature gauge 41
7.17 Differential pressure switch 41
7.18 DHW microswitch 42
7.19 DHW heat exchanger 42
7.20 Circuit boards 43
5. Commissioning 22
5.1 Preliminary electrical checks 22
5.2 Gas supply 22
5.3 Water supply 22
5.4 Filling the heating system 23
5.5 Initial system flush ('cold') 23
5.6 Initial lighting 24
5.7 Gas inlet working pressure 25
5.8 Main burner pressure 25
5.9 Adjusting central heating output (range rating) 26
5.10 Functional checks 27
5.11 Checking flame supervision device 28
5.12 Final system flush ('hot') 28
5.13 Fitting case 28
5.14 Handing over to user 29
8. Fault finding 44
8.1 Introduction 44
8.2 Logical fault finding procedure 44
8.3 Fault finding charts 45
9. Electrical diagrams 54
9.1 Functional flow diagram 54
9.2 Wiring diagram 55
9.3 Schematic appliance circuit diagram 56
10. Short parts list 57
11. Supplementary LPG information 59
Leave these instructions with the user when the installation is completed.
Supplied By www.heating spares.co Tel. 0161 620 6677
1. Introduction
Note: This boiler must be installed and serviced by a competent person in accordance with the Gas Safety (Installation and Use) Regulations
1994. In the UK 'CORGI' Registered Installers undertake the work to a safe and satisfactory standard.
The TURBOmax is a fully automatic, wall mounted, room sealed combination boiler for central heating and domestic hot water. Domestic hot water is supplied directly from the boiler, without requiring a copper cylinder, cold water tank, feed and expansion tank or associated pipework. Domestic hot water has priority over central heating.
The boiler has been designed for use with a sealed central heating system, and comes fully tested and assembled with a built-in circulating pump, bypass, expansion vessel and diverter valve.
The TURBOmax carries the 'CE' Mark. This demonstrates that the boiler fulfils the essential requirements of the Gas Appliance Directive (Directive 90/396/EEC) and the Gas Appliances (Safety) Regulations 1992.
The CE Mark also demonstrates that the appliance complies with the requirements of the Electromagnetic Compatibility Directive (Directive 89/336/EEC) and the Low Voltage Directive (Directive 73/23/EEC).
The TURBOmax range consists of models with outputs for domestic hot water of 24 and 28 kW. The boiler is easily sited on any internal wall and can be installed with either a horizontal or vertical RSF (Room Sealed Fan assisted) flue. Flue extensions and additional bends and elbows are available for increased siting flexibility. (The boiler is not suitable for external installation).
If desired an inhibitor may be used in the system. Guidance on the use of inhibitors is contained in these instructions.
Natural Gas and LPG versions of the boiler are available.
The boiler contains a domestic hot water heat exchanger. The temperature in the heat exchanger is limited by the boiler control system and it is not necessary to install a scale reducer on the cold mains inlet to the boiler. However, in exceptionally hard water areas to prevent scale formation in the property hot water system pipework, a scale reducer may be fitted.
The TURBOmax has built-in diagnostic indicator lights which illuminate in sequence, indicating the operational status of the boiler. This feature provides key information to aid commissioning and fault finding.
The data badge is fitted on the bottom of the combustion chamber.
See text of General Requirements for Installation Requirements or notes.
Supplied By www.heating spares.co Tel. 0161 620 6677
2. Boiler specification
2.1 Technical data
TURBOmax VUW 242 E VUW 282 E units
Maximum CH heat input 29.3 34.2 kW
(100,000) (116,600) (Btu/h)
CH heat output range 9.6-24.0 11.2-28.0 kW
(32,800-81,900) (38,200-95,500) (Btu/h)
Maximum DHW heat input 29.3 34.2 kW
(100,000) (116,600) (Btu/h)
Maximum DHW heat output range 9.6-24.0 11.2-28.0 kW
(32,800-81,900) (38,200-95,500) (Btu/h) DHW flow rate @ 35 °C rise 10 11.5 l/min Mains water pressure required for max. flow rate 0.8 1.0 bar Minimum water flow rate 2.7 2.7 l/min Mains water pressure required for min flow rate 0.3 0.3 bar Maximum inlet water pressure 10 10 bar
Inlet gas working pressure required (Natural Gas) 20 20 mbar Gas supply (G20) Gross C.V. (s.t.) 37.8 37.8 MJ/m Gas burner pressure max. rate 10.0 10.6 mbar Gas burner pressure ignition rate 2.0 2.0 mbar Gas rate max (DHW) 2.79 3.26 m3/h Main burner jet size 16 x 7/120 18 x 7/120 no. x size
CH flow temperature range 40-90 40-90 °C Minimum CH water flow (for 20 °C rise) 1,032 1,204 l/h Pump pressure available 0.25 0.25 bar 8l expansion vessel pre-charge pressure 0.75 0.75 bar Maximum CH system pressure 3.0 3.0 bar
Connections Heating flow / return 22 22 mm Cold water inlet 15 15 mm DHW outlet 15 15 mm Gas inlet 15 15 mm Pressure relief discharge pipework (min) 15 15 mm
Weight 47 48 kg Primary water content 0.7 0.7 litres
Electrical supply Voltage 230/50 230/50 V~/Hz 2 x internal fuses 2 2 A 1 x internal fuse 1,25 1,25 A external fuse 3 3 A Power input 130 130 W
3
Supplied By www.heating spares.co Tel. 0161 620 6677
2.2 Dimensions
(All dimensions in mm)
1a Air/flue duct to the rear 1b Air/flue duct to the side 2 Appliance bracket 3 Heating system return (22 mm) 4 Cold water connection (15 mm) 5 Gas connection (15 mm) 6 Hot water connection (15 mm) 7 Heating system flow (22 mm) 8 Pressure relief valve outlet
(3/4 in BSP)
* with standard horizontal flue
accessory. (max. = 2965 mm with extensions)
2.3 Boiler connections
1 Compression union (flow of
heating system)
2 Service valve (flow of heating
system) 3 Domestic hot water connection 4 Compression Union (gas) 5 Gas service valve (supplied with
the boiler) 6 Cold water connection with
shut-off valve 7 Service valve (return of heating
system) 8 Compression union (return of
heating system) 9 Pressure relief valve
fig. 1
fig. 2
GW 547/0
GW 546/0
Supplied By www.heating spares.co Tel. 0161 620 6677
2.4 Function diagram
1 Air duct 2 Air pressure switch 3 Combustion chamber 4 Temperature sensor (NTC) 5 Ignition electrodes 6 Modulating burner 7 Overheat thermostat 8 Fully modulating automatic gas
valve
9 DHW heat exchanger 10 Indicator lights (LED’s) 11 Maximum radiator temperature
control
12 Maximum hot water temperature
control
13 Central heating control and
lockout reset 14 Main on/off control 15 CH flow service valve 16 Gas service valve 17 Flue gas duct 18 Fan 19 High efficiency heat exchanger 20 Flame sensing electrode 21 Differential pressure switch 22 Expansion vessel charging valve 23 Expansion vessel 24 Automatic air vent 25 Circulating pump 26 Diverter valve 27 Water switch (DHW) 28 Water section 29 Temperature and Pressure gauge 30 Automatic bypass valve 31 Pressure relief valve 32 CH return service valve 33 Cold water shut off valve
fig. 3
GW 573/1
Supplied By www.heating spares.co Tel. 0161 620 6677
3. General requirements
3.1 Related documents
The installation of the boiler must be in accordance with the relevant requirements of Gas Safety (Installation and Use) Regulations 1994, Health and Safety Document No. 635 (The Electricity at Work Regulations 1989), BS7671 (IEE Wiring Regulations) and the byelaws of the local Water Undertaking. It should also be in accordance with the relevant requirements of the Local Authority, Building Regulations, Building Standards (Scotland) Regulations and the relevant recommendations of the following British Standards:-
BS 5440: Flues and ventilation of gas fired boilers not exceeding 60 kW:
- Part 1: Flues
- Part 2: Ventilation BS 5449: Specification for forced
circulation hot water for domestic premises.
BS 5546: Specification for gas hot water supplies for domestic premises.
BS 6700: Services supplying water for domestic use within buildings and their curtilages.
BS 6798: Specification for installation of gas fired boilers not exceeding 60 kW input.
BS 6891: Specification for installation of low pressure gas pipework up to 28 mm (R1) in domestic premises (2nd family gas).
BS 7593: Treatment of water in domestic hot water central heating systems.
BRITISH GAS PUBLICATION DM2: Guide for Installation in Timber Framed Housing
3.2 Boiler location
The location chosen for the boiler must permit the provision of a satisfactory flue termination. The location must also provide adequate space for servicing and air circulation around the boiler. The boiler may be installed in any room, although particular attention is drawn to the requirements of BS7671 (I.E.E. Regulations) and, in Scotland, the electrical provisions of the Building Standards (Scotland) Regulations,inrespectofthe installation of a boiler in a room containing a bath or shower.
(Note: Where a room sealed boiler is installed in a room containing a bath or shower, any electrical switch or boiler control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower).
Where the installation of the boiler will be in an unusual location, special procedures may be necessary and BS 5546 and BS 6798 give detailed guidance on this aspect.
The boiler must be mounted on a flat, vertical wall, which must be sufficiently robust to take the weight of the boiler. The boiler may be installed on a combustible wall, subject to the requirements of the Local Authorities and Building Regulations.
A compartment used to enclose the boiler must be designed and constructed specifically for this purpose. (An existing cupboard or compartment may be used provided that it is modified for the purpose). Details of essential features of cupboard/compartment design including airing cupboard installations are given in BS 6798.
Important
The appliance must be installed and serviced by a competent person as stated in the Gas Safety (Installation and Use) Regulations 1994
If the boiler is to be fitted in a timber framed building, it should be fitted in accordancewithBritishGasPublication DM2 'Guide for Gas Installations in Timber Framed Housing'.
Supplied By www.heating spares.co Tel. 0161 620 6677
3.3 Gas supply
The gas supplier should ensure the availability of an adequate supply of gas.
A gas meter may only be connected to the service pipe by the supplier of gas or their contractor.
An existing meter should be checked to ensure that it is capable of passing the rate of gas supply required.
Installation pipes should be fitted in accordance with BS 6891.
Pipework from the meter to the boiler must be of an adequate size. Do not use pipes of a smaller size than the boiler gas connection (15mm).
The complete installation must be tested for soundness and purged as described in BS 6891.
3.4 Flue system
The standard horizontal flue system (Art. No. 300 807) is suitable for installations up to 995 mm measured from the centre of the boiler flue outlet to the outside face of the wall (A, fig.
4). Flue extensions (Art. No. 300 802) are available to extend this length up to 2965 mm. Both 90° elbows (Art. No. 300 808) and 45° bends (Art. No. 300 809) are also available to increase siting flexibility.
A vertical flue system is also available (Art. No. 300 800).
