Vaillant TURBOmax Pro 28, TURBOmax Pro 2 E, TURBOmax Pro 28/2 E Instructions For Installation And Servicing

INSTRUCTIONS FOR
INSTALLATION AND SERVICING
TURBOmax Pro 28/2 E
Wall hung room sealed fan assisted combination boilers
The code of practice for the installation,
commissioning & servicing of central heating systems
0
2
TABLE OF CONTENTS
Introduction
Boiler Specification
General Requirements
Boiler Installation Sequence
General information . . . . . . . . . . . . . . . . . . . . . . . . . .5
EC designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
List of Contents
Contents included with boiler . . . . . . . . . . . . . . . . . . . .4
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Boiler connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Functional diagram . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Related documents . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Boiler location . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Flue system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Rear outlet flue system . . . . . . . . . . . . . . . . . . . .11
Top outlet flue system . . . . . . . . . . . . . . . . . . . .11
Extended top outlet flue system . . . . . . . . . . . . . .11
Flue termination . . . . . . . . . . . . . . . . . . . . . . . .12
Air supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Cupboard or compartment ventilation . . . . . . . . . . . . . .13
Electrical supply . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Guide to system requirements . . . . . . . . . . . . . . . . . . .14
Water circulation system . . . . . . . . . . . . . . . . . .14
Filling and make up . . . . . . . . . . . . . . . . . . . . .14
Pressure relief valve . . . . . . . . . . . . . . . . . . . . .14
Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . .14
Expansion vessel . . . . . . . . . . . . . . . . . . . . . . .15
Circulating pump . . . . . . . . . . . . . . . . . . . . . . .16
System by-pass . . . . . . . . . . . . . . . . . . . . . . . . .16
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
DHW expansion vessel accessory . . . . . . . . . . . .16
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Preparation of boiler location . . . . . . . . . . . . . . .17
Selecting position of boiler . . . . . . . . . . . . . . . . .17
Using boiler template . . . . . . . . . . . . . . . . . . . . . . . . .18
Fitting the boiler hanging bracket . . . . . . . . . . . . . . . . .19
Install the flue system . . . . . . . . . . . . . . . . . . . . . . . . .19
Fitting the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Removing boiler casing . . . . . . . . . . . . . . . . . . . . . . .20
Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Cold water mains inlet and hot water outlet . . . . . . . . . .22
Central heating flow and return pipework . . . . . . . . . . .23
Connecting the flue system to the boiler . . . . . . . . . . . .24
Electrical installation general requirements . . . . . . . . . . .25
Connecting to the main supply . . . . . . . . . . . . . . . . . .26
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Fit boiler casing . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Commissioning Part I
Preliminary electrical checks . . . . . . . . . . . . . . . . . . . .31
Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Water supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Filling the heating system . . . . . . . . . . . . . . . . . . . . . .33
Draining the heating system . . . . . . . . . . . . . . . . . . . .33
Initial system flush (`cold`) . . . . . . . . . . . . . . . . . . . . . .33
3
TABLE OF CONTENTS
Gas supply adjustments (Commissioning Part II)
Servicing
Fault Finding
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Logical fault finding procedure . . . . . . . . . . . . . . . . . .57
Fault finding charts . . . . . . . . . . . . . . . . . . . . . . . . . .58
Diagrams
Functional flow diagram . . . . . . . . . . . . . . . . . . . . . . .66
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Short parts list
Short parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
Initial inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Cleaning the burner and primary heat exchanger . . . . . .44
Parts replacement
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Initial preparation . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Gas valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Temperature sensors (NTCs) . . . . . . . . . . . . . . . . . . . .49
Main heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . .49
Expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Electronic control board . . . . . . . . . . . . . . . . . . . . . . .51
Main transformer . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Air pressure switch . . . . . . . . . . . . . . . . . . . . . . . . . .52
System bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Diverter valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Aqua sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
DHW heat exchanger . . . . . . . . . . . . . . . . . . . . . . . .55
Pressure relief valve . . . . . . . . . . . . . . . . . . . . . . . . . .55
Checking functions . . . . . . . . . . . . . . . . . . . . . . . . . .56
Functional checks (Commissioning Part III)
Functional checks . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Adjusting pump speed . . . . . . . . . . . . . . . . . . . . . . . .41
Final system flush (hot) . . . . . . . . . . . . . . . . . . . .41
Handing over to the user . . . . . . . . . . . . . . . . . . . . . .42
Gas inlet working pressure . . . . . . . . . . . . . . . . . . . . .34
Main burner pressure . . . . . . . . . . . . . . . . . . . . . . . . .35
Adjusting the central heating output (range rating) . . . . .36
Burner pressure and gas rate . . . . . . . . . . . . . . . . . . .37
4
LIST OF CONTENTS
Contents included with boiler
Ensure that all contents are included before commencing installation.
