Vaillant turboMAX pro 24/2 E, turboMAX pro 28/2 E Instructions For Installation And Servicing

For the installer
Instructions for Installation and Servicing
turboMAX pro
Wall hung room sealed fan assisted
combination and system boilers
24/2 E 28/2 E
GB
Table of Contents
1 List of Contents . . . . . . . . . . . . . . . . . . . . . 3
1.1 Contents included with boiler (turboMAX pro)3
2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 General Information . . . . . . . . . . . . . . . . . . . . . 4
2.2 EC designation . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Boiler Specification . . . . . . . . . . . . . . . . . . . 5
3.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Boiler connections . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Functional diagram . . . . . . . . . . . . . . . . . . . . . . 6
4 General Requirements . . . . . . . . . . . . . . . . . 7
4.1 Related documents . . . . . . . . . . . . . . . . . . . . . . 7
4.2 Boiler location . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.3 Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.4 Flue system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.4.1 Top outlet flue system . . . . . . . . . . . . . . . . . . . . 8
4.4.2 Rear outlet flue system . . . . . . . . . . . . . . . . . . . 8
4.4.3 Extended top outlet flue system . . . . . . . . . . . 8
4.4.4 Flue termination . . . . . . . . . . . . . . . . . . . . . . . . 9
4.5 Air supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.6 Cupboard or compartment ventilation . . . . . . 9
4.7 Electrical supply . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.8 Guide to system requirements . . . . . . . . . . . . . 10
4.8.1 Water circulation system . . . . . . . . . . . . . . . . . . 10
4.8.2 Filling and make up . . . . . . . . . . . . . . . . . . . . . . 10
4.8.3 Pressure relief valve . . . . . . . . . . . . . . . . . . . . . 10
4.8.4 Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.8.5 Expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . 10
4.8.6 Circulating pump . . . . . . . . . . . . . . . . . . . . . . . . 11
4.8.7 System by-pass . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.8.8 Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7 Gas supply adjustments (Commissioning Part II) 21
7.1 Gas inlet working pressure . . . . . . . . . . . . . . . . 21
7.2 Main burner pressure . . . . . . . . . . . . . . . . . . . . 21
7.3 Adjusting the central heating output
(range rating) . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.4 Burner pressure and gas rate . . . . . . . . . . . . . . 23
7.5 Fit combustion chamber cover . . . . . . . . . . . . . 24
7.6 Fit boiler casing . . . . . . . . . . . . . . . . . . . . . . . . . 24
8 Functional checks (Commissioning Part III) . 25
8.1 Functional checks . . . . . . . . . . . . . . . . . . . . . . . 25
8.2 Functional check of operation . . . . . . . . . . . . . 25
8.3 Adjusting pump speed . . . . . . . . . . . . . . . . . . . . 26
8.4 Handing over to the user . . . . . . . . . . . . . . . . . 26
9 Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9.1 Initial inspection . . . . . . . . . . . . . . . . . . . . . . . . . 27
9.2 Cleaning the burner and primary heat
exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
10 Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . 29
10.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10.2 Logical fault finding procedure . . . . . . . . . . . . 29
11 Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11.1 Functional flow diagram . . . . . . . . . . . . . . . 37
11.2 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Benchmark gas boiler commissioning
checklist..................................... 39
5 Boiler Installation Sequence . . . . . . . . . . . . 12
5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 Using boiler template . . . . . . . . . . . . . . . . . . . . 13
5.3 Fitting the boiler hanging bracket . . . . . . . . . . 13
5.4 Install the flue system . . . . . . . . . . . . . . . . . . . . 14
5.5 Fitting the boiler . . . . . . . . . . . . . . . . . . . . . . . . 14
5.6 Removing boiler casing . . . . . . . . . . . . . . . . . . . 14
5.7 Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.8 Cold water mains inlet and hot water outlet . . 15
5.9 Central heating flow and return pipework . . . 15
5.10 Connect the flue system to the boiler . . . . . . . 16
5.11 Electrical installation . . . . . . . . . . . . . . . . . . . . . 16
5.12 Connection to the main supply . . . . . . . . . . . . 16
5.13 Electronic board layout . . . . . . . . . . . . . . . . . . . 17
5.14 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6 Commissioning Part I . . . . . . . . . . . . . . . . . 20
6.1 Preliminary electrical checks . . . . . . . . . . . . . . 20
6.2 Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.3 Cold water supply . . . . . . . . . . . . . . . . . . . . . . . 20
6.4 Filling the heating system . . . . . . . . . . . . . . . . . 20
6.5 Initial system flush („cold“) . . . . . . . . . . . . . . . 20
Instructions for Installation and Servicing turboMAX pro R32
1 List of contents
8
7
6
1
2
5
4
I
0
3
9
10
1.1 Contents included with boiler
Ensure that all contents are included before commen­cing installation.
Note! DO NOT remove the boiler from the polystrene base at this stage.
List of contents 1
Fig. 1.1: Items supplied with unit (turboMAX pro)
Item Quantity Description
1 1 Boiler
2 1 Flue restriction ring
3 1 Cold water inlet valve
4 3 Flow and return service value, gas service
valve
5 5 Copper tails for water outlet connection
6 1 Template
7 1 Guarantee Card
8 1 Installation and connection accessories and
PRV packages incl. DHW outlet union nut
9 3 Installation and Servicing, Users and Flue
Installation Instructions
10 1 Hanging bracket
Instructions for Installation and Servicing turboMAX pro R3 3
2 Introduction
2 Introduction
2.1 General Information
Note! This boiler must be installed and serviced by a competent person in accordance with the Gas Safety (Installation and Use) Regulations 1998. In the UK „CORGI“ registered installers under­take the work to a safe and satisfactory standard.
The turboMAX pro is a fully automatic, wall mounted, room sealed combination boiler for central heating and domestic hot water. Domestic hot water is supplied directly from the boiler, without requiring a copper cylinder, cold water tank, feed and expansion tank and associated pipework. Domestic hot water has priority over central heating. The boiler has been designed for use with a sealed central heating system, and comes fully tested and assembled with a built in circulating pump, expansion vessel and diverter valve. The turboMAX pro has an output for domestic hot water of 24 or 28 kW. The boiler is easily sited on any internal wall and can be installed with either a horizontal or vertical RSF (room sealed fan assisted) flue. Two types of flue system are available, rear flue outlet, top outlet (with turret) concentric flue system (100 mm outside diameter) and an extended concentric flue system (125 mm outside diameter). Flue extensions and additio­nal bends and elbows are available for both flue systems to increase the siting flexibility. The boiler is not suitable for external installation. This boiler is available in Natural Gas. An optional LPG conversion kit is available. If desi­red, an inhibitor may be used in the system. Guidance on the use of inhibitors is contained in these instructions. The boiler contains a domestic hot water heat exchan­ger. The temperature in the heat exchanger is limited by the boiler control system and it is not necessary to install a scale reducer on the cold mains to the boiler. However, in exceptionally hard water areas to prevent scale formation in the property hot water system pipe­work, a scale reducer may be fitted. turboMAX pro combination boilers have a built in dia­gnostic system which indicates the operational status of the boiler. This feature provides key information to aid commissioning and fault finding.