TURBOmax boilers may also be used in SE- duct applications (SE- duct flue system available Art. No. 300810)
Refer to the flue installation instructions for full details.
fig. 4
GW 579/0
Supplied By www.heating spares.co Tel. 0161 620 6677
3.4.1 Flue Termination
1. The terminal must be positioned such that the combustion products can disperse freely at all times.
2. In certain weather conditions a plume of water vapour may be visible from the flue terminal. Positions where this could be a nuisance should be avoided.
3. If the terminal is fitted less than 2m above a balcony, above ground or above a flat roof to which people have access, then a suitable guard must be provided and fitted (available from Tower Flue Components, Tonbridge, TN9 1TB: reference TFC type K3).
Table 1:
Terminal position for fan-assisted flue (minimum distance - see fig. 5)
A- Directlybelowanopenable mm
window or other opening (e.g. air brick) 300
B- Below gutters, soil pipes
or drain pipes 25 C- Below eaves 25 D- Below balconies 25
(below car port roof 200) E- From vertical drain pipes
and soil pipes 25 F- From internal or external
corners 25 G-Above ground or balcony
level 300 H- From a surface facing a
terminal 600 I- From a terminal facing a
terminal 1200 J- From an opening in a
car port (e.g. door, window)
into a dwelling 1200 K- Vertically from a terminal
on the same wall 1500 L- Horizontally from a
terminal on the same wall 300 M-Distance from adjacent
wall for Vertical Flue 500
fig. 5
Where a terminal is fitted less than 1m below a plastic gutter or less than
0.5m below painted eaves or any other painted surface then a suitable shield at least 1m long should be fitted to protect the surface.
GW 595/0
Note: Vertical flues mustnot terminate within 600 mm of an openable window, air vent or any other ventilation opening.
Supplied By www.heating spares.co Tel. 0161 620 6677
3.5 Air supply
Detailed recommendations for air supply are given in BS 5440: Part 2.
It is not necessary to have an air vent in the room or internal space in which the boiler is installed.
3.5.1 Cupboard or compartment air supply
TURBOmax Room Sealed Combination Boilers are very high efficiency appliances. As a consequence the heat loss from the appliance casing during operation is very low. For cupboard and compartment installations it is therefore not necessary to provide any high or low level permanent air vents for cooling purposes.
3.6 Electricity supply
A 230 V~ 50Hz single phase electricity supply fused to 3 amps must be provided in accordance with the latest edition of BS7671 (I.E.E. Wiring Regulations) and any other local regulations that may apply.
THIS APPLIANCE MUST BE EARTHED. The method of connection to the mains electricity supply must provide a means of completely isolating the boiler and its ancillary controls. Isolation is preferably by the use of a fused three pin plug and unswitched shuttered socket outlet, both complying with the requirements of BS 1363. Alternatively, a 3 Amp fused double-pole switch with a 3mm contact separation on both poles may be used.
3.7 Guide to system requirements
3.7.1 Water circulation system
Detailed recommendations for the water circulation system are given in BS 6798 and BS 5449: Part 1 (for small bore and micro bore central heating systems).
Pipework not forming part of the useful heating surface should be insulated to help prevent heat loss and possible freezing, particularly where pipes are run through roof spaces and ventilated underfloor spaces.
Draining taps must be located in accessible positions which permit the draining of the whole system including the boiler and the hot water system. Draining taps should be at least 1/2 in. BSP nominal size and be in accordance with BS 2879.
The boiler is suitable for use with minibore or microbore systems. Copper tubing to BS 2871: Part 1 should be used for water carrying pipework. All capillary joints in the DHW pipework must be made with lead free solder.
Particularly where a new boiler is to be fitted to an existing system, it is good practice that the system is thoroughly cleansed. This cleasing should take place prior to the fitting of the new boiler and be in accordance with BS 7593.
For advice on the application of system cleansers contact Sentinel, Grace Dearborn Ltd, Widnes, Cheshire, WA8 8UD. Tel: 0151 4951861.
10
Supplied By www.heating spares.co Tel. 0161 620 6677
3.7.2 Filling and make up
The system should be filled with water via a separate filling point fitted at a convenient position on the heating circuit. Where local Water Authority Regulation allows, a temporary connection to the mains may be used (fig. 6). The connection must be removed when filling is completed. Where local Water Authority Regulation does not allow temporary connection, a sealed system filler pump with break tank must be used. The heating system will not be filled automatically from the domestic hot water side.
(Alternative methods of filling sealed systems are given in BS 5449).
3.7.3 Pressure relief valve
A pressure relief valve is provided ready assembled within the boiler (5, fig. 7). This safety device is required on all sealed C.H. systems and is pre-set at 3 bar and provided with a3/4 in. BSP connection for a discharge pipe, which must be of no less than 15mm diameter.
fig. 6
Heating circuit return
Stop valve
Double check valve assembly
Test valve
Hose unions
Temporary Hose
Mains water supply
GW 400/0
3.7.4 Pressure and temperature gauge
This is factory fitted to the boiler and indicates the primary circuit pressure to facilitate filling and testing, as well as showing the temperature of the central heating system water.
fig. 7
GW 609/0
11
Supplied By www.heating spares.co Tel. 0161 620 6677
3.7.5 Expansion vessel
An expansion vessel is incorporated into the boiler suitable for a sealed heating system with a maximum water content of 100 litres.
If the nominal capacity of the built in expansion vessel is not sufficient for the heating system (for instance in case of modernisation of old open systems) an additional expansion vessel can be installed external to the boiler. It should be fitted in the return pipe as close as possible to the boiler in accordance with BS 5449: Part 1.
Guidance on the sizing of an additional expansion vessel is given in Table 2.
3.7.6 Circulating pump
The circulating pump is included in the boiler. The pump head available for the heating system is shown in fig. 8.
3.7.7 System by-pass
An automatic system by-pass is included within the boiler. The boiler is suitable for use in systems with thermostatic radiator valves and no additional by-pass is required.
Table 2: Sizing of Additional Expansion Vessel
Safety valve setting (bar) 3.0 Initial system pressure (bar) 1.0 1.5 Total water content of system VESSEL VOLUME (L)
litres
25 2.7 3.9
50 5.4 7.8 100 10.9 15.6 125 13.6 19.5 150 16.3 23.4 175 19.1 27.3 200 21.8 31.2 225 24.5 35.1 250 27.2 39.0 275 30.0 42.9 300 32.7 46.8 325 35.7 50.7 350 38.1 54.6 375 40.9 58.5 400 43.6 62.4 425 46.3 66.3 450 49.0 70.2 475 51.8 74.1 500 54.5 78.0
For system volumes other than those given above, multiply the system volume by the factor
0.109 0.156
across
3.7.8 Venting
The boiler is fitted with an automatic air vent. Additional provision should be made to enable the heating system to be vented during filling and commissioning either by automatic air vents or manually.
3.7.9 DHW expansion vessel accessory
A DHW expansion vessel kit (Art. No.
8070) is available as an optional
accessory from Vaillant Ltd. This expansion vessel kit should be fitted to the boiler whenever either a stop valve of the loose jumper type or a non return valve are present in the cold water mains supply to the boiler (fig. 9).
fig. 8
GW 402/1
fig. 9
12
GW 494/0
Supplied By www.heating spares.co Tel. 0161 620 6677
4. Boiler installation
sequence
4.1 General
The boiler should be mounted on a flat and vertical area of wall of sufficient area for the boiler plus the required minimum clearances for installation and servicing (fig. 10). These are shown on the installation template supplied with the boiler and are:
5 mm either side of the boiler 100 mm below the boiler* 165 mm on top of the boiler 500 mm in front of the boiler **
* 150 mm where optional pre-
installation connecting group (Art. no. 8015) is used.
** This clearance is only required to
enable easier access to the boiler for servicing and may be provided by an openable door, etc.
Note: If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with British Gas publication reference DM2 'Guide for gas installations in timber framed housing.'
4.2 Boiler delivery
The TURBOmax is delivered in two packs:
a. the carton containing the boiler b. separately boxed flue accessory,
either: 1m horizontal flue accessory
(Art. No. 300 807); or vertical flue accessory
(Art. No. 300 800)
fig. 11
GW 403/1
13
Supplied By www.heating spares.co Tel. 0161 620 6677
4.2.1 Installation accessories
Table 3 lists the standard and optional accessories which are available for the TURBOmax combination boilers.
4.2.2 Unpack the boiler (fig. 11)
Open the boiler carton and remove: a. protective cardboard sheet
b. top and bottom decorative panels c. polystyrene packaging
Note: Care should be taken not to scratch the white surface of the boiler casing.
Packed in the boiler carton are the following:
boiler installation template
boiler hanging bracket
gas service valve
fixing screws and wallplugs
installation and user instructions
flue restrictor
domestic hot and cold water
connections and straddle bracket
Table 3: Installation Accessories
Standard Accessories Art. No.
1. Air/flue duct and terminal accessory 300 807
Optional Accessories Art. No.
1. Vertical air / flue duct (including terminal) 300 800
2. Pitched roof adjustable roof tile (for use with vertical air/flue duct) 9076
3. Flat roof penetration collar (for use with vertical air/flue duct) 9056
4. 1 m air /flue duct extension 300 802
5. 2 m air / flue duct exension 300 803
6. Additional 90° elbow for air / flue duct 300 808
7. Additional 45° bends (pair) for air / flue duct 300 809
8. Additional air / flue duct joint clamps (pair) 300 806
9. Se- duct flue kit 300 810
10. Internal flue fixing kit 8098
11. Pre - installation connecting group (includes 300 813) 8015
12. Vaillant boiler replacement connection accessory 300 813
13. Pipe cover accessory 8099
14. Plug in 24 hour central heating timeclock 300 820
15. Plug in 7 day central heating timeclock 300 821
4.3 Preparation of boiler location
4.3.1 Select position of boiler.
Refer to Section 3.2 'Boiler Location' for information regarding siting the boiler. In general the boiler must be positioned such that:
there is adequate space around the
boiler for service and maintenance the boiler can be correctly flued,
i.e. the flue terminal position is sited in accordance with Section 3.4.1 and the air / flue duct can be installed in accordance with the flue installation instructions supplied.
all necessary pipework can be
connected, including the pressure relief valve discharge pipe.
fig. 11
14
GW 601/0
Supplied By www.heating spares.co Tel. 0161 620 6677
4.3.2 Using the boiler template (fig. 12)
4.3.2.1 Once a suitable location has
been chosen, fix the paper installation template on the wall ensuring that the centerline of the template is vertical using a spirit level or plumb line.
The template shows the positions of the fixing holes for the boiler hanging bracket (2) and the optional pre-installation connection group (3). The template also shows the position of the flue exit hole, for use where the air flue duct is to be installed directly to the rear of the boiler, e.g. where the boiler is installed on an outside wall and the flue terminates directly behind.
4.3.2.2 A Pre - installation connection
group (Art. No. 8015) is available as an optional accessory. It is used to allow the installation of the central heating and domestic hot water pipework without the need to have the boiler in position. Where an old existing Vaillant boiler is to be replaced, the boiler replacement accessory (Art. No. 300 813) can be used to allow easy connection on the new boiler to the existing connecting group. Refer to the instructions supplied separately with these accessories.