DO NOT remove the boiler from the polystrene base at this stage.
BEDIENUNGSANLEITUNG
BEDIENUNGSANLEITUNG
BEDIENUNGSANLEITUNG
BEDIENUNGSANLEITUNG
8
9
9
9
BEDIENUNGSANLEITUNG
Instructions for Use
7
10
6
1
2
5
4
I
0
3
Fig. L.1: Items supplied with unit
Table L.1: Items supplied with unit
Euro B/S 021/1 GB_Pro
Item Quantity Description
1 1 Boiler
2 1 Flue restriction rings
3 1 Cold water inlet valve
5 1 Copper tail for hot water outlet connection
6 1 Template
4 3 Flow and return service valve, gas service valve
7 1 Guarantee Card and Benchmark log book
8 1
Installation and connection accessories and PRV packages incl. DHW outlet union nut
9 3
Installation and Servicing, Users and Flue Installation Instructions
10 1 Hanging bracket
5
INTRODUCTION
The TURBOmax Pro is a fully automatic, wall mounted, room sealed combination boiler for central heating and domestic hot water. Domestic hot water is supplied directly from the boiler, without requiring a copper cylinder, cold water tank, feed and expansion tank and associated pipework. Domestic hot water has priority over central heating.
The boiler has been designed for use with a sealed central heating system, and comes fully tested and assembled with a built in circulating pump, expansion vessel and diverter valve.
The TURBOmax Pro has an output for domestic hot water of 28 kW. The boiler is easily sited on any internal wall and can be installed with either a horizontal or vertical RSF (room sealed fan assisted) flue. Two types of flue system are available, rear flue outlet, top outlet (with turret) concentric flue system (100 mm outside diameter) and an extended concentric flue system (125 mm outside diameter). Flue extensions and additional bends and elbows are available for both flue systems to increase the siting flexibility. The boiler is not suitable for external installation.
This boiler is available in Natural Gas. An optional LPG conversion kit is available.
If desired, an inhibitor may be used in the system. Guidance on the use of inhibitors is contained in these instructions.
The boiler contains a domestic hot water heat exchanger. The temperature in the heat exchanger is limited by the boiler control system and it is not necessary to install a
scale reducer on the cold mains to the boiler. However, in exceptionally hard water areas to prevent scale formation in the property hot water system pipework, a scale reducer may be fitted.
TURBOmax Pro combination boilers have a built in diagnostic system which indicates the operational status of the boiler. This feature provides key information to aid commissioning and fault finding.
The data badge is fitted on the rear of the control panel.
See text of General Requirements for installation requirements or notes.
Vaillant ltd. support the Benchmark initiative. Within the information pack, you will find a Benchmark Log Book. It is very important that this is completed correctly at the time of installation, commisioning and hando­ver to the user.
Note: This boiler must be installed and service by a competent person in accordance with the Gas Safety (Installation and Use) Regulations
1998. In the UK „CORGI“ registered installers undertake the work to a safe and satisfactory standard.
General Information
EC designation
TURBOmax Pro boilers (VUW GB 282/2-3) carry the „CE“ Mark. This demonstrates that the boilers fulfil the essential requirements of the Gas Appliance Directive (90/396/EEC) and the Gas Appliance (Safety) Regulations 1992.
The „CE“ Mark also demonstrates that the boilers comply with the requirements of the Electromagnetic Compatibility Directive (89/336/EEC), the Low Voltage Directive (72/23/EEC), the Boiler Efficiency Directive (92/42/EEC) and the Boiler (Efficiency) Regulations
1993.