The data badge is fitted on the rear of the control panel. See text of General Requirements for installation requi­rements or notes. Vaillant ltd. support the Benchmark initiative. In this installation manual you will find the Benchmark gas boiler commissioning checklist. It is very important that this is completed correctly at the time of installati­on and commissioning..
Important! When tightening or slackening screwed connec­tions always use suitable open-ended spanners (not pipe wrench, or extensions, etc.). Incorrect use and/or unsuitable tools can lead to damage being caused (e.g. gas or water leakage)!
2.2 EC designation
turboMAX pro (24/28) a carry the "CE" Mark. This demonstrates that the boilers fulfil the essential require­ments of the Gas Appliance Directive(90/396/EEC) and the Gas Appliance (Safety) Regulations 1992.
The "CE" Mark also demonstrates that the boilers comp­ly with the requirements of the Electromagnetic Compatibility Directive (89/336/EEC), the Low Voltage Directive (72/23/EEC), the Boiler Efficiency Directive (92/42/EEC) and the Boiler (Efficiency) Regulations 1993.
Instructions for Installation and Servicing turboMAX pro R34
Boiler Specification 3
3 Boiler Specification
3.1 Technical Data
turboMAX pro 24/2 E turboMAX pro 28/2 E Units (VUW GB 242/2-3) (VUW GB 282/2-3)
Maximum CH heat input (net) 29.7 (101.000) 31.1 (106.200) kW (Btu/h)
CH heat output range (80/60 °C) 8.9 - 24 10.4 - 28
(30.400 - 81.900) (35.500 - 95.500) kW (Btu/h)
Maximum DHW heat input (net) 26.7 (91.200) 31.1 (106.200) kW (Btu/h)
SEDBUK Band D D
SAP Seasonal Efficiency 79.6 79.7 %
DHW heat output 24 28 kW
DHW flow rate T = 35 °C rise 9.8 11.5 l/min
DHW flow rate at factory set
temperature rise (T 42 °C) 8.2 9.5 l/min
Mains water pressure required
for max. flow rate 0.5 0.5 bar
Minimum water flow rate 1.5 1.5 l/min
Mains water pressure required
for min. flow rate 0.15 0.15 bar
Maximum inlet water pressure 10 10 bar
Inlet gas working pressure
required (natural gas) 20 20 mbar
Gas supply (G20) Gross CV (s.t.) 37.8 37.8 MJ/m
Gas burner pressure max. rate (natural gas) G 20 9.8 10.8 mbar
(LPG 3+) G 30/31 28 - 30/37 28 - 30/37 mbar
Gas burner pressure ignition rate G 20 1.9 1.8 mbar
G 30/31 3.9/5.4 3.8/5.3 mbar
Gas rate max. (DHW) - 2.8 3.3 m3/h
CH temperature flow range 35 - 82 35 - 82 °C
Minimum CH water flow
(for 20 °C rise) 1032 1203 l/h
Pump pressure available 0.25 (25) 0.25 (25) bar (KPa)
Expansion vessel
pre-charge pressure 0.75 0.75 bar
Maximum CH system pressure 3 3 bar
Weight 42 45 kg
Primary water content 2.0 2.0 l
Electrical supply 230/50 230/50 V~/Hz
External fuse 3 3 A
Power input 150 150 W
Case height 800 800 mm
Case width 440 440 mm
Case depth 338 338 mm
3
Instructions for Installation and Servicing turboMAX pro R3 5
3 Boiler Specification
C
C
1
2
3
4
5
6
7
8
9
10
11
12
13 14
15
17 16
18
19
21
22
23
24
25
26
27
28
29
30
31
0
7
6
264638
145
6
5
100
100
35 35
432
130
180
1
148
8
543 2 1
902
3.2 Boiler connections
3.3 Functional Diagram
Fig. 3.1: Connection diameters turboMAX pro
Key: 1 Heating system return (22 mm tail) 2 Cold water connection with shut off valve
(15 mm tail) 3 Gas connection (15 mm tail) 4 Hot water connection (15 mm tail) 5 Heating system flow (22 mm tail)
Fig. 3.2: Functional Diagram
6 Flue outlet (100 mm flue with turret) 7 Hanging bracket 8 Rear flue outlet
1 Air duct 2Fan 3 Main heat exchanger 4 Temperature sensor (NTC I) 5 Flame sensing electrodes 6 Modulating burner 7 Fully modulating automatic gas value 8 Maximum hot water temperature control 9 Maximum radiator temperature control 10 Diverter valve 11 DHW heat exchanger 12 Automatic bypass valve 13 CH flow service valve 14 Hot water outlet 15 Gas service valve 16 Cold water service valve 17 CH return service valve 18 Pressure relief valve 19 Aqua sensor (DHW flow switch) 21 Main on/off control 22 Pressure gauge 23 Indicator lights 24 Expansion vessel 25 Expansion vessel charging valve 26 Circulating pump 27 Automatic air vent 28 Ignition electrode 29 Temperature sensor (NTC II) 30 Air pressure switch 31 Flue gas duct
Instructions for Installation and Servicing turboMAX pro R36
General Requirements 4
4 General Requirements
4.1 Related Documents
The installation of the boiler must be in accordance with the relevant requirements of Gas Safety (Installation and Use) Regulations 1998, Health and Safety Document No. 635 (The Electricity at Work Regulations 1989), BS7671 (IEE Wiring Regulations) and the Water Supply (WaterFittings) Regulations. It should also be in accor­dance with the relevant requirements of the Local Authority, Building Regulations, Building Standards (Scotland) Regulations and the relevant recommendati­ons of the following British Standard; Including current amendments to Approved Documents Part L and J.:
BBSS 55444400::
exceeding 70 kW net:
- Part 1: Flues
- Part 2: Ventilation
BBSS 55444499::
for domestic premises.
BBSS 55554466::
domestic premises.
BBSS 66770000::
within buildings and their curtilages.
BBSS 66779988::
boilers not exceeding 70 kW input net.
BBSS 66889911::
gas pipework up to 28 mm (R1) in domestic premises
nd
family gas).
(2
BBSS 77559933::
central heating systems.Institute of Gas Engineers Publication IGE/UP/7/1998: Guide for Installation in Timber Framed Housing. Benchmark Code of Practice. Building Regulations Approved Documents Part L 2002 Part J 2002.
Flues and ventilation of gas fired boilers not
Specification for forced circulation hot water
Specification for gas hot water supplies for
Services supplying water for domestic use
Specification for installation of gas fired
Specification for installation of low pressure
Treatment of water in domestic hot water
Important!
The appliance must be installed and serviced by a competent person as stated in the Gas Safety
(Installation and Use) Regulations 1998.
Standards (Scotland) Regulations, in respect of the installation of a boiler in a room containing a bath or shower.
Note! Where a room sealed boiler is installed in a room containing a bath or shower, any electrical switch or boiler control utilising mains electrici­ty should be so situated that it cannot be tou­ched by a person using the bath or shower.
Where the installation of the boiler will be in an unusual location, special procedures may be necessary and BS 5546 and BS 6798 give detailed guidance on this aspect. The boiler must be mounted on a flat, vertical wall, which must be sufficiently robust to take the weight of the boiler. The boiler may be installed on a combustible wall, subject to the requirements of the Local Authorities and Building Regulations. A compartment used to enclose the boiler must be desi­gned and constructed specifically for this purpose. (An existing cupboard or compartment may be used provi­ded that it is modified for the purpose). Details of essen­tial features of cupboard/compartment design including airing cupboard installations are given in BS 6798. If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with Institute of Gas Engineers Publication IGE/UP/7/1998 „Guide for Gas Installation in Timber Framed Housing“.