4.3.2.3 Mark on the wall the positions
of the hanging bracket fixing holes (2). Drill two holes Ø10 mm for the hanging bracket. (Note: Use the alternative fixing holes where necessary).
4.3.2.4 Rear exit flue.
Mark the position of the centre of the flue duct and its circumference, e.g. by drilling through the template (1, fig. 12).
4.3.2.5 Other flue options.
Refer to the installation instructions supplied with the flue accessory for detailed instructions on other flue options such as vertical RSF flues, flue runs to the side of the boiler and the use of additional flue elbows and bends etc.
4.3.2.6 Remove the template from the
wall and plug the drilled holes using the wallplugs supplied.
fig. 12
4.3.3 Fitting the boiler hanging bracket.
Secure the hanging bracket to the wall using the screws supplied. (If the condition of the wall is poor it may be necessary to use additional or alternative fixings to ensure adequate support).
NOTE: If the boiler is to be fitted in a timber framed building ensure that the brackets are secured to a substantial part of the timber frame capable of taking the weight of the boiler.
GW 426/0
15
Supplied By www.heating spares.co Tel. 0161 620 6677
4.4 Installing the flue system
At this stage install the flue system (refer to separate installation instructions supplied).
4.5 Mounting the boiler
4.5.1 Preparation
Remove the boiler from the carton. Lay the boiler on the floor and
remove the white boiler bottom cover by removing two screws (l, fig. 51) and slackening two screws (2, fig.
51). Do not remove boiler side panels. Remove the two plastic sea­ling caps from the domestic water connections.
Fit the pre-assembled cold water inlet and hot water outlet pipes with straddle bracket (1,2,3, fig. 15) to water connections on boiler (4, fig.
15) using washers provided.
4.5.2 Fitting the boiler (fig. 13)
Lift the boiler up to the wall so that it is slightly above the hanging bracket.
Note: Lift the boiler from under the front edge of the side panels. Do not lift the boiler by the control box. Do not attempt to lift the boiler without the side panels or side casing fitted.
Lower the boiler slowly onto the hanging bracket so that the cross member at the top rear of the boiler fully engages into the hanging bracket.
4.5.3 Pipework connections (fig. 14)
Figure 14 shows the central heating, domestic hot water, mains cold water, gas and pressure relief valve connections.
4.5.3.1 Central heating flow and return
Before connecting the heating circuit to the appliance, all pipework and radiators must be thoroughly flushed to remove any installation debris.
Connect the flow and return pipes to the central heating service valves (8) and (9) on the appliance using the 22mm compression connections.
4.5.3.1.1 Top pipework connection
If it is desired to run heating and water pipework to above the boiler, the purpose provided voids in the left and right sides of the boiler casing may be used (see fig. 16).
Note: To allow fitting of the bottom boiler cover, the left hand tab (2, fig.
16) should be folded upwards where pipes are fitted in the left hand void.
Where pipes are installed in these voids, a method of disconnection e.g. a compression connector (1, fig. 16) must be provided to allow easy removal of the boiler from the wall, if required.
4.5.3.2 Cold mains water inlet and hot water outlet (fig. 14)
Flush out all foreign matter from the mains supply pipe before connecting to the boiler.
Connect the mains water supply (3) and hot water outlet pipes (4) to the 15 mm compression connections.
Note: The boiler has a maximum domestic water working pressure of 10 Bar. If the cold mains supply pressure exceeds 10 Bar, a pressure reducing valve must be fitted to the cold water inlet.
4.5.3.3 Pressure relief valve discharge
The appliance contains the pressure relief valve required for a sealed system (5). Connect a discharge pipe not less than 15 mm diameter to the outlet of thisvalve.
This discharge pipework should be as short as possible and installed with a continuous fall away from the boiler. The pipe should terminate in a position which ensures that any discharge of water or steam from the valve cannot create a hazard to persons in or about the premises, or cause damage to any electrical components or external wiring, and the point of discharge should be clearly visible. The discharge must not terminate above a window, an entrance or any type of public access. The installer must consider that the pipe could discharge boiling water.
fig. 13
fig. 14
fig. 15
fig. 16
GW 608/0
GW 609/0
GW 706/0
GW 677/0-A
16
Supplied By www.heating spares.co Tel. 0161 620 6677
4.5.3.4 Gas supply The boiler is supplied with a 20 x 15
mm gas service valve (10, fig. 14). Fit the 20mm compression fitting to the boiler gas inlet (11, fig. 14) and tighten. Install a gas supply pipe not less than 15mm diameter and connect to thegas service valve. (Ensure the gas supply pipework is adequately sized such that a 20 mbar - (8" w.g.) ­gas pressure is available at the boiler inlet at full flow rate). Tighten all union connections.
4.6 Connecting the flue assembly to the boiler
Note : A flue restrictor ring is sup­plied packed with the users and installation instructions. The restrictor should be used under the following circumstances : -
Horizontal flues
Where a horizontal flue less than 1 m
in length is used.
(DO NOT fit the restrictor where the
horizontal flue is more than 1 m in length).
Vertical flues
Where a vertical flue less than 1 m (e.g. 1 m between the top of the boiler and the bottom of the vertical air / flue duct assemly) is used
(DO NOT fit the restrictor where the vertical flue is more than 1 m in length).
fig. 18
fig. 17
GW 553/0
GW 592/0
4.6.1 Horizontal Flue
Remove two screws (1, fig. 18) and take off one half ring (2, fig. 18). If necessary, fit the flue restrictor ring (Note : It will be necessary to remove both half rings if the flue restrictor ring is to be fitted. The flue restrictor ring should be placed on top of flue outlet directly below the two half rings see fig. 18a. One half ring should be replaced immediately).
Place a 63mm diameter x 35 mm wide flue duct clamp (4, fig. 19) loosely over the flue duct (1, fig. 19). Place the 63 mm diameter x 25 mm wide flue duct clamp (5, fig. 19) over the flue gas connection on the boiler.
fig. 18a
fig. 19
GW 705/0
GW 593/0
17
Supplied By www.heating spares.co Tel. 0161 620 6677
Loosen screws on the 95 mm diameter x 55mm wide clamp (6, fig. 21) and push over the air duct.
Remove screws and sealing washer on the 95 mm diameter x 25 mm wide clamp (3, fig. 21) and push onto the flue elbow on the side to be connected to the appliance. Ensure the clamp is clear of the end of the elbow.
Push the flue elbow into the clamp (2, fig. 20) connected to the appliance flue gas duct and tighten the securing screws lightly.
Ensure that the elbow and air/flue duct line up and are closely butted together. Pull the clamp (4, fig. 20) over the joint between the flue gas duct and flue elbow. Ensure that the air/flue duct and terminal are correctly positioned. Tighten the securing screws on both clamps.
Note : Excessive tightening of these screws is not necessary. Ensure that the air / flue duct and terminal assembly is not displaced though the wall. Check that the air duct of the terminal still projects by 90 mm through the wall.
Refit the half ring 2, fig. 21. Pull the 95 mm diameter x 25 mm wide clamp (3, fig. 21) over the joint between the flue elbow and half rings. Refit the screws and sealing washer and tighten lightly.
Pull the 95 mm diameter x 55 mm wide clamp (6, fig. 21) over the joint between the flue elbow and air/flue duct. Tighten the securing screws on both clamps.
Drill two holes, 3 mm diameter through both air duct clamps into the air ducts at the most convenient positions (5, fig. 21). Take care not to penetrate the inner flue duct. Screw the clamps to the air ducts using the self tapping screws provided.
Lower the flue assembly until a gap of about 25 mm exists between the air duct of the air/flue duct and terminal assembly and the half rings on the appliance. The two ducts must not butt together.
Pull the sleeve (2, fig. 22) down over the flue connection of the appliance against the stop. Align the holes in the sleeve and boiler flue gas connector and secure with a self tapping screw (1, fig.23).
Note : The sleeve must not be screwed to the bottom of the flue gas duct of the air/flue duct assembly. This duct must be able to slide in order to absorb small movements of the roof structure.
Refit the two half rings. Pull the 95mm diameter x 55 mm wide clamp down over the joint between the air/flue duct assembly and the half rings. Tighten the clamp screws (1, fig.24).
fig. 20
fig. 21
GW 616/0
GW 594/0
4.6.2 Vertical Flue
Remove the two half rings (2, fig. 18)
fig. 22
and, if necessary, fit the flue restrictor ring.
(Note: It will be necessary to remove both half rings if the flue restrictor ring is to be fitted. The flue restrictor ring should be placed on top of flue outlet directly below the two half rings (see fig. 18A). One half ring should be replaced immediately).
Fit the 63 mm diameter x 68 mm wide flue duct sleeve (2, fig. 22) over the flue gas duct of the air/flue duct assembly.
Loosen the screws of the 95 mm diameter x 55 mm wide clamp (1, fig.
22) and push over the air duct of the air/flue duct assembly.
fig. 23
18
GW 560/0
fig. 24
GW 558/0
GW 602/0
Supplied By www.heating spares.co Tel. 0161 620 6677
Drill two holes 3 mm diameter through the air duct clamp (2. Fig 24) ensuring that the drill does not pene­trate the flue duct. Screw the clamp to the boiler half ring using the self tap­ping screws provided.
Note: The air duct clamp must not be screwed to the bottom of the air flue duct and terminal assembly. The air/flue duct and terminal assembly must be able to slide in the air duct clamp to absorb any slight movements in the roof structure.
4.7 Electrical installation
4.7.1 General electrical requirements
All electrical work shall be carried out by a competent person and shall comply with BS7671 (IEE Regulations).
The boiler is supplied for connection to a 230V~ 50Hz supply fused at 3A rating. Connection to the mains supply should be made via a fused 3 pin plug to an unswitched, shuttered socket, both complying with the requirements of BS1363.(Alternatively, connection may be made via a 3 Amp fused double pole isolator having a contact separation of at least 3mm in all poles and supplying the boiler and controls only).
The point of connection to the mains must allow complete electrical isolation of the boiler and its ancillary controls. It should be readily accessible and adjacent to the boiler. A 3 core flexible cord according to BS6500 tables 6, 8 or 16 (3x0.75 to 3x1.5 mm2) should be used.
Warning: This appliance must be
earthed
4.7.2 Connecting to mains supply
Slacken front panel fixing screw (1, fig. 25) and lower front panel. Remove terminal box cover by undoing screw (1, fig. 26)
Connect the power supply cord as follows (see fig. 28):-
green / yellow (earth) wire....
boiler terminal
Blue (neutral) wire..... boiler terminal N
Brown (live) wire..... boiler terminal L
Note: Do not use boiler terminal
connections 7-8-9
IMPORTANT Ensure that all cords pass through the terminal box entrance grommets and are securely fixed by the cable clamps. Ensure that the power supply cord is connected such that the current carrying conductors become taut before the earthing conductor should the supply cord slip from the cable clamp.
Refit the terminal box cover after completion of all electrical components
fig. 25
fig. 26
fig. 27
GW 603/0
GW 614/0
GW 638/0-B
fig. 28
GW 679/0
19
Supplied By www.heating spares.co Tel. 0161 620 6677
4.8 Controls
4.8.1 External electrical controls
The boiler terminals 3,4 and 5 are for connecting external controls such as a time switch and/or room thermostat.