6
BOILER SPECIFICATION
Technical data
TURBOmax Pro 28/2 E
( VUW GB 282/2-3)
Units
CH heat output range (80/60 °C)
10.4 - 28
(35 500 - 95 500)
kW (Btu/h)
DHW heat output 28 (95 500) kW (Btu/h) DHW flow rate T =35 °C rise 11.5 l/min DHW flow rate at factory set temperature rise (T 42 °C) 9.5 l/min Mains water pressure required for max. flow rate 0.5 bar Minimum water flow rate 1.5 l/min Mains water pressure required for min. flow rate 0.15 bar Maximum inlet water pressure 10 bar Inlet gas working pressure required (natural gas) 20 mbar
Gas burner pressure ignition rate 1.8 mbar Gas rate max. (DHW) 3.3 m3/h
Weight 45 kg Primary water content 2.0 l
Maximum CH heat input (net) 31.1 (106 200) kW (Btu/h)
Gas supply (G20) Gross CV (s.t.) 37.8 MJ/m
3
Gas burner pressure max. rate 10.8 mbar
CH temperature flow range 35 - 82 °C Minimum CH water flow (for 20 °C rise) 1203 l/h Pump pressure available 0.25 (25) bar (kPa) Expansion vessel pre-charge pressure 0.75 bar Maximum CH system pressure 3 bar
Electrical supply 230/50 V~/Hz­External fuse 3 A Power input 150 W
Maximum DHW heat input (net) 31.1 (106 200) kW (Btu/h)
Case height 800 mm Case width 440 mm Case depth 338 mm
7
BOILER SPECIFICATION
Boiler connections
0
7
6
310
592
145
6
5
100
100
35 35
432
130
180
1
148
8
543 21
Fig. B.1: Connection diameters
Euro B/S 024/2
Key: 1 Heating system return
(22 mm compression)
2 Cold water connection with shut
off valve (15 mm compression)
3 Gas connection (15 mm
compression)
4 Hot water connection
(15 mm tail)
5 Heating system flow
(22 mm compression)
6 Flue outlet (100 mm flue with
turret)
7 Hanging bracket 8 Rear flue outlet
8
BOILER SPECIFICATION
C
C
1
2
3
4
5 6
7
8
9
10
11
12
13 14
15
17 16
18
19
21
22
23
24
25
26
27
28
29
30
31
Functional Diagram
1 Air duct 2 Fan 3 Main heat exchanger 4 Temperature sensor (NTC I) 5 Flame sensing electrodes 6 Modulating burner 7 Fully modulating automatic gas
value
8 Maximum hot water temperature
control
9 Maximum radiator temperature
control
10 Diverter valve 11 DHW heat exchanger 12 Automatic bypass valve 13 CH flow service valve 14 Hot water outlet 15 Gas service valve 16 Service valve 17 Service valve 18 Pressure relief valve 19 Aqua sensor (DHW flow switch) 21 Main on/off control 22 Pressure gauge 23 Indicator lights 24 Expansion vessel 25 Expansion vessel charging valve 26 Circulating pump 27 Automatic air vent 28 Ignition electrode 29 Temperature sensor (NTC II) 30 Air pressure switch 31 Flue gas duct
Fig. B.2: Functional Diagram
Euro B/S 196/0
9
GENERAL REQUIREMENTS
Ensure that ALL regulations are observed.
Fig. R.1
Euro B/S 006/0_GB
Related Documents
The installation of the boiler must be in accordance with the relevant requirements of Gas Safety (Installation and Use) Regulations 1998, Health and Safety Document No. 635 (The Electricity at Work Regulations 1989), BS7671 (IEE Wiring Regulations) and the Water Supply (Water Fittings) Regulations. It should also be in accordance with the relevant requirements of the Local Authority, Building Regulations, Building Standards (Scotland) Regulations and the relevant recommendations of the following British Standards:
BS 5440: Flues and ventilation of gas fired boilers not exceeding 70 kW net:
- Part 1: Flues
- Part 2: Ventilation
BS 5449: Specification for forced circulation hot water for domestic premises.
BS 5546: Specification for gas hot water supplies for domestic premises.
BS 6700: Services supplying water for domestic use within buildings and their curtilages.
BS 6798: Specification for installation of gas fired boilers not exceeding 60 kW input.