4.3 Gas Supply
The gas supplier should ensure the availability of an adequate supply of gas. A gas meter may only be connected to the service pipe by the supplier of gas or their contractor. An existing meter should be checked to ensure that it is capable of passing the rate of gas supply required. Installation pipes should be fitted in accordance with BS
6891. Pipework from the meter to the boiler must be of an adequate size. Do not use pipes of a smaller size than the boiler gas connection (15 mm). The complete installation must be tested for soundness and purged as described in BS 6891.
Preliminary remarks
This appliance should only be installed in conjunction with a Vaillant flue system. Install the flue system as detailed in the separate flue installation instructions supplied with this boiler.
4.2 Boiler location
The location chosen for the boiler must permit the provision of a satisfactory flue termination. The location must also provide adequate space for servicing and air circulation around the boiler. The boiler may be installed in any room, although particular attention is drawn to the requirements of BS7671 (IEE Regulations) and, in Scotland, the electrical provisions of the Building
Instructions for Installation and Servicing turboMAX pro R3 7
4.4 Flue system
Note! The boilers are delivered ready for installation utilising a top outlet flue assembly. For installa­tion with a rear outlet flue assembly refer to the boiler flue outlet adaptation instructions supplied with the rear flue accessory.
4 General Requirements
70
1103
70
15
48
1285
603
4.4.1 Top outlet flue system (100 mm outside diameter)
The top outlet horizontal flue system (Art. No. 303 807) is suitable for installations up to 720mm measured from the centre of the boiler flue outlet to the outside face of the wall. Flue extensions are available to extend this length up to 4.5 m for 24 kW and 3.2 m for 28 kW. Both 90° bends and 45° elbows are also available to increase siting flexibility. A vertical flue system is also available (Art. No. 303 800).Refer to flue system installation instructions for full details.
800
48
4
48
Fig. 4.1: Art.-No. 303 807
A vertical flue system is also available (Art. No. 303 800). Refer to flue system installation instructions for full details.
4.4.2 Rear outlet flue system (100 mm outside diameter)
The rear outlet horizontal flue system (Art. No. 303 817) is suitable for installations up to 600 mm wall thickness.
800
Fig. 4.3: Art.-No. 303 817
4.4.3 Extended top outlet flue system (125 mm outside diameter)
A top outlet horizontal flue system of 125 mm outside diameter is also available (Art. No. 303 609) and can be used to achieve flue lengths of up to 12.9 m for 24 kW; 10 m for 28 kW. Both 45° and 90° bends and elbows are also available to increase siting flexibility. A vertical 125 mm concentric flue system is also availa­ble (Art. No. 303 600). Refer to flue system installation instructions for full details.
Fig. 4.2: Art.-No. 303 800
Fig. 4.4: Art.-No. 303 609
Instructions for Installation and Servicing turboMAX pro R38
General Requirements 4
A
BCD
A
G
H, I
F
J
B
F
M
L
L
K
K
G
G
F
F
E
A
A
4.4.4 Flue termination
The following details refer to both flue systems. a. The terminal must be positioned such that the pro-
ducts of combustion can disperse freely at all times.
b. In certain weather conditions a plume of water
vapour may be visible from the flue terminal. Positions where this could be a nuisance should be avoided.
c. If the terminal is fitted less than 2 m above a bal-
cony, above ground or above a flat roof to which people have access then a suitable terminal guard; 280 mm x 280 mm x 270 mm deep, must be provi­ded and fitted (made by Tower Flue Components, Tonbridge, TN9 1TB).
Note! Vertical flues must not terminate within 600 mm of an openable window, air vent or any other ventilation opening.
The flue assembly shall be so placed or shielded as to prevent ignition or damage to any part of the building.
Terminal position for fan-assisted flue (minimum distance) mm
A1)Directly below an openable, above an opening
or horizontal to an opening i.e. air brick, opening
window or other, etc 300
B Below gutters, soil pipes or drain pipes 25
C Below eaves 25
D Below balconies (below car port roof) 25
E From vertical drain pipes and soil pipes 25
F From internal or external corners 25
G Above ground or balcony level 300
H From a surface or boundary facing a terminal 600*
H From a terminal facing a terminal 1200
J From an opening in a car port (e.g. door, window)
into a dweling 1200
K Vertically from a terminal on the same wall 1500
L Horizontally from a terminal on the same wall 300
M Distance from adjacent wall for vertical Flue 500
1) In addition, the terminal should not be nearer than 150mm to an
opening in the building fabric formed for the purpose of accommodating a built-in element such as a window.
* BS 5440-1 It is recommended that a fanned flue terminal should
be positioned as follows: a) at least 2m from an opening in a buil­ding directly opposite, and b) so that the products of combustion are not directly directed to discharge across a boundary.
4.5 Air supply
Detailed recommendations for air supply are given in BS 5440: Part 2. It is not necessary to have an air vent in the room or internal space in which the boiler is installed.
Fig. 4.5: Flue termination
4.6 Cupboard or compartment ventilation
The boilers are very high efficiency appliances. As a con­sequence the heat loss from the appliance casing during operation is very low. For cupboard or compartment in­stallations it is therefore not necessary to provide any high or low level permanent air vents for cooling purposes.
4.7 Electrical supply
A 230 V, ~ 50 Hz single phase electricity supply fused to 3 Amp. must be provided in accordance with the latest edition of BS7671 (IEE Wiring Regulations) and any other local regulations that may apply. The method of connection to the mains electricity supp­ly must provide a means of completely isolating the boi­ler and its ancillary controls. Isolation is preferably by the use of a fused three pin plug and unswitched shutte­red socket outlet, both complying with the requirements of BS 1363. Alternatively, a 3 Amp. fused doublepole
Instructions for Installation and Servicing turboMAX pro R3 9
switch with a 3 mm contact separation on both poles may be used.
4 General Requirements
Important! This appliance must be earthed.
4.8 Guide to system requirements
4.8.1 Water circulation system
Detailed recommendations for the water circulation system are given in BS 6798 and BS 5449: Part 1 (for small bore and micro bore central heating systems).
Pipework not forming part of the useful heating surface should be insulated to help prevent heat loss and possible freezing, particularly where pipes are run through roof spaces and ventilated underfloor spaces. Draining taps must be located in accessible positions which permit the draining of the whole system including the boiler and the hot water system. Draining taps should be at least 1/2 in. BSP nominal size and be in accordance with BS 2879. The boiler is suitable for use with minibore or microbore systems. Copper tubing to BS 2871: Part 1 should be used for water carrying pipework. All capillary joints in all DHW pipework must be made with lead free solder. Particularly where a new boiler is to be fitted to an existing system, it is good practice that the system is thoroughly cleansed.
Important: To prevent the formation of deposits and pre­vent serious damage to the appliance and system , cleansers must be used carefully and must be completely removed by thoroughly flushing the system. Cleansers should only be left in systems for a maximum of 24 hours.