Terminals 3 and 4 are linked together when the boiler is supplied. If external controls are used, this link must be removed, and the controls connected across terminals 3 and 4.
Terminal 5 is an additional neutral connection for external neutrals such as from the anticipator of a room thermostat.
Refer to Section 4.8.2 for full connection details.
4.8.2 Connection of external electrical controls
4.8.2.1 Connection details for
programmable thermostat and boiler terminal strip (refer to fig. 29).
Fig. 29 shows the connection details where a programmable thermostat (time switch with built-in room thermostat) is used to control the boiler. (Important: The arrowed numbers indicate connection into the relevant terminal in the boiler terminal strip).
4.8.2.2 Connection details for
external time switches and boiler terminal strip (refer to fig 29a).
Fig. 29a shows the connection details where a time switch is used without a room thermostat to control the boiler. (Important: The arrowed numbers indicate connection into the relevant terminal in the boiler terminal strip).
If a room thermostat is tobeconnected in addition to a time switch the wire between the time switch 'ON' terminal and boiler terminal 4 should be broken by the contacts of the room thermostat (see Schematic layout, fig. 30).
If a frost thermostat is to be fitted it should be connected in parallel across terminals 3 and 4.
4.8.2.3 Vaillant optional Plug-in timer
Accessories Refer to the instructions supplied with
the optional plug in timer accessories for connection details.
Connection details for programmable thermostats
Vaillant Calotrol (VRT 9083 and VRT 9084)
ACL Drayton Digistat 2 and 3
NL 43
ACL Drayton PT110, PT170
ACL Drayton Lifestyle CT171, CT172, PT271, PT371
Danfoss Randall TP2, TP3, TP4, TP5
Honeywell CM51, CM41
Landis & Gyr REV 10 and 21
Potterton Myson Pot 1
NL1234
NL3
NL1234
fig
Connection details for time switch
ACL Drayton Lifestyle LP711
ACL Drayton Switchmaster 300 (Please note: Remove Link N-2 and L-4)
Grässlin Towerchron Dt71, T200l
Honeywell ST6100
Honeywell ST7000B (Battery operated)
Horstmann 425 Coronet Channel Plus, H17, H11
Landis & Gyr RWB100, 152, 170
Potterton Myson EP400l, EP500l
Danfoss Randall 103, 103E, 103E7
Danfoss Randall Set 1E, TS975
fig.
NL 4
ENL123456
NL 43
NL12345 E
NL 43
ENL123456
NL3 4
NL1234
NL4 3
NL1234
NL 34
NL1234
NL3 4
NL1234
NL 3 4
NL1234
43NL
123E56
ON
Connection detail for room thermostat and time switch
Boiler Terminal Strip
NL34
1234
34
123
OFF ON
34
123
34
ABC
345
2L1NC
OFF ON
OFF ON
OFF ON
ON
34
L234
OFF ON
ON OFF
ON OFF
34
Q1 Q2
ON
fig
20
GW 409/0
Supplied By www.heating spares.co Tel. 0161 620 6677
4.8.3 Thermostatic radiator valves
The boiler has a built-in automatic bypass valve making it ideal for use in systems with thermostatic radiator valves (no separate system bypass is required).
For optimum fuel economy it is recommended that where TRVs are used they are used in conjunction with a programmable roomstat or separate timer and room thermostat to ensure complete boiler shutdown when the heating demand is satisfied. (The radiator in the room containing the room thermostat should not be fitted with a TRV).
4.8.4 Circulating pump
The boiler incorporates a built-in circulating pump that is fully pre-wired. (No additional wiring is necessary). The pump incorporates an automatic overrun period after the boiler switches off.
4.8.5 Anti-cycling 'economiser' control
The boiler incorporates a built in anti-cycling control to ensure that energy wasteful short cycling of the boiler cannot occur. This control prevents the boiler from re-igniting for a pre-set period of 5 minutes after central heating operation. (The hot water operation is unaffected by this control and hot water can be drawn at any time).
Note: To temporarily override the anti-cycling control, turn the main on/off control to the ”off” position (0), and then back to the ”on” position (I) after a few seconds.
21
Supplied By www.heating spares.co Tel. 0161 620 6677
5. Commissioning
5.1 Preliminary electrical checks
Check the electrical installation by carrying out short circuit, earth continuity and resistance to earth tests and a check for correct polarity.
5.2 Gas supply
The complete gas installation including the gas meter must be inspected, tested for soundness and purged in accordance with BS 6891.
The gas supply to the boiler can be purged by slackening the gas service valve beneath the boiler (1, fig. 31). Ensure that there is adequate ventilation, extinguish naked flames and do not smoke whilst purging.
After purging, the gas service valve connection must be re-tightened and tested for soundness. (The boiler itself does not require purging as this will be done by the automatic burner sequence control).
5.3 Water supply
Open all domestic hot water taps supplied by the boiler, turn on the mains water supply to the boiler and open the mains water isolating valve below the boiler (2, fig. 31).
Water will now flow through the boiler to the hot taps. Starting with the lowest tap supplied, turn the hot taps off one at a time until the hot water pipework is purged of air.
Check all hot and cold pipework for leaks.
fig. 31
GW 610/0
22
Supplied By www.heating spares.co Tel. 0161 620 6677
5.4 Filling the heating system
The boiler primary circuit and the heating system should be filled using a filling method as described in Section 3.7.2.
Ensure that the boiler CH service valves (3, fig. 31) are open.
Partially open the filling valve and allow water to enter the system. Starting with the lowest radiator, open the radiator air release until water (clear of bubbles) is emitted.
Repeat this at all radiators until the complete system is full, all air locks have been cleared and the boiler pressure gauge reads 1.5 Bar. Release any air from the pump by slackening the centre screw (1, fig. 32).
The boiler is equipped with an automatic air release valve. To allow this to vent the boiler, the cap on top (2, fig. 32) must be slackened by 1-2 turns. (This cap must be left slackened during boiler operation to ensure any residual air or system gases are released).
Check the heating system and boiler connections are sound.
fig. 32
GW 634/0
5.5 Initial system flush ('cold')
The whole of the heating system must be flushed out at least twice: once cold, and once hot as instructed later in Section 5.12.
Open all radiator or heating valves and boiler CH service valves (3, fig.
31) and drain the heating system and boiler completely from the lowest points of the system via 1/2in. BSP drain taps (opened full bore to remove any installation debris prior to lighting the boiler).
Refill the heating system as described in Section 5.4: Filling the heating system.
Check the operation of the pressure relief valve by rotating the knob on the valve.
23
Supplied By www.heating spares.co Tel. 0161 620 6677
5.6 Initial lighting
Check that the boiler combustion
chamber (5, fig. 33) is correctly fitted.
Ensure the cold water shut-off valve
(4, fig. 34) is open by turning anti-clockwise.
Open the gas service valve (2, fig.
34) Check that the CH service valves
(1 and 5, fig. 34) are open. Check that all external heating
controls are calling for heat. Switch on the electricity supply to
the boiler. Set both the maximum hot water
temperature control (4, fig. 33) and maximum radiator temperature control (3, fig. 33) to '9'.
Turn the boiler on/off control (1,
fig. 33) to the ”on” position ( ). Set the boiler central heating
control (2, fig. 33) to the 'Heating and Hot Water' position ( ).
The boiler will now operate for central heating. Allow the boiler to run for a few minutes to clear any air remaining in the primary circuit.
(If the boiler should fail to light the 'lock out' indicator will illuminate - see fig. 41. This usually means that the gas supply is turned off, or is not purged of air. Check gas supply, and turn the central heating control to the reset position - ( ) - and repeat lighting procedure).
Set the boiler central heating
control to the 'Hot Water only' position ( ). The boiler will now switch off.
Reset the maximum radiator tempe-
rature control to the required setting according to Section 5.14.
FULLY open a hot water tap. The
boiler will now operate for hot water.
fig. 33
fig. 34
GW 612/0
GW 553/0
24
Supplied By www.heating spares.co Tel. 0161 620 6677
At this point the preset maximum domestic hot water flow rate can be adjusted if required.
Note: The water flow limiter built into the boiler ensures that the maximum domestic hot water flow rate does not exceed the nominal setting (equivalent to a hot water temperature rise of 35°C). Adjustment is only required if the user requires a higher temperature rise than this setting.
Turn the water flow adjusting screw (1, fig. 35) clockwise to decrease the flow from the tap until the temperature rise is at the desired level. Turn off the hot tap after completion of adjustment.
5.7 Gas inlet working pressure
Check the gas inlet working pressure by slackening the sealing screw and attaching a U gauge to the test point (3, fig. 36) on the inlet tothe gas valve. Fire the boiler at full rate by opening a hot water tap. Check that the U gauge is reading 20 mbar.
(If the pressure is not 20mbar this should be investigated before continuing with the commissioning procedure. Lower pressures than 20mbar are indicative of an incorrectly sized or partially blocked gas supply).
Turn off the hot tap. Remove U gauge. Tighten the test point screw and test for soundness.
tolerance shown, contact Vaillant Ltd. Technical Department). Turn off the hot tap.
Remove U gauge. Tighten the sea-
ling screw (1, fig. 36)and test for soundness. Reconnect NTC sensor (3, fig. 37). Refit plastic plug in chamber sensing tube. Reset the maximum hot water
temperature selector to the required setting (see Section 5.14). Raise control box and secure in
position using screw (1, fig. 25).
fig. 35
fig. 36
GW 635/0
GW 636/0
5.8 Main burner pressure
The burner pressure on this boiler has been factory set and does not require adjustment. The main burner pressure may be checked in the following way:
Slacken the sealing screws and
attach one arm of a U gauge to the burner test point (1, fig. 37). Remove plastic sealing plug and connect the other arm to the combustion chamber sensing tube (2, fig. 37). Ensure the maximum hot water
temperature control (4, fig. 37) is set to '9'. Fully open a hot water tap to fire
the boiler at full rate. Break the in line connector to the NTC temperature sensor (3, fig.
37). Check that the burner pressure is as
shown in Table 4. (If the burner pressure is not correct within the
fig. 37
Table 4: Burner Pressure & Gas Rate
VUW 242 VUW 282
Maximum Burner 10.0 mb 10.6 mb Pressure (DHW) (
Maximum Gas 2.79 m3/h 3.26 m3/h Rate
+
1.0 mb) (
-–
(98.5 ft3/h) (115.1 ft3/h)
+
1.0 mb)
-–
GW 637/0
25
Supplied By www.heating spares.co Tel. 0161 620 6677
5.9 Adjusting the central
heating output (range rating)
The TURBOmax is fully modulating for central heating, and it is therefore not necessary to range rate the central heating. However, if desired, it is possible to range rate the boiler, as follows:
Remove screw (1, fig. 38) and
lower control panel. Slacken the sealing screw and
attach one arm of a U gauge to the burner pressure test point (1, fig.37). Remove plastic sealing plug and connect the other arm to the combustion chamber sensing tube (2, fig.37).
Remove screw (1, fig. 39) and
remove terminal box cover to access the range rating potentiometer (2, fig. 40) beneath.