BS 6891: Specification for installation of low pressure gas pipework up to 28 mm (R1) in domestic premises (2ndfamily gas).
BS 7593: Treatment of water in domestic hot water central heating systems. Institute of Gas Engineers Publication IGE/UP/7/1998: Guide for Installation in Timber Framed Housing.
Important: The appliance must be installed and serviced by a competent person as stated in the Gas Safety (Installation and Use) Regulations 1998.
Preliminary remarks
This appliance should only be installed in conjunction with a Vaillant flue system.
Install the flue system as detailed in the separate flue installation instructions supplied with this boiler.
10
GENERAL REQUIREMENTS
Gas Supply
The gas supplier should ensure the availability of an adequate supply of gas.
A gas meter may only be connected to the service pipe by the supplier of gas or their contractor.
An existing meter should be checked to ensure that it is capable of passing the rate of gas supply required.
Installation pipes should be fitted in accordance with BS 6891.
Pipework from the meter to the boiler must be of an adequate size. Do not use pipes of a smaller size than the boiler gas connection (15 mm).
The complete installation must be tested for soundness and purged as described in BS 6891.
Boiler location
The location chosen for the boiler must permit the provision of a satisfactory flue termination. The location must also provide adequate space for servicing and air circulation around the boiler. The boiler may be installed in any room, although particular attention is drawn to the requirements of BS7671 (IEE Regulations) and, in Scotland, the electrical provisions of the Building Standards (Scotland) Regulations, in respect of the installation of a boiler in a room containing a bath or shower.
Where the installation of the boiler will be in an unusual location, special procedures may be necessary and BS 5546 and BS 6798 give detailed guidance on this aspect. The boiler must be mounted on a flat, vertical wall, which must be sufficiently robust to take the weight of the boiler. The boiler may be installed on a combustible wall, subject to the requirements of the Local Authorities and Building Regulations. A compartment used to enclose the boiler must be designed and constructed specifically for this purpose. (An existing cupboard or compartment may be used provided that it is modified for the purpose). Details of essential features of cupboard/compartment design including airing cupboard installations are given in BS 6798. If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with Institute of Gas Engineers Publication IGE/UP/7/1998 „Guide for Gas Installation in Timber Framed Housing“.
Note: Where a room sealed boiler is installed in a room containing a bath or shower, any electrical switch or boiler control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
11
GENERAL REQUIREMENTS
Top outlet flue system (100 mm outside diameter)
The top outlet horizontal flue system (Art. No. 303 807) is suitable for installations up to 720 mm measured from the centre of the boiler flue outlet to the outside face of the wall. Flue extensions are available to extend this length up to 3.2 m. Both 90° bends and 45° elbows are also available to increase siting flexibility.
A vertical flue system is also available (Art. No. 303 800).
Refer to flue system installation instructions for full details.
Rear outlet flue system (100 mm outside diameter)
The rear outlet horizontal flue system (Art. No. 303 817) is suitable for installations up to 600 mm wall thickness.
Extended top outlet flue system (125 mm outside diameter)
A top outlet horizontal flue system of 125 mm outside diameter is also available (Art. No. 303 609) and can be used to achieve flue lengths of up to 10 m. Both 45° and 90° bends and elbows are also available to increase siting flexibility.
A vertical 125 mm concentric flue system is also available (Art. No. 303 600).
Refer to flue system installation instructions for full details.
Flue system
Note: The TURBOmax Pro boiler is delivered ready for installation utilising a top outlet flue assembly. For installation with a rear outlet flue assembly refer to the boiler flue outlet adaptation instructions supplied with the rear flue accessory.
48
800
48
4
Fig. R.2: Art.-No. 303 807
LAS Euro B/S 037/0
48
1285
603
Fig. R.3: Art.-No. 303 800
LAS Euro B/S 036/0
800
Fig. R.4: Art.-No. 303 817
LAS Euro B/S 073/0
Fig. R.5: Art.-No. 303 609
GU LAZ 082/0
70
1103
70
15
12
GENERAL REQUIREMENTS
Flue termination
The following details refer to both flue systems.
a. The terminal must be positioned
such that the products of combustion can disperse freely at all times.
b. In certain weather conditions a
plume of water vapour may be visible from the flue terminal. Positions where this could be a nuisance should be avoided.
c. If the terminal is fitted less than
2 m above a balcony, above ground or above a flat roof to which people have access then a suitable terminal guard; 280 mm x 280 mm deep, must be provided and fitted (made by Tower Flue Components, Tonbridge, TN9 1TB).