This cleansing must take place prior to the fitting of the new boiler and be in accordance with BS 7593. For advice on the application of system cleansers contact either Sentinel, GE Betz. Widnes, Cheshire, WA8 8UD. Tel: 0151 420 9595
4.8.2 Filling and make up
The system can be filled using the built in filling loop. The connection must be removed when filling is completed. Where local Water Authority regulation does not allow temporary connection, a sealed system filler pump with break tank must be used. The heating system will not be filled automatically from the domestic hot water side. (Alternative methods of filling sealed systems are given in BS 5449).
4.8.3 Pressure relief valve
A pressure relief valve is provided with the boiler. This safety device is required on all sealed C.H. systems and is preset at 3 bar and provided with a 15 mm compression connection for a discharge pipe, which must be of no less than 15 mm in diameter. The Pressure Relief Valve must not be used for draining purposes.
4.8.4 Pressure gauge
This is factory fitted to the boiler and indicates the primary circuit pressure to facilitate filling and testing.
4.8.5 Expansion vessel
The 24 kW boiler incorporate a 6 litre expansion vessel which is suitable for a sealed heating system with a maximum water content of 60 litres. A 10 litre expansion vessel kit is available as an optional accessory. The 28 kW boilers incorporate a 10 litre expansion vessel which is suitable for a sealed heating system with a maximum water content of 100 litres. If the nominal capacity of the built in expansion vessel is not sufficient for the heating system (for instance in case of moder­nization of old open systems) an additional expansion vessel can be installed external to the boiler. It should be fitted in the return pipe as close as possible to the boiler in accordance with BS 5449: Part 1. Guidance on the sizing of an additional expansion vessel is given in Table.
Vessel Volume [L] Initial system pressure (bar) 1.0 1.5 Pressure relief valve setting (bar) 3.0
Total water content of system ltres
25 2.7 3.9
50 5.4 7.8
100 10.9 15.6
125 13.6 19.5
150 16.3 23.4
175 19.1 27.3
200 21.8 31.2
225 24.5 35.1
250 27.2 39.0
275 30.0 42.9
300 32.7 46.8
325 35.7 50.7
350 38.1 54.6
375 40.9 58.5
400 43.6 62.4
425 46.3 62.4
450 49.0 58.5
475 51.8 74.1
500 54.5 78.0 For system volumes other than those given above, multiply the system volume by the factor across 0.109 0.156
Instructions for Installation and Servicing turboMAX pro R310
4.8.6 Circulating pump
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400
50
100
150
200
250
300
350
400
450
500
550
600
650
700
Volume flow [l/h]
Lift [mbar]
setting III
setting II
The circulating pump is included in the boiler. The pump head available for the heating system is shown in fig. 4.6.
General Requirements 4
Fig. 4.6: Pump specifications
4.8.7 System by-pass
An automatic system by-pass is included within the boi­ler. The boiler is suitable for use in systems with ther­mostatic radiator valves and no additional by-pass is required.
4.8.8 Venting
The boiler is fitted with an automatic air vent. Additional provision should be made to enable the heating system to be vented during filling and commissioning either by automatic air vents or manually.
Instructions for Installation and Servicing turboMAX pro R3 11
150
5
200
500
5
I
0
0120
60
9030
°C
bar
4
3
2
1
0
5 Boiler Installation Sequence
440
800
338
I
0
0120
60
9030
°C bar 4
3
2
1
0
5 Boiler Installation Sequence
5.1 General Preparation of boiler location Clearances required
Mount the boiler on a flat and vertical area of wall of sufficient area for the boiler plus the required clearan­ces for installation and servicing. The clearances are as detailed below and are shown on the installation template supplied with the boiler:
- 150 mm below the boiler
- 5 mm on either side of the boiler
- 210 mm on top of the boiler
- 500 mm in front of the boiler*
* Clearance is only required to enable easier access to
the boiler for servicing and may be provided by an openable door, etc.
Note! If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with Institute of Gas Engineers Publication IGE/UP/7/1998 „Guide for Gas Installations in Timber Framed Dwellings“.
Fig. 5.2: Free space required for installation
Selecting position of boiler
Refer to „Boiler location“ for information regarding sit­ing the appliance. In general the boiler must be positio­ned such that.
• There is adequate space around the boiler for service and maintenance.
• The boiler can be correctly flued, i.e. the flue terminal position is sited in accordance with the flue terminati­on section and the air/flue duct can be installed in accordance with the flue installation instructions sup­plied.
• All necessary pipework can be connected, including the pressure relief valve.
Note! Should it be necessary to run system pipework to above the boiler within the width of the casing, use the optional top connection acces­sory (Art.No. 306 251).
Fig. 5.1: Dimensions of boiler
Instructions for Installation and Servicing turboMAX pro R312
Boiler Installation Sequence 5
55
210
124163 21200/202/240/242/280/282/824/828 Pro/Plus
60/100
07/2002
2
3
1
turboMAX only
3
402
171
174,5
12,5
1
1
2
5.2 Using boiler template
Fix the paper template to the wall ensuring that the cor­rect flue exit point has been identified, ensure that the template is vertical. The template shows
- The position of the fixing holes for the boiler moun­ting bracket (1).
- The position of the connections.
- The position of the flue exit hole.
- Upper hole (2) indicates top outlet flue with flue tur­ret facing rearward.
- Lower hole (3) indicates rear outlet flue exiting directly through wall.
• Mark the position of the hanging bracket fixing holes (1).
• Drill 2 holes Ø 8 mm for the hanging bracket.
Note! Use alternative fixing holes where necessary.
Identify correct flue exit
Mark the centre of the selected air/flue duct and its cir­cumference, e.g. by drilling through the template. For installation of a rear exit outlet please refer to the installation instructions of the rear exit outlet kit (Art. No. 303 817).
Other flue options
Flue instructions for other flue systems such as vertical RSF flues, flues run to the side of the boiler and the use of additional bends etc. are detailed in the flue installati­on instructions provided with the boiler. Remove the template from the wall and plug the drilled holes using the wallplugs supplied.
5.3 Fitting the boiler hanging bracket
Fix the hanging bracket (2) to the wall using the screws supplied. (it may be necessary to use additional or alternative fixings to ensure adequate support).
Fig. 5.3: Using Boiler template
Fig. 5.4: Free space required for installation
Note! If the boiler is to be fitted in a timber framed building ensure that the bracket is secured to a substantial part of the timber frame capable of taking the weight of the boiler.
Instructions for Installation and Servicing turboMAX pro R3 13
I
0
1
2
5 Boiler Installation Sequence
3
I
0
2
I
0
90°90°
1
5.4 Install the flue system
Install the flue system (refer to separate air/flue duct installation instructions).
5.5 Fitting the boiler
• Lift the boiler (3) up to the wall so that it is slightly above the hanging bracket (1).
Note! Lift the boiler from either side at the bottom edge.
• Lower the boiler slowly onto the hanging bracket so that the cross member at the rear of the boiler fully engages onto the hanging bracket.
5.6 Removing boiler casing
• Turn both securing fasteners (1) anti-clockwise by 90° to release control panel (2).
• Pull the case (3) forward at the bottom to disengage from the securing clips.
• Lift the case slightly to clear the top locations and pull forward to remove.
5.7 Gas supply
• Connect the 15 mm compression gas service cock (1) supplied with the appliance (2) and tighten.
• Connect a gas supply pipe of not less than 15 mm diameter to the gas service cock.
• Tighten all connections. (Ensure the gas supply pipework is adequately sized such that a 20 mbar gas pressure is available at the boiler inlet at full flow rate).