Operate the central heating by
turning the central heating control to the 'Heating and Hot Water' position ( ) ensuring that the external controls are calling for heat and the maximum radiator temperature control is set to 9.
The central heating output can now
be altered by inserting an electricians screwdriver into the potentiometer (2, fig. 40)
Turn the potentiometer fully
anticlockwise to the stop. Slowly turn the potentiometer
clockwise, whilst observing the U gauge.
Stop turning the potentiometer when
the burner pressure is at the correct setting for the output required (see table 5).
Turn the boiler off.
Remove U gauge. Tighten the
sealing screw, (1, fig. 36) and test for soundness.
Refit plastic plug in chamber
sensing tube. After setting, refit cover screw (1,
fig. 39) and re-secure control panel (1, fig. 38).
fig. 38
Table 5: Central Hea
Output to Range rating mbar
central Heating
mbar VUW 242 VUW 282
28.0 (95,560) - 10,6
24.0 (81,900) 10,0 8,0
21.0 (71,700) 8,0 6,3
18.0 (61,500) 6,1 4,8
15.0 (51,200) 4,5 3,4
12.0 (41,000) 3,1 2,2
min. 9,6 (32,800) 2,0 -
GW 603/0
fig. 39
fig. 40
GW 614/0
GW 638/0-B
min. 11,2 (38,240) - 2,0
26
Supplied By www.heating spares.co Tel. 0161 620 6677
5.10 Functional Checks
5.10.1 Introduction
The Vaillant TURBOmax is equipped with a set of diagnostic indicator lights to showthe operational status of the boiler. A functional check of DHW and CH operation can be made using these indicator lights (fig. 41).
5.10.2 Functional check of domestic
hot water
Ensure that the power on indicator
is illuminated. Set the boiler central heating
control to the 'Hot Water only' position ( ).
Turn on a hot tap and draw water
at a high rate. The hot water demand indicator
will illuminate. The appliance will start its lighting
sequence. Once the fan and flue system has proved itself, the fan operation indicator will light.
The gas valve will open and
sparking will commence at the burner. The ignition indicator will illuminate.
As soon as the burner has ignited
and the flame has been sensed the flame indicator will illuminate.
By illuminating in this sequence the
indicator lights have demonstrated correct operation of the boiler for DHW.
5.10.3 Functional check of central
heating
Ensure that the power on indicator
is illuminated. Set the boiler central heating
control to the 'Central Heating and Hot Water' position ( ).
Ensure external controls are calling
for heat. The central heating demand
indicator will illuminate. Providing the boiler has not
achieved its set temperature, and the anti cycling control is not activated, the boiler will start its lighting sequence. Once the fan and flue system have proved their satisfactory operation the fan operation indicator will light.
Burner lock out indicator Flame indicator Ignition indicator Fan operation indicator Central heating demand indicator Hot water demand indicator Power on indicator
fig. 41
The gas valve will open and spar-
king will commence at the burner. The ignition indicator will illuminate.
As soon as the burner has ignited
and the flame has been sensed the flame indicator will illuminate.
By illuminating in this sequence the
indicator lights have demonstrated correct operation of the boiler for CH.
Note : Should the boiler fail to light
the burner lock out indicator will
illuminate. This usually means that the
gas supply is turned off or has not been purged of air. Check the gas supply, turn the central heating control to the reset position ( ) and repeat the lighting procedure.
GW 618/0
27
Supplied By www.heating spares.co Tel. 0161 620 6677
5.11 Checking flame
supervision device
Operate the boiler and turn off the gas supply at the boiler gas service valve. The boiler should attempt to re-light (sparking at ignition electrode visible through viewing window) for approximately 10 seconds before shutting down. The lock out indicator light will illuminate. Open the gas service valve and turn the central heating control (2, fig. 33) to the reset position ( ). The boiler should now re-light.
5.12 Final system flush ('hot')
Allow the boiler and system to reach maximum temperature and check that the heating system is watertight. Turn the boiler off and rapidly drain both boiler and system while still hot.
Refill the system and release all air as described in Section 5.4. Release water from the system until the system design pressure of 1.2 bar is attained.
(The actual reading on the pressure gauge - (6, fig. 33) - should ideally be
0.5 Bar plus an additional pressure
corresponding to the highest point of the system above the base of the boiler - 10 m head equals an additional 1 Bar reading on the pressure gauge. The minimum pressure should not be less than 1 Bar in any installation).
If the system is to be treated with an inhibitor it should be applied at this stage. Sentinel X 100 is suitable for this purpose and it should be applied in accordance with the manufacturers instructions.
Further instructions can be obtained from Sentinel, Grace Dearborn Ltd, Tel: 0151 4951861.
Disconnect the temporary filling connection.
5.13 Fitting case
Attach top door panel by slotting side clips (1, fig. 42) into holes in side panel and sliding panel down to secure. Attach bottom door panel by locating onto top hinge pin (2, fig.
43) and inserting bottom hinge screw (1, fig. 43) so that it also locates into the door.
5.13.1 Door hinged at left hand side
If required the appliance lower door can be altered to hinge on the lefthand side.
Remove screws from bottom hinge pin (1, fig. 43) and transfer to left hand side panel.
Lift bottom of top hinge pin (2, fig.
43)away from casing to release retaining lug. Rotate top hinge through 90° to remove. Refit to left hand side casing.
Attach bottom door panel by locating onto top hinge pin (2, fig. 43) and inserting bottom hinge screw (1, fig.
43) so that it also locates into the door.
5.13.2 Fit bottom cover
Attach bottom cover to boiler by locating over front screws (2, fig. 51) and secure with rear screws (1, fig. 51).
fig. 42
fig. 43
GW 605/0
GW 606/0
28
Supplied By www.heating spares.co Tel. 0161 620 6677
5.14 Hand over to user
Set the maximum radiator temperature control (3, fig. 44) to the desired setting. The following settings may be used as a guide:
Spring and Autumn 5 – 6 Winter (normal) 6 – 7 Winter (severe) 7 – 9
Note: if the setting is too low the radiators may not reach the desired temperature.
Set the maximum hot water temperature control (4, fig. 44) to the desired setting. For normal circumstances the maximum hot water temperature should be set to 6.
Instruct the user in the safe and efficient operation of the boiler, in particular the function of:-
the boiler on / off control
the maximum radiator temperature
control the maximum hot water temperature
control the pressure gauge.
Show the user how to operate any external controls.
Explain to the user the importance of having the boiler regularly serviced by a competent servicing company. To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement. Please contact Vaillant Service Department (FREEPHONE 0800
318076) for further details. Leave the user instructions in the
purpose provided pocket on the front of the control panel (2, fig 38).
Leave the installation and service instructions with the user.
6. Servicing
To ensure the continued safe and efficient operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once per year should be adequate. It is law that all servicing work is carried out by a competent person (CORGI registered).
IMPORTANT:
Before starting any maintenance work:
Isolate the mains electricity supply
by disconnecting the plug at the socket outlet (if there is an isolating switch only remove the fuse from the switch).
Turn OFF the gas supply at the gas
service valve fitted to the boiler. Always test for gas soundness and
always carry out functional checks after any service work and after exchanging any gas carrying component.
Always check earth continuity,
polarity and resistance to earth with a multi-meter after any service work and after exchanging any electrical component.
Note: The boiler is fitted with a combustion analysis test point (7, fig.
44). A suitable combustion analyser can be connected to this point to establish the combustion performance of the boiler.
6.1 Initial Inspection
Before commencing any servicing or maintenance work, carry out an initial inspection of the system as follows:-
Inspect the flue, pipework and electrical connections for indications of damage or deterioration.
Inspect the air supply and ventilation arrangements of the installation, ensuring that the requirements of Section 3.5 are met.
Operate the boiler by turning the maximum hot water temperature control (4, fig. 44) to '9' and fully opening a hot water tap. Inspect the burner operation through the viewing window. Check that the flames are burning evenly over the full surface of the burner. Inspect for signs of excessive lifting or sooting.
Check the heating and hot water system, in particular the condition of theradiator valves, evidence of leakage from the heating system and dripping hot water taps.
fig. 44
GW 612/0
29
Supplied By www.heating spares.co Tel. 0161 620 6677
6.2 Routine maintenance
6.2.1 Remove front case
Remove bottom hinge screw (1, fig. 46) and pull lower door panel forward and down to release it from the top hinge pin (2, fig. 46).
Slide the top panel up to release retaining clips (1, fig. 47). Lift off top panel.
Remove boiler bottom cover by
undoing two screws (1, fig. 51) and slackening two screws (2, Fig.
51).
6.2.2 Turn off the boiler (fig. 45)
Isolate the electrical supply to the
boiler Turn off the gas service valve (2)
Turn off boiler CH service valves
(1 and 5) Turn off DHW cold water service
valve (4).
fig. 45
GW 553/0
6.2.3 Remove combustion chamber front cover (5, fig. 44)
Remove four screws (2, fig. 54) securing combustion chamber front cover
Lift combustion chamber clear of top retaining lugs and pull forward.
Remove combustion chamber cover by first bringing the left side forward to clear boiler casing.
6.2.4 Inspect main heat exchanger
Remove five screws securing heat exchanger front panel (1 and 3, fig. 48) and remove by gently pulling down and forward.
Inspect main heat exchanger and remove any deposits with a soft brush.
fig. 46
fig. 47
GW 606/0
GW 605/0
30
Supplied By www.heating spares.co Tel. 0161 620 6677
6.2.5 Inspect burner
With the combustion chamber front cover and heat exchanger front panel removed it is possible to inspect the burner. Any deposits should be removed with a soft brush. Check the condition of the ignition and monitoring electrodes.
6.2.6. Check central heating
expansion vessel
Note : It is not necessary to carry out this check every year - a check every three years should be sufficient.
Release the pressure from the boiler as described in section 7.1.2.
Remove valve cap from expansion vessel charge point (2, fig. 49).
Check that internal charge pressure of expansion vessel is between 0.7 - 0.9 Bar. If pressure is lower than this the vessel should be re-pressurised using an air pump.
Refit valve cap (2, fig. 49). Open central heating service valves
and re-pressurised the boiler and heating system if necessary (see section 5.4).
fig. 48
fig. 49
GW 639/0
GW 604/0
6.3 Re-commissioning the boiler
Refit the heat exchanger front
panel. Refit combustion chamber front
cover ensuring that the seal is in good condition. Ensure that the cover is correctly fitted and a good seal is obtained.
Turn on the gas and electricity
supplies. Check soundness of internal gas
connections. Carry out electrical safety checks
(see section 5.1) Check water soundness
Operate burner and check flame
picture. Check for correct function of the
boiler ( see section 5.10). Check burner pressure as described
in section 5.8 and boiler gas flow rate.
Refit case (see Section 5.13)
31
Supplied By www.heating spares.co Tel. 0161 620 6677
7. Parts replacement
IMPORTANT:
Before starting any maintenance work:
Isolate the mains electricity supply
by disconnecting the plug at the socket outlet (if there is an isolating switch only, remove the fuse from the switch).