Note: Vertical flues must not terminate within 600 mm of an openable window, air vent or any other ventilation opening.
Where a terminal is fitted less than 1 m below a plastic gutter or less than 0.5 m below painted eaves or any other painted surface then a sui­table shield at least 1 m long should be fitted to protect the surface.
A
BCD
A G
H, I
F
J
B
F
M
L
L
K
K
G
G
F
F
E
A
A
Fig. R.6: Flue termination
Terminal position for fan-assisted flue (minimum distance)
mm
A
1)
300
B Below gutters, soil pipes or drain pipes 25 C Below eaves 25 D Below balconies (below car port roof) 25
E From vertical drain pipes and soil pipes 25
F From internal or external corners 25
G Above ground or balcony level 300
I From a terminal facing a terminal 1200
K Vertically from a terminal on the same wall 1500
L Horizontally from a terminal on the same wall 300
M Distance from adjacent wall for vertical Flue 500
GW 595/2
J
From an opening in a car port (e.g. door, window) into a dweling
1200
H From a surface or boundary facing a terminal 600*
Directly below an openable, above an opening or horizontal to an opening i.e. air brick, opening window or other , etc
Table R.1. Terminal position for a fan assisted concentric flue (see fig. R.6)
1)
In addition, the terminal should not be nearer than 150 mm to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window.
* BS 5440-1 It is recommended that a fanned flue
terminal should be positioned as follows: a) at least 2m from an opening in a building directly opposite, and b) so that the products of combustion are not directly directed to discharge across a boundary.
13
GENERAL REQUIREMENTS
Cupboard or compartment ventilation
TURBOmax Pro combination boilers are very high efficiency appliances. As a consequence the heat loss from the appliance casing during operation is very low. For cupboard or compartment installations it is therefore not necessary to provide any high or low level permanent air vents for cooling purposes.
Air supply
Detailed recommendations for air supply are given in BS 5440: Part 2.
It is not necessary to have an air vent in the room or internal space in which the boiler is installed.
Electrical supply
A 230 V, ~ 50 Hz single phase electricity supply fused to 3 Amp. must be provided in accordance with the latest edition of BS7671 (IEE Wiring Regulations) and any other local regulations that may apply.
The method of connection to the mains electricity supply must provide a means of completely isolating the boiler and its ancillary controls. Isolation is preferably by the use of a fused three pin plug and unswitched shuttered socket outlet, both complying with the requirements of BS 1363. Alternatively, a 3 Amp. fused doublepole switch with a 3 mm contact separation on both poles may be used.
This appliance must be earthed.
14
GENERAL REQUIREMENTS
Guide to system requirements
Water circulation system
Detailed recommendations for the water circulation system are given in BS 6798 and BS 5449: Part 1 (for small bore and micro bore central heating systems).
Pipework not forming part of the useful heating surface should be insulated to help prevent heat loss and possible freezing, particularly where pipes are run through roof spaces and ventilated underfloor spaces.
Draining taps must be located in accessible positions which permit the draining of the whole system including the boiler and the hot water system. Draining taps should be at least 1/2 in. BSP nominal size and be in accordance with BS 2879.
The boiler is suitable for use with minibore or microbore systems. Copper tubing to BS 2871: Part 1 should be used for water carrying pipework. All capillary joints in the DHW pipework must be made with lead free solder.
Particularly where a new boiler is to be fitted to an existing system, it is good practice that the system is thoroughly cleansed. This cleansing should take place prior to the fitting of the new boiler and be in accordance with BS 7593.
For advice on the application of system cleansers contact either Sentinel, Betz Dearborn Ltd. Widnes, Cheshire, WA8 8UD. Tel: 0151 495 1861 or Fernox Alpha-Fry Technologies Tandem House Marlow Way, Beddington Farm Road Croydon CRO 4xS Tel. 0870 601 5000 Fernox technical help line 01799 550811
Filling and make up
The system should be filled with water via a seperate filling point at a convienient position on the heating cicuit. The connection must be removed when filling is completed. Where local Water Authority regulation does not allow temporary connection, a sealed system filler pump with break tank must be used. The heating system will not be filled automatically from the domestic hot water side.