Fig. 5.5: Remove of boiler casing
Fig. 5.6: Fitting the gas connection
Instructions for Installation and Servicing turboMAX pro R314
Boiler Installation Sequence 5
1
2
3
4
6
I
0
I
0
4
1
2
3
5
6
5.8 Cold water mains inlet and hot water outlet
Flush all foreign matter from the mains supply before connecting to the boiler.
• Connect the cold water service valve (1) to the cold inlet water connection (3) of the appliance with the washer (2) provided and tighten.
• Connect the cold water inlet pipe copper tail to the cold water service valve and tighten.
• Connect the 15 mm hot water outlet copper tail (4) to the hot water outlet connection of the appliance (6) with the washer provided (5) and tighten.
Note! The hot water outlet union nut is packed in with the PRV fitting pack.
5.9 Central heating flow and return pipework
Before connecting the heating circuit to the boiler appli­ance, all pipework and radiators must be thoroughly flushed to remove any installation debris.
• Connect the central heating flow (4) and return (1) ser­vice valves to the appliance (6 and 3) with the washers provided (2 and 5) and tighten the nuts. Ensure that the valve spindles face downwards and the drain points face to either side of the boiler.
• Connect the central heating pipework to the flow (4) and return (1) tails.
Pressure Relief Valve
Connect a discharge pipe not less than 15 mm diameter to the outlet of this valve. The discharge pipework should be as short as possible and installed with a continuous fall away from the boiler. The pipe should terminate in a position which ensures that any discharge of water or steam from the valve cannot create a hazard to persons in or about the premi­ses, or cause damage to any electrical components or external wiring, and the point of discharge should be clearly visible (see diagram in plastic bag).
Fig. 5.7: Fitting the hot and cold water connections
Fig. 5.8: Central heating flow and return pipework
Instructions for Installation and Servicing turboMAX pro R3 15
5 Boiler Installation Sequence
2
1
5.10 Connect the flue system to the boiler
• Refer to separate air/flue duct installation instructions included with the boiler.
5.11 Electrical installation
General requirements
Important! All electrical work shall be carried out by a competent person and shall comply with BS7671 (IEE Regulations).
The boiler is supplied for connection to 230 V, ~ 50 Hz supply fused at 3 A rating. Connection to the mains supply shall be made via a fused 3 pin plug to an unswitched shuttered socket, both complying to the requirements of BS1363. (Alternatively, connection may be made via a 3 A fused double pole isolator having a contact separation of at least 3 mm in all poles and supplying the boiler and con­trols only). The point of connection to the mains supply must allow complete electrical isolation of the boiler and its ancil­lary controls. It should be readily accessible and adja­cent to the boiler. A 3 core flexible cord according to BS6500 tables 6, 8 or 16 (3 x 0.75 to 3 x 1.5 mm2) should be used.
3
NL987543
RT 24V 230V RT 230V
Fig. 5.9: Wiring system
Warning! This appliance must be earthed.
Important! Ensure that all cords pass through the cable clamps in the rear of the control box and are securely fixed. Ensure that the power supply is connected such that the current carrying con­ductors become taut before the earth conductor should the supply cord slip from the cable clamp.
Warning! Mains connection terminals L and N remain live even when the boiler on/off control is switched off.
5.12 Connection to the main supply
• Lower the control panel.
• Unclip the terminal box cover (1) from the control panel (2).
• Feed the power supply cord in to the appliance as shown (fig 5.9).
• Use cable clamps.
Fig. 5.10: Exposed rear view of switchgear cabinet
• Connect the power supply cord as follows (Fig. 5.11).
Green/yellow (earth) wire: boiler terminal Earth sign Blue (neutral) wire: boiler terminal N Brown (live) wire: boiler terminal L
Note! DO NOT use boiler terminal connections 7-8-9.
• Refit the terminal box cover by pushing into place until it clips back into position.
• Raise the control panel and secure in place.
Instructions for Installation and Servicing turboMAX pro R316
NL987
F3
543
24V
230V
F1
5.13 Electronic board layout
Boiler Installation Sequence 5
Socket X2 for internal unit components
Socket X4 for minority reversing
Socket X7 for accessory box connection
Do not use!
Socket X8 for VRC-VC connection
Mains power supply: connections L, N and earth
Room thermostat, 230 V: connections 3, 4 and 5
Socket X12: pump connection
Socket X14: gas valve connection
Abb. 0.0 Bildunterschrift
Fig. 5.11 Connection wiring
Instructions for Installation and Servicing turboMAX pro R3 17
Socket X13: fan unit connection
5 Boiler Installation Sequence
LN
234
LN 3
4
1
ACL Drayton Tempus 1, Tempus 2 Lyfestyle LP111, LP711
ACL Drayton Switchmaster SM300
ACL Drayton Switchmaster 980
Danfoss Randall 103 Series
Danfoss Randall Set 1E, TS975
Danfoss Randall TS715
Grässlin Towerchron QE1, QM1
Honeywell ST610A, ST6100C
Horstmann Channel Plus H11, H17, 425 Coronet
Horstmann Centaur Plus C11, C17
LN
234
LN 4
3
1
Potterton Myson EP 4002, EP 5002
Smiths Timeguard SupplyMASTER FST11, FST17
Sunvic Select 107
N1
AB C
N4
2
L
L
3
34
12
65E
4L3
N
3
E
NE
234
NE
1
L
L
3
56
4
LN
234
LN 3
4
1
LN
234
LN 3
4
1
LN
234
LN 3
4
1
NE
234
NE
1
L
L
3
56
4
NE
234
NE
1
L
L
3
4
LN
234
LN 3
4
1
LN
234
LN 3
4
1
AB
DLN
LN
C
N
E
3
12
4
345E
12
4
432/L
1/N
3
65
mains supply
LN E
E
Landis & Staefa RWB7, RWB30
LN
234
LN 3
4
1
ACL Drayton Lyfestyle PT271, PT371
ACL Drayton Digistat 2, 3, 4
ACL Drayton Digistat RF - SCR Receiver
Danfoss Randall TP4, TP5, TP5E
Danfoss Randall TP5E RF with receiver RX1
Danfoss Randall TP75
Grässlin Towerchron RTC7
Honeywell CM61, CM67, CM31, CM37
Horstmann Centaurstat 1, 7
Landis & Staefa REV 11, REV 15, REV 22
12
34
3
Sunvic TLX 6501
Sunvic TLX RFP, TLX RFD
Vaillant VRT 230, 220
N1
3
N3
2
L
L
4
32
43
1
LN
234
LN 3
4
1
BC
2341
A
3
56
4
12
34
3
AB
34
C
12
4
34
3
LL1
34
Smiths Timeguard ProgramaSTAT PRT11, PRT17
LN
4
LN
3
34
12
34
3
LN
234
LN 3
4
1
3
45
5.14 Controls External electrical controls
The boiler terminals 3, 4 and 5 are for connecting external electrical controls such as a time switch and/or room thermostat. Terminals 3 and 4 are linked together when the boiler is supplied. If external controls are used, this link must be removed, and the controls connected across terminals 3 and 4. Terminal 5 is an additional neutral connection for exter­nal neutrals such as from the anticipator of a room thermostat.
Connection of external controls Connection details for programmable room thermostats.