When removing any water carrying
components ensure that the control box cover and terminal box cover are in position and water is kept away from all electrical components.
Turn OFF the gas supply at the gas
service valve fitted to the boiler. Always test for gas soundness and
always carry out functional checks after any service work and after exchanging any gas carrying component.
Always check earth continuity,
polarity and resistance to earth with a multimeter after any service work and after exchanging any electrical component.
7.1.2 Releasing CH water pressure and draining the boiler (fig. 50)
Isolate electrical supply to boiler.
Remove combustion chamber cover
as in section 7.1.5. Turn off boiler CH service valves
(2). Attach a length of rubber tube to
draining points (4), and drain the water from the boiler into a suitable container by undoing the drain points one turn.
When pressure gauge reads zero,
open main heat exchanger air vent (5, fig. 57) to allow complete draining of the boiler. Close air vent before refilling the boiler.
fig. 50
GW 619/0
7.1 Initial preparation
(These initial preparation procedures need only be carried out where specifically mentioned in theindividual component replacement procedures).
7.1.1 Turning off the boiler (fig. 50)
Isolate the electrical supply to the
boiler Turn off the gas service valve (1)
Turn off boiler CH service valves (2)
Turn off DHW cold water service
valve (3).
32
Supplied By www.heating spares.co Tel. 0161 620 6677
7.1.3 Removal of front casing
7.1.3.1 Door (fig. 52) Remove bottom hinge screw (1)
and pull the bottom door panel forwards and down to release it from top hinge pin (2).
7.1.3.2 Top panel (fig. 53) Slide top panel upwards to release
retaining clips (1).
7.1.3.3 Bottom cover plate (fig. 51) Remove two screws (1) and slacken
two screws (2). Slide cover forwards and drop
down to remove
7.1.3.4 Reassembly Reassemble in reverse order.
7.1.4 Removal of side casings
Remove front casing as in section
7.1.3. Remove screws (3, fig. 53)
Remove screws (4, fig. 53) and
retaining brackets. Slide side case panel upwards to
release retaining clips (2, fig. 53) and lift off. Reassemble in reverse order
7.1.5 Removal of combustion chamber
cover (fig. 54).
Remove front casing as in section
7.1.3, Remove four screws (2) securing
combustion chamber front cover Lift combustion chamber cover clear
of top retaining lugs and pull forward Remove combustion chamber cover
by first bringing the left side forward to clear boiler casing. Check condition of case seal and if
necessary replace before refitting Reassemble in reverse order,
ensuring that the combustion chamber front cover is correctly fitted and a good seal obtained.
7.1.7 Removal of heat exchanger front panel.
Remove the five screws (1 and 3,
fig. 47) securing the heat exchanger and remove the panel by gently pulling down and forward.
fig. 51
fig. 52
fig. 53
GW 611/0
GW 606/0
GW 605/0
7.1.6 Lower front control panel (fig. 54)
Remove front casing as in section
7.1.3, Undo screw (1) and lower control
box forward from top.
fig. 54
GW 613/0
33
Supplied By www.heating spares.co Tel. 0161 620 6677
7.2 Replacement of fan (fig. 55)
Isolate the boiler from the electrical
supply. Remove front casing as in section
7.1.3, and remove combustion chamber cover as in section 7.1.5.
Disconnect the electrical connections
from the fan. Remove the 2 fan securing screws
(4) and remove fan. Reassemble in reverse order.
Re-fit combustion chamber and front
casing. Carry out electrical checks (see
section 5.1).
7.3 Replacement of air pressure switch (fig. 56)
Isolate the boiler from the electrical
supply. Remove front casing as in section
7.1.3. Disconnect electrical connections to
pressure switch Remove screw (1) and lift out
pressure switch. Disconnect air tubes (2) fromswitch.
Reassemble in reverse order.
Carry out electrical checks (see
section 5.1).
fig. 55
fig. 56
GW 639/0-a
GW 640/0
Note: Air tubes should be reconnected P1 to white tube. P2 to blue tube. (P1 and P2 are marked on air pressure switch).
34
Supplied By www.heating spares.co Tel. 0161 620 6677
7.4 Replacement of burner
Isolate the boiler from the electrical
supply. Remove front casing as in section
7.1.3. Remove combustion chamber cover
as in section 7.1.5 Disconnect the ignition and flame
sensing electrode leads (1, fig. 57). Remove two screws (2, fig 57) and
pull burner forwards to remove. Reassemble in reverse order.
Carry out electrical checks (see
section 5.1) and check burner pressure (see section 5.8) and gas rate.
7.5 Replacement of electrodes
Isolate the boiler from the electrical
supply. Remove front casing as in section
7.1.3, and remove combustion chamber cover as in section 7.1.5
Remove heat exchanger front panel
as in section 7.1.7 Pull off HT lead (ignition electrode)
or sensing wire (flame sensing electrode) (1, fig 57)
Depress spring retaining clip (1, fig
58) gently pull electrode up and clear of burner.
To replace the electrode, depress
spring retaining clip (1, fig 58) and insert electrode until the "V" locates in the cross support (2, fig 58)
Carry out electrical checks (see
section 5.1).
fig. 57
GW 641/0
fig. 58
GW 642/0
35
Supplied By www.heating spares.co Tel. 0161 620 6677
7.6 Replacement of NTC temperature sensor
Note: The NTC temperature sensor is an extremely reliable component and as such is unlikely to fail. Before changing the NTC please check that it is defective - see section 8 - fault finding.
Disconnect boiler from electricity
supply. Remove front casing as in section
7.1.3 and remove combustion chamber cover as in section 7.1.5
Pull off connecting wire to sensor.
Unscrew NTC sensor. (4, fig 62)
Reassemble in reverse order.
Carry out electrical checks (see
section 5.1).
7.7 Replacement of gas valve
Isolate the boiler from the electrical
supply. Remove front casing as in section
7.1.3 Lower front control panel as in
section 7.1.6 Turn off the gas service valve (1, fig
50). Remove screw (5, fig. 59) and lift
off gas operator cover. Disconnect modulating coil wires at
plug provided and pull wires off gas operator. Disconnect air tube ( 7, fig. 59)
from operator. Disconnect ignition leads (3, fig.
65) from rear of control box. Remove three screws (1 + 2, fig.
65) and lift off control box rear covers. Disconnect main solenoid wires from main switchboard and boiler earth strip. Remove two screws (3, fig. 59)
Slacken retaining screw (8, fig. 59).
Rotate gas valve to the left and then
lift up to remove. Reassemble in reverse order.
Set burner pressure in accordance
with instructions supplied with spare part. Carry out electrical checks (see
section 5.1).and test all gas joints for soundness
fig. 59
GW 643/0
36
Supplied By www.heating spares.co Tel. 0161 620 6677
7.7.1 Replacement of main solenoid valve.
Isolate the boiler from the electrical
supply. Remove front casing as in section
7.1.3 Lower front control panel as in
section 7.1.6 Turn off the gas service valve
(1, fig. 50). Disconnect ignition leads (3, fig.65)
from rear of control box. Remove three screws (1+ 2, fig. 65)
and control box covers. Disconnect solenoid wires from
main switchboard and appliance earth strip.
Remove two screws (2, fig. 61)
and pull solenoid forward to remove from gas valve
Reassemble in reverse order.
Carry out electrical checks (see
section 5.1).and test all gas joints for soundness
7.7.2 Replacement of modulating valve
Isolate the boiler from the electrical
supply. Remove front casing as in section
7.1.3 . Lower front control panel as in
section 7.1.6 Turn off the gas service valve
(1, fig. 50). Remove screw (5, fig. 59) and lift
cover off gas valve. Disconnect modulating coil wires at
the connecting plug provided. Remove modulating valve by
unscrewing wheel adjuster from gas valve body.
Reassemble in reverse order.
Set burner pressure in accordance
with instructions supplied with spare parts.
Carry out electrical checks (see
section 5.1).and test all gas joints for soundness.
7.7.3 Replacement of gas operator
Isolate boiler from the electrical
supply. Remove front casing as in section
7.1.3. Lower front control panel as in
section 7.1.6. Turn off gas service valve (1, fig.
50). Remove screw (5, fig. 59) and lift
cover off gas valve. Disconnect two wires from gas
operator. Remove screws (1 and 3, fig. 60)
and pull operator forward to remove.
Reassemble in reverse order using
new cork gasket supplied with spare part.
Set burner pressure in accordance
with instructions supplied with spare part.
Carry out electrical checks (see
section 5.1) and test all gas joints for soundness.
7.8 Replacement of main heat exchanger
Turn off the boiler as in section
7.1.1. Remove front casing as in section
7.1.3 and remove combustion chamber cover as in section 7.1.5
Remove heat exchanger front panel
as in section 7.1.7 Release CH water pressure and
drain boiler as in section 7.1.2. Remove burner assembly as in
section 7.4. Pull off wire from NTC (4, fig. 62)
Disconnect flow and return
connections (3, fig 62) Slide the heat exchanger forward
to remove. Disconnect flow and return pipes
from the heat exchanger by rotating at joints (bayonet fix)
Reassemble in reverse order.
Recommission boiler (see section 5).
fig. 60
fig. 61
fig. 62
GW 643/0
GW 644/0
GW 641/0
37
Supplied By www.heating spares.co Tel. 0161 620 6677
7.9 Replacement of CH expansion vessel
In the unlikely event of a failure of the CH expansion vessel follow procedure
7.9.1 or 7.9.2 depending upon the
installation circumstances.
7.9.1. Boiler installed with air/flue
duct to left/right hand side, or vertical flue installation (where 300mm vertical clearance exists above the boiler).
Remove front casing as in section
7.1.3 Turn off the boiler as in section
7.1.1. Release CH water pressure and
drain boiler as in section 7.1.2. Remove combustion chamber cover
as in section 7.1.5 Remove 2 screws (2, fig 63).
Remove screw (1, fig. 56) to
release air pressure switch. Slide expansion vessel upwards
and out of boiler casing. Replace in reverse order.
Refill and repressurise the boiler
(see section 5.4).
7.9.2 Boiler installed with air flue duct to the rear, or vertical flue installation (where less than 300mm vertical clearance exists above the boiler)
EITHER Remove the boiler from the wall as follows:
Remove front casing as in section
7.1.3 Turn off the boiler as in section
7.1.1. Release CH water pressure and
drain boiler as in section 7.1.2. Lower front control panel as in
section 7.1.6 Disconnect external wiring from
boiler wiring terminal box. Disconnect flow and return
connections at compression connection above boiler CH service valves (1, fig. 64).and remove two screws securing retaining lug to appliance chassis (2, fig. 64)
Disconnect gas connection at
compression joint on top of gas service valve (3, fig. 64).
Disconnect domestic hot and cold
water connections (4, fig. 64) Disconnect the flue from the top of
boiler as described in section 4.6. Remove boiler from wall.
Remove screw (3, fig. 56) to
release air pressure switch. Remove two screws (2, fig. 63) and
slide expansion vessel upwards and out of boiler casing.
Reassemble in reverse order.