(Alternative methods of filling sealed systems are given in BS 5449).
Pressure relief valve
A pressure relief valve is provided with the boiler. This safety device is required on all sealed C.H. systems and is preset at 3 bar and provided with a 15 mm compression connec­tion for a discharge pipe, which must be of no less than 15 mm in diame­ter. The Pressure Relief Valve must not be used for draining purposes.
Pressure gauge
This is factory fitted to the boiler and indicates the primary circuit pressure to facilitate filling and testing.
15
GENERAL REQUIREMENTS
Expansion vessel
The 28 kW boiler incorporates a 10 litre expansion vessel which is suitable for a sealed heating system with a maximum water content of 100 litres.
If the nominal capacity of the built in expansion vessel is not sufficient for the heating system (for instance in case of modernisation of old open systems) an additional expansion vessel can be installed external to the boiler. It should be fitted in the return pipe as close as possible to the boiler in accordance with BS 5449: Part 1.
Guidance on the sizing of an additional expansion vessel is given in Table R.2.
Table R.2: Sizing of additional expansion vessel
Vessel Volume [L] Initial system pressure (bar) 1.0 1.5 Pressure relief valve setting (bar) 3.0
Total water content of system
litres
25
50 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500
2.7
5.4
10.9
13.6
16.3
19.1
21.8
24.5
27.2
30.0
32.7
35.7
38.1
40.9
43.6
46.3
49.0
51.8
54.5
3.9
7.8
15.6
19.5
23.4
27.3
31.2
35.1
39.0
42.9
46.8
50.7
54.6
58.5
62.4
66.3
70.2
74.1
78.0
For system volumes other than those given above, multiply the system volume by the factor across
0.109 0.156
16
GENERAL REQUIREMENTS
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400
50
100
150
200
250
300
350
400
450
500
550
600
650
700
Volume flow [l/min]
Lift [mbar]
setting II
setting I
Fig. R.7: Pump specifications
Euro B/S_VC_011/0GB
Pump specifications Circulating pump
The circulating pump is included in the boiler. The pump head available for the heating system is shown in fig. R.7.
System by-pass
A fixed system by-pass is included within the boiler. The boiler is suitable for use in systems with thermostatic radiator valves and no additional by-pass is required.
Venting
The boiler is fitted with an automatic air vent. Additional provision should be made to enable the heating system to be vented during filling and commissioning either by automatic air vents or manually.
DHW expansion vessel accessory
A DHW expansion vessel kit (Art.No 306 237) is available as an optional extra from Vaillant Ltd. This expansion vessel kit should be fitted to the boiler whenever, either a stop valve of the loose jumper type or a non return valve are present in the cold water mains supply to the boiler.
17
GENERAL REQUIREMENTS
150
5
200
500
5
I 0
0120
60
9030
°C
bar
4
3
2
1
0
Euro B/S 022/1
440
800
338
I 0
0 120
60
9030
°C
bar 4
3
2
1
0
Euro B/S 023/1
General
Preparation of boiler location
Clearances required
Mount the boiler on a flat and vertical area of wall of sufficient area for the boiler plus the required clearances for installation and servicing.
The clearances are as detailed below and are shown on the installation template supplied with the boiler:
- 150 mm below the boiler,
- 5 mm oneither side of the boiler,
- 210 mm on top of the boiler,
- 500 mm in front of the boiler.*
* Clearance is only required to
enable easier access to the boiler for servicing and may be provided by an openable door, etc.
Selecting position of boiler
Refer to „Boiler location“ for information regarding siting the appliance. In general the boiler must be positioned such that:
There is adequate space around
the boiler for service and maintenance.
The boiler can be correctly flued,
i.e. the flue terminal position is sited in accordance with the flue termination section (see page 12) and the air/flue duct can be installed in accordance with the flue installation instructions supplied.
All necessary pipework can be
connected, including the pressure relief valve.
Note: If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with Institute of Gas Engineers Publication IGE/UP/7/1998 „Guide for Gas Installations in Timber Framed Dwellings“.