Fig. I.12 shows the connection details where a pro­grammable room thermostat (time switch with built in room thermostat) is used to control the boiler.
Attention! The arrowed numbers indicate connection into the relevant terminal in the boiler terminal strip.
Connection details for external time switches and boiler terminal strip.
Fig. 5.13 shows the connection details where a time switch is used without a room thermostat to control the boiler.
Attention! The arrowed numbers indicate connection into the relevant terminal in the boiler terminal strip.
If a room thermostat is to be connected in addition to a time switch the wire between the time switch „ON“ ter­minal and boiler terminal 4 should be broken by the contacts of the room thermostat (see schematic layout, Fig. 5.14).
Vaillant optional plug in timer accessories
Refer to the instructions supplied with the optional accessories for connection details. Upon completion of all electrical connections refit the terminal box cover by pushing into place. The cover is secured by two locking clips.
Fig. 5.12 Connection details for programmable thermostats
Fig. 5.13 Connection details for time switch
Instructions for Installation and Servicing turboMAX pro R318
Fig. 5.14
3
987
MAINS SUPPLY 230 V 50 Hz
L
L
LN
N
N
N
20 VDCDO NOT USE IN UK!
3 A FUSE
SWITCH CONTACTS
ROOM THERMOSTAT
CLOCK
4
5
Thermostatic radiator valves
The boiler has a built in automatic bypass valve making it ideal for use in systems with thermostatic radiator val­ves (no separate system bypass is required). For optimum fuel economy it is recommended that where TRV’s are used they are used in conjunction with a programmable room thermostat or separate timer and room thermostat to ensure complete boiler shut down when the heating demand is satisfied. (The radiator in the room containing the room thermostat should not be fitted with a TRV).
Boiler Installation Sequence 5
Automatic pump spin control (APS)
The boiler incorporates a built in control which will spin the built in circulating pump and operate the diverter valve (turboMAX only) once in a 24 hour period. This control helps to prevent seizure when the boiler is not operated for a period of time. This control is not active when the power supply to the appliance is turned off.
Frost protection
The boiler has an integral frost thermostat which is desi­gned for protection of the boiler.To protect remote or exposed parts of the heating system or property additio­nal frost protection measures must be taken such as the installation of an external frost thermostat. This frost thermostat should be connected across the boiler termi­nals 3 and 4, in parallel with any external heating con­trols. External frost protection cannot be used when plug in timers have been fitted.
Circulating pump
The boiler incorporates a built in circulating pump that is fully prewired (no additional wiring is necessary). The pump incorporates an automatic overrun period after the boiler switches off.
Anti-cycling ‘economiser’ control
The boiler incorporates a built in anti-cycling control to ensure that energy wasteful short cycling of the boiler cannot occur. This control prevents the boiler from re­igniting for a preset period of 5 minutes after central heating operation (the hot water operation is unaffected by this control and hot water can be drawn at any time).
Note! To temporarily override the anti-cycling control turn the main boiler on/off switch to the off position „0“ and then back to the on position „I“ after a few seconds.
Instructions for Installation and Servicing turboMAX pro R3 19
6 Commissioning Part I
2
5
3
4
1
6 Commissioning Part I
6.1 Preliminary electrical checks
Check the electrical installation by carrying out short circuit, earth continuity and resistance to earth tests and a check for correct polarity.
6.2 Gas supply
The complete gas installation including the gas meter must be inspected, tested for soundness and purged in accordance with BS 6891. The gas supply to the boiler can be purged by slacke­ning the gas service valve beneath the boiler. Ensure that there is adequate ventilation, extinguish all naked flames and do not smoke whilst purging. After purging, the gas service valve connection must be retightened and tested for soundness. (The boiler itself does not require purging as this will be done by the automatic burner sequence control).
6.3 Cold water supply
Open all domestic hot water taps supplied by the boiler, turn on the mains water supply to the boiler and open the mains water isolating valve below the boiler. Water will now flow through the boiler to the hot taps. Starting with the lowest tap supplied, turn the hot taps off one at a time until the hot water pipework is purged of air. Check all hot and cold water pipework for leaks.
6.4 Filling the heating system
Proceed as follows to fill the system:
• Open all radiator valves on the system.
• Fill the system via the seperate filling point.
• Open the valve slowly and fill the unit with water until the required pressure has been acheived (2).
• Bleed the air from the radiators.
• The boiler is equipped with an automatic air release valve. To allow this to vent the boiler, the cap top must be slackened by 1 - 2 turns. (This cap must be left slackened during operation to ensure any residual air or system gases are released).
• Close the filling valve (1) and disconnect the temporary connection.
• Now check the water pressure in the unit again (and add more water if necessary).
6.5 Initial system flush (“cold“)
The whole of the heating system must be flushed out at least twice: once cold, and once hot as instructed later. Open all radiator and heating valves and the boiler CH service valves and drain the heating system and boiler completely from the lowest points of the system via 1/2” BSP drain taps (opened full bore to remove any installa­tion debris prior to lighting the boiler). Refill the heating system. Check the operation of the pressure relief valve by rotating the knob on the valve. Now check the water pressure in the unit again (and add more water if necessary).
Fig. 6.1: Filling / draining the heating system
Close the filling valve (1) and disconnect the temporary connection.
Instructions for Installation and Servicing turboMAX pro R320
Gas supply adjustments (Commissioning Part II) 7
1
1
2
1
1a
2
2a
7 Gas supply adjustments
7.1 Gas inlet working pressure
To check the gas inlet working pressure:
• Lower the front panel of the boiler.
• Lower the control panel.
• Slacken the sealing screw (1) located at measuring point ”P.IN”.
• Attach U-gauge to the inlet test point on the gas valve (2).
• Ensure that the gas service valve is open.
• Set the DHW temperature control to maximum and fire the boiler at full rate by opening a hot water tap.
• Ensure that the hot water outlet temperature adjustment control is set to maximum.
• Check that the U-gauge is reading in the range of 18 to 20 mbar. (If the pressure is not within this range this should be investigated before continuing with the commissioning preocedure. (Lower pressures than this range are indicative of an incorrectly sized or partially blocked gas supply.)
• Turn off the hot tap.
• Remove U-gauge, tighten test point sealing screw (1).
• Test for soundness.
• Record appliance working gas inlet pressure (mbar) in the Benchmark gas boiler commissioning checklist.
7.2 Main burner pressure
The burner pressure on this appliance has been factory set and does not require adjustment. To check the main burner pressure connect the U-Gauge as follows depen­ding on the gas type.
• Remove front case and combustion chamber cover.
Note!
All measurements and adjustments to the gas valve must be done with the combustion cham­ber cover removed.
For natural gas appliances:
• Slacken the sealing screw (1) at test point on the gas valve and attach one arm of a U-gauge (2) to the test point.
For LPG appliances:
• Slacken the sealing screw (1a) at test point on the bur­ner inlet gas pipe and attach one arm of a U-gauge (2a) to the test point.
Connection for Natural gas
Fig. 7.1: Gas inlet working pressure
Connection for LPG
Fig. 7.2
Instructions for Installation and Servicing turboMAX pro R3 21
7 Gas supply adjustments (Commissioning Part II)
1
+
-
2
Set the DHW temperature control to maximum and fire the boiler at full rate by fully opening a hot water tap. Check that the burner pressure is as the maximum shown in table 7.1. Measure the domestic hot water mode burner operating pressure (mbar), the heat input (kW), the inlet and outlet domestic hot water temperatures (°C) and flow rate (l/min) and record details in the boiler logbook.