Re-mount the boiler (see section 4.5
and 4.6). Re-commission the boiler (see
section 5).
fig. 63
fig. 64
GW 639/0
GW 620/0
OR A suitable replacement expansion
vessel can be fitted externally to the boiler as described in Section 3.7.5 (if possible on the central heating return in an accessible position). In these circumstances, the replacement expansion vessel must be correctly sized ignoring the original expansion vessel which can be left in position on the boiler.
38
Supplied By www.heating spares.co Tel. 0161 620 6677
7.10 Replacement of transformer
Isolate boiler from the electricity
supply. Remove front casing as in section
7.1.3 Lower front control panel as in
section 7.1.6. Disconnect ignition leads (3, fig.
65) from rear of control box. Remove back of control box by
undoing the 3 screws (1 and 2, fig.
65). Unplug transformer (A, fig 67)
connecting lead from main switch board. Move clips (3, fig. 67) to the left and remove transformer from control box. Reassemble in reverse order.
Carry out electrical checks (see
section 5.1).
7.11 Replacement of overheat thermostat
Isolate the boiler from the electricity
supply. Remove front casing as in section
7.1.3. Lower front panel as in section
7.1.6. Pull wires off overheat thermostat
(2, fig 66). Unscrew overheat thermostat to
remove. Reassemble in reverse order.
Carry out electrical checks (see
section 5.1).
Pull pump forward to remove.
Fit new '0' rings (supplied with
pump) to pump connections. Re-assemble in reverse order.
Carry out electrical checks
(see section 5.1).
fig. 65
fig. 66
GW 614/0
GW 645/0
7.12 Replacement of pump
Remove front casing as in section
7.1.3. Turn boiler off as in section 7.1.1.
Release pressure and drain boiler
as in section 7.1.2. Lower front control panel as in
section 7.1.6. Disconnect ignition leads (3, fig.
65) from rear of control box. Remove back of control box by
undoing the 3 screws (1 and 2, fig. 65). Unplug pump wire from main
switchboard, and remove earth lead from earth strip. Undo the 3 pump screws (1, fig.
68).
fig. 67
fig. 68
GW 615/1X
GW 559/0
39
Supplied By www.heating spares.co Tel. 0161 620 6677
7.13 Replacement of automatic air release
Turn off boiler as in section 7.1.1.
Remove front casing as in section
7.1.3. Release CH water pressure and
drain boiler as in section 7.1.2. Lower front control panel as in
section 7.1.6. Unscrew cap (2, fig. 68) of auto air
release and remove inner components.
Replace with new inner
components and reassemble in reverse order.
Refill and repressurise the boiler
(see section 5.4).
7.14 Replacement of automatic bypass
Turn off boiler as in section 7.1.1.
Remove front casing as in section
7.1.3. Release CH water pressure and
drain boiler as in section 7.1.2. Lower front control panel as in
section 7.1.6. Remove spring clip (1, fig. 66).
Disconnect wires from overheat
thermostat (2, fig. 66). Remove temperature gauge phial
from primary flow pipe. Undo unions (3, fig. 66). Remove
bypass/connecting pipe. Undo union (1, fig. 69) to remove
bypass. Reassemble in reverse order using
sealing washers supplied. Refill and repressurise the boiler
(see section 5.4).
7.15 Replacement of diverter valve
Turn off boiler as in section 7.1.1.
Remove front casing as in section
7.1.3. Release CH water pressure and
drain boiler as in section 7.1.2. Open hot water taps.
Lower front control panel as in
section 7.1.6. Remove pump as in 7.12
Remove three screws (1, fig. 70)
and pump support bracket (2, fig.
70). Remove clip and disconnect pressure
tube (1, fig. 71) from divertervalve. Undo nut (2, fig. 71) and
disconnect pressure guage tube. Disconnect union (6, fig. 71).
Disconnect electrical connections
from DHW microswitch (3, fig 71). Remove clip (4, fig. 71) by pulling
down. Undo two unions (5, fig. 71).
Undo union (3, fig. 72).
Carefully pull diverter valve and
cold water inlet pipe away from DHW heat exchanger Lift valve and cold water inlet pipe (1, fig. 72) out of boiler.
Reassemble in reverse order.
Carry out electrical checks (see
section 5.1). Refill and repressurise the boiler
(see section 5.4).
fig. 69
fig. 70
fig. 71
GW 607/0
GW 646/0
GW 647/0
40
Supplied By www.heating spares.co Tel. 0161 620 6677
7.15.1 Replacement of water section diaphragm (fig. 72).
Turn off boiler as in Section 7.1.1.
Remove bottom cover as in section
7.1.3.3. Open hot water taps.
Remove clip (2), undo union (3)
Remove 6 screws (4).
Pull water section base away from
DHW heat exchanger and drop down. Remove diaphragm.
Replace in reverse order.
Carry out electrical checks (see
section 5.1). Refill and repressurise the boiler
(see section 5.4).
7.16 Replacement of pressure
and temperature gauge
Turn off boiler as in section 7.1.1.
Remove front casing as in section
7.1.3. Release CH water pressure and
drain boiler as in section 7.1.2. Lower front control panel as in
section 7.1.6. Undo union (2, fig 71) on diverter
valve to release pressure gauge tube. Remove temperature gauge phial
from pocket on primary flow pipe. Press spring clips on side of gauge
to remove from front panel. Replace in reverse order.
Refill and repressurise the boiler
(see section 5.4).
fig. 72
fig. 73
GW 635/0-a
GW 649/0
7.17 Replacement of differential
pressure switch
Turn off boiler as in section 7.1.1.
Remove front casing as in section
7.1.3. Release CH water pressure and
drain boiler as in section 7.1.2. Lower front control panel as in
section 7.1.6. Remove clip at rear of switch by
pulling it to the left. Disconnect wires from switch (1,
fig. 73). Pull pressure differential switch
forward to remove. Reassemble in reverse order.
Carry out electrical checks (see
section 5.1). Refill and repressurise the boiler
(see section 5.4).
41
Supplied By www.heating spares.co Tel. 0161 620 6677
7.18 Replacement of DHW microswitch.
Isolate appliance from electricity
supply. Remove front casing as in section
7.1.3. Lower front control panel as in
section 7.1.6. Lift off microswitch retaining ’bow’
spring, Pull microswitch forward to remove
from mounting bracket and disconnect wires.
Reassemble in reverse order.
Carry out electrical checks (see
section 5.1).
7.19 Replacement of DHW heat exchanger
Turn off boiler as in section 7.1.1.
Remove front casing as in section
7.1.3. Release CH water pressure and
drain boiler as in section 7.1.2. Lower front control panel as in
section 7.1.6. Unscrew the top two unions (1, fig.
74), bottom left hand union and backnut (2, fig. 74)
fig. 74
GW 650/1
Note: The connection between the DHW heat exchanger and water section is a push fit joint.
Pull heat exchanger.forwards to
remove. Reassemble in reverse order using
new sealing rings supplied. Refill and repressurise the boiler
(see Section 5.4).
42
Supplied By www.heating spares.co Tel. 0161 620 6677
7.20 Removal of printed circuit boards (PCBs)
Before commencing work on PCB replacements carry out the following:-
Diagnose which board requires
changing using the fault finding guide (see section 8: Fault finding).
Turn off the boiler as in section
7.1.1. Remove front casing as in section
7.1.3. Lower from control panel as in
section 7.1.6. Remove back of control box by
undoing the 3 screws (1 and 2, fig. 65).
7.20.1 Replacement of main
switchboard
Disconnect external wiring from
boiler terminal strip. Unplug 2 ribbon cables from
control board (2, fig. 75). Unplug all leads from the main
switchboard.(1, fig. 75) and lift switchboard carefully out of control box.
Reassemble in reverse order.
Note: When refitting the main switchboard ensure that the on/off control knob spindle (3, fig. 75) engages correctly into the on/off switch (5, fig. 75) mounted on the board.
Carry out electrical checks (see
section 5.1)
fig. 75
GW 615/0
7.20.2 Replacement of control board
Unplug 2 ribbon cables from
control board (2, fig. 76). Push four spring retaining clips
(5, fig. 76) out, and gently lift control board out of control box.
Reassemble in reverse order.
Note: When refitting the control board, ensure that the user control spindles (a, fig. 75) are aligned with the potentiometer and control switch holes (b, fig. 75) and that the locating rib of the potentiometer/switch correctly engages in the groove of the control knob spindle.
Carry out electrical checks
(see section 5.1)
fig. 76
GW 617/0
43
Supplied By www.heating spares.co Tel. 0161 620 6677
8. Fault finding
8.1 Introduction
The TURBOmax has built in diagnostic indicator lights (fig. 77) to assist you with fault finding in the unlikely event of a boiler malfunction. The lights will illuminate in sequence, indicating the operational status of the boiler e.g.
Power on indicator (green)
Illuminates when the electricity supply to the boiler is on, the main on/off control is set to position ( ) and the internal boiler fuses are o.k.
Hot water demand indicator (yellow)
Illuminates whenever there is a demand for hot water i.e. a hot water tap is opened.
Central heating demand indicator (yellow)
Illuminates whenever there is a demand for central heating i.e. the central heating control is set to positi­on ( ) and the external heating controls are calling for heat.
Note: If the external controls are not calling for heat (i.e. the room thermostat has reached temperature) this indicator will go out. This is perfectly normal.
8.2 Logical fault finding procedure
8.2.1 Preliminary Checks
These checks must be carried out before attempting to use the fault finding guide:-
1) Carry out electrical safety checks
(see Section 5.1: Preliminary electrical checks).
2) Check that the external electricity
supply to the boiler is on, and a supply of 230V~ is present between boiler terminals 'L' and 'N'.
3) Check that gas supply to the boiler
is on and that it has been correctly purged (see Section 5.2: Gas Supply).
4) Ensure the heating system is full of
water and charged to approx. 1 Bar. If not refill the system and vent (see section 5.4: Filling the heating system). Ensure boiler flow and return service valves are open.
5) Check that boiler main on/off
control is set to position ( )
6) Set boiler central heating control to Heating and Hot Water position ( )
7) Ensure that the Maximum Radiator Temperature and Maximum Hot Water Temperature controls are set to position '9'.
8) Check that all the external controls are on and calling for heat (if no external controls are fitted, boiler terminals 3 and 4 must be linked). Check that boiler anti-cycling 'economiser' control is not engaged (see Section 4.8.5).
8.2.2 Procedure
Note: Always check the operation of the boiler for central heating first before checking hot water operation. Do not open a hot tapunlessinstructed to by the fault finding guide.
Fan operation indicator (yellow)
Illuminates to indicate that the fan is operating and has been checked by the fan pressure switch,
Ignition indicator (yellow)
Illuminates when gas valve, operator and ignition transformer are energised. This indicator remains on during burner operation.
Flame indicator (yellow)
Illuminates when flame is recognised by the flame monitoring system
Burner lockout indicator (red)
Illuminates if the burner fails to light within 10 seconds of the ignition indicator. This light will also illuminate if the burner has been prevented from lighting due to lack of water or poor water circulation. To reset the appliance after a lockout, turn the central heating control to the reset position ( ) and release.
fig. 77
GW 618/0
44
Supplied By www.heating spares.co Tel. 0161 620 6677
Go to sheet C
Yes
Go to sheet C
Yes
No
Does green power
’on’ indicator ( ) glow
Is 230 V present across terminals L and N
No
Yes
Repair external
wiring fault
No
Check and if necessary replace 2A fuses
situated below boiler terminal strip (spare
fuse supplied with the appliance).