Fig. I.2: Free space required for installation
Fig. I.1: Dimensions of boiler
Note: Should it be necessary to run
system pipework to above the boiler within the width of the casing, use the optional top connection accessory spacing frame.
5
5
210
124163 03240/242/280/282/824/828 Pro/Plus
60/100
07/2000
124163_03
1
3
2
18
BOILER INSTALLATION SEQUENCE
Using boiler template
Fix the paper template to the wall ensuring that the correct flue exit point has been identified, ensure that the template is vertical.
The template shows
- The position of the fixing holes for the boiler mounting bracket (1).
- The position of the connections.
- The position of the flue exit hole.
- Upper hole (2) indicates top outlet flue with flue turret facing rearward.
- Lower hole (3) indicates rear out­let flue exiting directly through wall.
Mark the position of the hanging bracket fixing holes (1).
Drill 2 holes Ø 8 mm for the hanging bracket.
Identify correct flue exit.
Mark the centre of the selected air/ flue duct and its circumference, e.g. by drilling through the template. For installation of a rear exit outlet please refer to the installation instruc­tions of the rear exit outlet kit (Art. No 303817).
Other flue options
Flue instructions for other flue systems such as vertical RSF flues, flues run to the side of the boiler and the use of additional bends etc. are detailed in the flue installation instructions provided with the boiler.
Remove the template from the wall and plug the drilled holes using the wallplugs supplied.
Note: Use alternative fixing holes where necessary.
Fig. I.3: Using Boiler template
I
0
3
320
131
22
26,5
27
131
105
105
1
2
0
120
60
90
30
°C
bar
4
3
2
1
0
Euro B/S 043/1
19
BOILER INSTALLATION SEQUENCE
Fig. I.4: Fitting the boiler
Fitting the boiler
Lift the boiler (3) up to the wall so
that it is slightly above the hanging bracket (1).
Lower the boiler slowly onto the
hanging bracket so that the cross member at the rear of the boiler fully engages onto the hanging bracket.
Note: Lift the boiler from either side at the bottom edge.
Install the flue system
Install the flue system (refer to separate air/flue duct installation instructions).
Fitting the boiler hanging bracket
Fix the hanging bracket (2) to the wall using the screws supplied. (it may be necessary to use additional or alternative fixings to ensure adequate support).
Note: If the boiler is to be fitted in a timber framed building ensure that the bracket is secured to a substantial part of the timber frame capable of taking the weight of the boiler.
3
I
0
2
I
0
90°90°
1
Euro B/S 041/1
Fig. I.5: Remove of boiler casing
20
BOILER INSTALLATION SEQUENCE
Removing boiler casing
Turn both securing fasteners (1)
anti-clockwise by 90° to release control panel.
Lower control panel (2).
Pull the case (3) forward at the
bottom to disengage from the securing clips.
Lift the case slightly to clear the top
locations and pull forward to remove.
21
BOILER INSTALLATION SEQUENCE
Gas supply
Connect the 15 mm compression
gas service cock (1) supplied with appliance and tighten.
Connect a gas supply pipe of not
less than 15 mm diameter to the inlet of the gas service cock.
Tighten all connections.
(Ensure the gas supply pipework is adequately sized such that a 20 mbar gas pressure is available at the boiler inlet at full flow rate).
I
0
1
2
Euro B/S 046/0GB_Pro
Fig. I.6: Fitting the gas connection
22
BOILER INSTALLATION SEQUENCE
Cold water mains inlet and hot water outlet
Flush all foreign matter from the mains supply before connecting to the boiler.
Connect the cold water service
valve (1) to the cold inlet water connection of the appliance with the washer (2) provided and tigh­ten.
Connect cold water service pipe to
the cold water service valve and tighten.
Connect the 15 mm hot water
outlet copper tail (4) to the hot water outlet connection of the appliance with the washer (5) pro­vided and tighten.
Connect hot water outlet pipework
to the copper tail.
Note: The hot water outlet union nut is packed in with the PRV fittings pack.
1
2
3
4
5
6
I
0
Euro B/S 045/0GB_Pro
Fig. I.7: Fitting the hot and cold water connections
Loading...
+ 50 hidden pages