After completion of all tests tighten sealing screw, replace the sealing plug and check all test points for soundness (1/1a).
7.3 Adjusting the central heating output (range rating)
The boilers are fully modulating for central heating, and it is therefore not necessary to range rate the boiler. However, if desired, it is possible to range rate the boiler, as follows:
• Connect the U-gauge to check burner pressure.
• Use Table 7.1 on to determine the central heating
output required.
• Identify required range rating setting and note main
burner pressure in mbar for that output.
• Turn on the central heating.
• Turn the central heating maximum radiator tempera-
ture control to its highest setting.
• Ensure that any thermostatic radiator valves are open
and set to high.
• Wait for approx. 2 minutes until the burner pressure
switches to full load.
• The central heating output can now be altered by ins-
erting an electricans screwdriver into the potentiometer (2).
• Turn the potentiometer fully anticlockwise.
• Slowly turn the potentiometer clockwise, whilst
observing the U-gauge.
• Stop turning the potentiometer when the burner pres-
sure is at the correct setting for the output required.
• Turn off the hot tap.
• Remove U-gauge, tighten test point sealing screw (1).
• Reassemble the boiler.
• Refit plastic plug in chamber sensing tube.
• Carry out all safety checks as detailed in these
instructions.
• Record central heating operating pressure in the
Benchmark gas boiler commissioning checklist along with the heat input (kW) and temperature difference between flow and return.
Fig. 7.3: Adjusting the central heating output
Note! This illustration shows the U-tube pressure gauge connected to a system configured to run on natural gas. When connecting the U-tube pressure gauge to a system running on LPG, please refer to Fig. 7.2 on page 21.
Attention! DO NOT open any hot water tap while carrying out this procedure (turboMAX plus only).
Instructions for Installation and Servicing turboMAX pro R322
Gas supply adjustments (Commissioning Part II) 7
7.4 Burner Pressure and gas rate
Burner Pressure turboMAX pro 24/2 E
Delivered gas Output[kW] Ignition rate 8.9 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0
Natural gas 2H Burner pressure1)[mbar]
Main burner jet mark
2)
for G20
7 / 120
LPG 3+
Main burner jet mark
2)
Burner pressure1)[mbar]
for G30 3.9 3.9 4.9 6.9 9.2 11.8 14.7 17.8 21.1 24.7
7 / 072 for G31 5.4 5.4 6.7 9.4 12.5 16.0 19.8 24.0 28.5 33.3
Burner Pressure turboMAX pro 28/2 E
Delivered gas Output[kW] Ignition rate 10.4 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0
Natural gas 2H Burner pressure1)[mbar]
Main burner jet mark
7 / 120
LPG 3+
Main burner jet mark
7 / 072 for G31 5.3 5.3 6.9 9.3 11.9 14.8 18.0 21.4 25.1 29.0 33.1
2)
for G20
Burner pressure1)[mbar]
2)
for G30 3.8 3.8 5.0 6.7 8.7 10.8 13.1 15.6 18.3 21.2 24.2
1.9 1.9 2.1 2 .9 3.7 4.7 5.8 6.7 8.4 9.8
1.8 1.8 2.3 3.0 3.9 4.8 5.8 6.8 8.0 9.2 10.5
Table 7.1 Burner pressure
1) 15 °C, 1013mbar, dry
2) The nozzles are stamped with the mark shown in this table.
The marking corresponds to the nozzle hole diameter multiplied by 100
Gas Rate turboMAX pro 24/2 E
Delivered gas Output[kW] 8.9 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0
Natural gas 2H Gas Rate1)[m3/h]
Main burner jet mark
2)
for G20
1.1 1.2 1.4 1.7 1.9 2.1 2.4 2.6 2.8
7 / 120
Gas Rate turboMAX pro 28/2 E
Delivered gas Output[kW] 10.4 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0
Natural gas 2H Gas Rate1)[m3/h]
Main burner jet mark
7 / 120
2)
per G20
1.3 1.5 1.7 1.9 2.1 2.4 2.6 2.8 3.1 3.3
Table 7.2 Gas flow rate
1) 15 °C, 1013mbar, dry
2) The nozzles are stamped with the mark shown in this table.
The marking corresponds to the nozzle hole diameter multiplied by 100
Instructions for Installation and Servicing turboMAX pro R3 23
7 Gas supply adjustments (Commissioning Part II)
1
I
0
I
0
90°
90°
3
2
7.5 Fit combustion chamber cover
Carefully re-fit the combustion chamber cover to the boiler ensuring it is correctly sealed. Secure cover with retaining clamps.
7.6 Fit boiler casing
• Carefully push case (1) onto the boiler such that the
locating points either side at the top of the boiler engage. Push the casing onto the securing clips at the bottom of the boiler.
• Close control panel (2).
• Secure control panel by turning both securing fasten-
ers (3) clockwise by 90°.
Fig. 7.4: Fit boiler casing
Instructions for Installation and Servicing turboMAX pro R324
Functional Checks (Commissioning Part III) 8
I
0
I
0
1
2
3
4
5
67
8 Functional Checks
8.1 Functional checks
Procedure
Once the unit has been installed and the gas supply has been checked, operate the system to ensure that it is working correctly.
• Operate the system, following the operating instruc-
tions supplied with the boiler.
• Check the system for water leaks and escaping gas.
• Check that the flue has been correctly installed,
according to the fitting instructions supplied with the flue assembly.
• Check the burner for correct ignition and flame
picture.
• Check the hot water system for correct operation.
• Check the heating system for correct operation.
• By illuminating in this sequence the indicator lights have demonstrated correct operation of the boiler for DHW.
Note! Should the boiler fail to light it will attempt 2 re-ignition sequences, if the boiler still fails to light the burner lock out indicator will illuminate (7). This usually means that the gas supply is turned off or has not been purged of air. Check the gas supply, push the reset button and repeat the lightning procedure.
Fig. 8.2 Functional check
Heating system
• Ensure that the power on indicator is illuminated (1).
Fig. 8.1 Test for correct functioning
• Ensure that the maximum radiator temperature control is turned to the high position.
8.2 Functional check of operation
The Vaillant turboMAX pro is equipped with a set of dia­gnostic indicator lights to show the operational status of the boiler. A functional check of DHW and CH operation can be made using these indicator lights.
• Ensure external controls are calling for heat.
• The central heating demand indicator will illuminate (3).
• Providing the boiler has not achieved its set temperature, and the anti-cycling control is not activated, the boiler will start its lighting sequence. Once the fan and flue system have proved their satis-
Hot water system
• Ensure that the power on indicator (1) is illuminated.
• Turn on a hot top and draw water at a high rate.
• The hot water demand indicator (2) will illuminate.
• The appliance will start its lighting sequence. Once the fan and flue system has proved itself, the fan ope­ration indicator (4) will light.
• The gas valve will open and sparking will commence at the burner. The ignition indicator (5) will illuminate.
• As soon as the burner has ignited and the flame has
factory operation the fan operation indicator (4) will light.
• The gas valve will open and sparking will commence at the burner. The ignition indicator (5) will illuminate.
• As soon as the burner has ignited and the flame has been sensed the flame indicator (6) will illuminate.