If fuse defective, suspect wiring fault on
external controls (see note 1)
Does green diode glow in the display now?
Go to sheet B
Sheet A Check electrical supply and appliance fuses
Ensure boiler main on/off control
is set to position ’ ’
NOTE 1
For test purposes, disconnect
external controls from terminals
3 - 4 and replace with a bridge
between these terminals. If
appliance then operates, the
fault is with the external controls.
45
Supplied By www.heating spares.co Tel. 0161 620 6677
Go to sheet C
Yes
Does green power ’on’ indicator ( )
glow now?
Yes
Check, replace 1,25 A fuse next to
the boiler terminal strip (spare fuse
provided with the appliance).
Reset overheat cut-off device by
pressing on the middle of the
Yes
No
transparent rubber cover.
Does green indicator now glow?
Yes
Check continuity of overheat
Yes
No
thermostat, replace if necessary.
Does green indicator now glow?
Check transformer (A, fig. 67):
230 V AC primary (black/grey) and
approx 17 V AC secondary (blue/brown)
Does green indicator now glow?
No
No No
Boiler on/off control defective,
replace main switchboard
46
Is 230 V present across boiler
terminals 3 and 5
Sheet B Check main on/off control, overheat Thermostat and anti-surge fuse
Replace main switch
board
Supplied By www.heating spares.co Tel. 0161 620 6677
Go to Sheet H
Yes
No
Does burner light?
Go to Sheet D
If the yellow central heating demand indicator ( )
still does not glow, replace main switchboard
Yes
No
Does yellow central heating demand indicator ( ) glow?
Check central heating control switch is set to position ( )
Yes
No
Is 230 V AC present across boiler
terminals 4 and 5?
External fault. Check whether all external controls are
calling for heat, replace or repair as necessary
(see also note 1, sheet A)
Sheet C Check Central Heating control and external controls
47
Supplied By www.heating spares.co Tel. 0161 620 6677
Go to Sheet H
Yes
Does burner light?
Yes
Go to Sheet E
No
NOTE 2
Before removing any water bearing
components, replace covers on electronic
control box.
48
No
Does pump run?
Sheet D Check operation of pump
Is red burner lockout
indicator ( ) glowing?
Yes
Turn central heating control
to position ( ) and release.
Yes
No
Turn boiler on/off control switch
off, then on again. Check maximum
radiator temperature control is set
high enough (e.g. 9)
Does pump now run?
No
Yes
Does pump run now?
No
No
Is 230 V~ present at the pump Plug
connection(x10) on the main switchboard
Yes
Check pump is not jammed.
Check/replace pump.
See note 2
Yes
Replace main switchboard
Supplied By www.heating spares.co Tel. 0161 620 6677
Go to Sheet H
Yes
Does burner
light?
Yes
Go to Sheet F
No
No
Replace
main
switchboard
Check NTC. Disconnect NTC
lead at plug (3, fig. 37), does
fan now run?
No
Does yellow ignition
indicator ( ) glow?
Yes
No
Check air/flue gas system is correctly
Defective switch
board.
Check/replace fan
Yes
fitted and not obstructed. Check Pitot
tube ( in fan outlet) and air hoses are not
obstructed and are correctly aligned.
Check or replace air pressure switch.
Yes
No
Yes
Check connection to
NTC temperature
sensor clean and
tight. If o.k, replace
NTC sensor
Yes
Switch main on/off control off and
on again. Does fan now operate?
Does yellow fan operation indicator ( ) glow?
Yes
No
Sheet E Check fan/flue gas system
Does fan run?
Is 230 V~present
No
across fan terminals?
No
Does yellow Central heating
demand indicator ( ) glow?
No heat demand, go to sheet C
49
Supplied By www.heating spares.co Tel. 0161 620 6677
Go to sheet H
Go to sheet G
Replace
main switchboard
Yes
No
Does sparking start
at burner?
No
Does red lockout indicator
Yes
Yes
( ) glow after 10 seconds?
Is gas solenoid
No
activated?
No
Is differential pressure
switch activated?
Yes
Yes
Has system been filled
with water?
No
Check for dirt or damage to the differential
pressure switch, supply tubes and diaphragm
Check continuity of
microswitch. Replace
if necessary. Check
Sheet F Check operation of differential pressure switch
50
Fill and vent
system and boiler
connection of plug X11
to main switchboard.
If burner still fails
to light, replace main
switchboard
Supplied By www.heating spares.co Tel. 0161 620 6677
Go to Sheet H
Flame supervision device
defective, replace main
switchboard
Go to Sheet H
Yes
No
No
Does burner light?
Does red lockout indicator ( ) glow
after 10 seconds?
Yes
Yes
No
Check all electrodes and leads for
damage and correct connection.
Reset lockout (turn central heating
control to position ( ) and release)
Does sparking commence at burner?
Replace if necessary
No
No
Does sparking commence at burner now?
Yes
Ignition tranformer on main
switchboard defective, replace main switchboard
Sheet G Check ignition system and gas section
51
Supplied By www.heating spares.co Tel. 0161 620 6677
Go Sheet J
Yes
No
Does burner flame modulate /
go out when maximum radiator
temperature control is turned
down to position 1 at a flow
temperature of approx. 50 °C?
Yes
Yes
No
Pull off cable from NTC and
short-circuit to earth. Is
flame extinguished?
Replace NTC-Sensor
Replace main switchboard
No
Does yellow flame indicator ( )
glow and flames increase in
size to full rate?
No
Yes
Is flame visible prior
Is flame extinguished
after 10s, and red
Sheet H Check operation of burner and modulation
lockout indicator ( ) lit
to lockout condition?
Check potentiometer for
partial load setting (see
5.9 C.H. range rating)
No
Check gas
supply is
live and
purged
Yes
Check/clean
burner,
ionization
sensor and
cable for
defects, good
Check cable plug-in connection
to modulating solenoid
No
contact and
correct position
Replace modulating solenoid of
gas valve if burner still fails to
Check
connections/
operation of
solenoid (200VDC)
Check air/flue
gas system is
correctly fitted
and not
increase to full rate.
and operator
(20VDC) replace
as necessary
obstructed. If
lockout still
occurs replace
mains switchboard
52
Supplied By www.heating spares.co Tel. 0161 620 6677
Normal operation
carry out electrical
safety checks
(See section 5.1
preliminary
electrical checks)
Check hot water flow rate
and temperature. Compare
with technical data. The
max temperature increase
is obtained with D.H.W.
thermostat on position 9.
If flow rate is not sufficient, check
incoming mains water supply
Yes
No
Does actuating lever operate
DHW microswitch on
diverter valve/water
section assembly?
Does yellow hot water demand
indicator ( ) glow?
Draw hot water at
high rate
Sheet J Check D.H.W. Operation
Yes
Check/replace DHW
microswitch
No
Check cold water inlet pressure
is sufficient. Check filter in cold
water inlet is clean. Check cold
water isolating valve (3, fig. 50) is
fully opened (turn anticlockwise).
Does lever move now?
Yes
No
No
Check/clean diaphragm and venturi
in the bottom part of the diverter
valve/water section; replace if necessary
Yes
Replace diverter section
53
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical diagrams
9.1 Functional Flow diagram: VUW 242 E / 282 E
S
fig. 78
54
GW 651/0
Supplied By www.heating spares.co Tel. 0161 620 6677
9.2 Wiring diagram: VUW 242 E / 282 E
Ignition
electrode
Flame
sensing
electrode
fig. 79
55
Supplied By www.heating spares.co Tel. 0161 620 6677
9.3 Schematic appliance circuit diagram: VUW 242 E / 282 E
fig. 80
56
GW 652/0
Supplied By www.heating spares.co Tel. 0161 620 6677
10. Short parts list
Key No. Description Part No. GC No.
01 Fan 19 0162 02 Air pressure switch 05 0557 03 Main heat exchanger VUW 242 06 4951 04 Main heat exchanger VUW 282 06 4952 05 Burner VUW 242 04 1960 06 Burner VUW 282 04 1961 07 Diverter valve 01 1269 08 DHW heat exchanger 06 4950 09 Ignition electrode 09 0562 10 Flame sensing electrode 09 0563 11 HT lead (ignition electrode) 09 1534 12 Expansion vessel 18 1045 13 Pump 16 1083 14 Gas valve (natural gas) 05 3210 15 Gas operator (natural gas) 05 0222 16 Main gas solenoid 17 0365 17 DHW microswitch 12 6255 18 Diaphragm 01 0357 19 Main switchboard 13 0391 20 Control board 13 0390 21 Main transformer 28 7442 22 NTC temperature sensor 25 2805 23 Temperature and pressure gauge 10 1558
fig. 81
fig. 84
GW 688/0
fig. 82
GW 696/0
fig. 85
GW 680/0
fig. 83
GW 694/0
fig. 86
GW 695/0
GW 687/0
57
Supplied By www.heating spares.co Tel. 0161 620 6677
fig. 87
GW 683/0
fig. 88
GW 684/0
fig. 89
GW 693/0
fig. 90
fig. 93
GW 686/0
fig. 91
GW 689/0
fig. 94
GW 691/0
fig. 92
GW 690/0
fig. 95
GW 682/1
GW 692/0
fig. 96
GW 685/0
fig. 97
58
GW 681/0
Supplied By www.heating spares.co Tel. 0161 620 6677
11. Supplementary
L.P.G. Appliances: information for TURBOmax
The appliance delivered is designed for use with LPG. Please read the instructions for installation therefore as follows:
VUW 242 EB VUW 282 EB
Related documents to be
supplemented by:
BS 5482: CP for domestic butane
and propane gas burning installations
Part 1: Installations in
permanent dwellings
Inlet pressure: Propane
37 mbar (14.6 inW.G.)
Technical Data
Type VUW VUW
242 E B 282 E B
Main burner jet size 16 x 7/075 18 x 7/075 number x mark.
Burner setting pressure 25.1 (9.9) Propane 26.6 (10.5) Propane mbar (in W.G.)
Restrictor 2 * 310 2 * 360 marking
Delivered gas
Propane G 31 MJ/m
Gross C.V. (s.t.) 95.65
Gas consumption (s.t.) 1.08 1.25 m3/h
2
59
Supplied By www.heating spares.co Tel. 0161 620 6677
HEATING, CONTROLS, HOT WATER
83 20 16 GB01
Head Office Vaillant Ltd., Vaillant House,
Medway City Estate, Trident Close, Rochester, Kent ME2 4EZ
Sales 01634 292310 Service Freephone 0800 318076 Technical Advice 01634 292392 Training 01634 292370
0796 V
Printed in Germany - Imprimé en Allemagne
Printed on 100 % recycled paper
Subject to alteration
We do not accept liability for damage arising as
a result of the non-observance of these instructions
Loading...