• By illuminating in this sequence the indicator lights have demonstrated correct operation of the boiler for CH.
been sensed the flame indicator (6) will illuminate.
Instructions for Installation and Servicing turboMAX pro R3 25
8 Functional Checks (Commissioning Part III)
1
Further information can be obtained from Sentinel,
8.3 Adjusting pump speed
The unit is fitted with a two-speed pump. The pump is delivered with the switch (1) set to position III.
Attention! Important note: The boiler should only be operated at pump set­ting III because the heating capacity for hot water is reduced when operated at pump setting II!
It is possible, however, to change the pump setting from Level III to Level II manually when there is noise coming from the heating system.
GE Betz. Widnes, Cheshire, WA8 8UD. Tel: 0151 420 9595
• Disconnect the temporary filling connection.
• Refit the boiler casing.
• Attach the bottom cover to the boiler by securing with the four screws provided. It may be necessary to apapt the bottom cover by removing the easy break sections.
8.4 Handing over to the user
• Set the maximum radiator temperature control to the desired setting.
• Set the maximum hot water temperature control to the desired setting.
• Instruct the user in the safe and efficient operation of the boiler, in particular the function of:
- The boiler on/off control
- The maximum radiator temperature control
- The maximum hot water temperature control
- The pressure gauge
Fig. 8.3: Pump speed
Final system flush („HOT“)
• Turn on the boiler for central heating and allow the boiler and system to reach operating temperature.
• Check that the heating system is watertight.
• Turn the boiler off and rapidly drain both boiler and system while still hot.
• Refill the system and release all air. Release water from the system until the system design pressure of
1.0 bar is attained.
(The actual reading on the pressure gauge should ideal­ly be 0.5 bar plus an additional pressure corresponding to the highest point of the system above the base of the boiler - 10 m head equals an additional 1 bar reading on the pressure gauge. The minimum pressure should not be less than 1 bar in any installation.) If the system is to be treated with an inhibitor it should be applied at this stage in accordance with the manufac­turers instructions.
• Show the user how to operate any external controls.
• Explain to the user the importance of having the boi­ler regularly serviced by a competent servicing com­pany. To ensure regular servicing, it is strongly recom­mended that arrangements are made for a Maintenance Agreement. Please contact Vaillant Service Solutions (0870 6060 777) for further details.
• Ensure the Benchmark gas boiler commissioning checklist is fully completed. Failure to install and commission this appliance to the manufacturers instructions may invaludate the war­ranty (Note: This does not affect your statutory rights).
• Leave the user instructions in the clips provided in the front panel of the boiler.
• Leave the installation and servicing instructions with the user.
Note!
When you have finished the installation, attach the sticker supplied (835593) to the appliance
in the user’s language.
Attention!
The device may only be used
• for initial operation
• for testing
• for continuous operation with the chamber cover closed and with the flue system fully mounted and sealed.
Instructions for Installation and Servicing turboMAX pro R326
9 Servicing
9.1 Initial Inspection
To ensure the continued safe and efficient operation of the boiler it is recommended that it is checked and ser­viced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once per year should be adequate. It is the law that all servicing work is carried out by a competent person (Corgi registered).
Important!
Before starting any maintenance work:
• Isolate the mains electricity supply by disconnecting the plug at the socket outlet (if there is only an isola­ting switch remove the fuse from the switch).
• Turn OFF the gas supply at the gas service valve fitted to the boiler.
• Always test for gas soundness and always carry out functional checks after any service work and after exchanging any gas carrying component.
• Always check earth continuity, polarity and resistance to earth with a multimeter after any service work and after exchanging any electrical component.
Servicing 9
Note! The boiler is fitted with a combustion analysis test point. A suitable combustion analyser can be connected to this point to establish the com­bustion performance of the boiler.
Before commencing any servicing or maintenance work, carry out an initial inspection of the system as follows:
• Inspect the flue, pipework and electrical connections for indications of damage or deterioration.
• Inspect the air supply and ventilation arrangements of the installation.
• Check the heating and water system, in particular the condition of radiator valves, evidence of leakage from the heating system and dripping hot water taps.
Functional check of boiler operation
• Carry out a functional check of the boiler operation as prevoiusly detailed.
• Remove the appliance casing as detailed and operate the boiler by fully opening a hot water tap. Inspect the burner operation through the viewing window. Check that the flames are evenly covering the surface of the burner. Inspect for signs of excessive flame lift or soo­ting.
Instructions for Installation and Servicing turboMAX pro R3 27
9 Servicing
6a
6b
7
9
10
8
2
1
5
5
4
6c
9.2 Cleaning the burner and primary heat exchanger
• Turn off the boiler.
• Isolate the electrical supply to the boiler.
• Remove the boiler case as described.
• Turn off the gas service valve.
• Turn off the boiler CH service valves.
• Turn off the cold water inlet service valve.
• Release the three clamps (1), remove the combustion chamber cover (2).
• Pull the three cables (4) and two tubes (5) from the fan assembly.
• Remove the fan assembly (6a, 6b, 6c).
• Remove the four screws (7) and detach the front cover panel from the combustion chamber (8).
• Check the burner (9) and heat exchanger fins (10) and remove any loose deposits with a soft brush.
• Reassemble in reverse order.
• Check central heating expansion vessel.
Note! It is not necessary to carry out this check every year – a check every three years should be sufficient.
• Release the system water pressure from the boiler.
• Remove valve cap from expansion vessel charge point.
• Check that the internal charge pressure of expansion vessel is between 0.7 - 0.9 bar. If pressure is lower than this the vessel should be re-pressurised using an air pump.
• Refit valve cap.
• Open central heating service valves and re-pressurise the boiler and heating system if necessary.
• Open the gas service valve.
• Turn on the mains power supply.
• Operate the boiler and carry out soundness, safety and function checks.
• Complete the service interval record section in the
Benchmark gas boiler commissioning checklist.
Fig. 9.1 Cleaning the burner and primary heat exchanger
Instructions for Installation and Servicing turboMAX pro R328
Fault Finding 10
10 Fault Finding
10.1 Introduction
The turboMAX pro has built in diagnostic indicator lights to assist you with fault finding in the unlikely event of a boiler malfunction. The lights will illuminate in sequence, indicating the operational status of the boiler. Should a fault develop in the boiler the indicators may flash high­lighting the possible fault e.g.
Power on indicator (green)
Illuminates when the electricity supply to the boiler is on, the main on/off control is set to position (I) and the internal boiler fuses are o.k. (A flashing indicator shows that the overheat thermost­at has cut out.)
Hot water demand indicator (yellow)
Illuminates whenever there is a demand for hot water i.e. a hot water tap is opened.
Central heating demand indicator (yellow)
Illuminates whenever there is a demand for central hea­ting i.e. the radiator temperature control is turned on and the external heating controls are calling for heat.
Note! If the external controls are not calling for heat (i.e. the room thermostat has reached temperature) this indicator will go out. This is perfectly normal.
To reset the appliance after a lockout (either burner lockout illuminated or any other indicator light flas­hing), turn the central heating control to the reset positi­on and release.
10.2 Logical fault finding procedure
Preliminary Checks
These checks must be carried out before attempting to use the fault finding guide:
1) Carry out electrical safety checks.
2)Check that the external electricity supply to the boiler is on, and a supply of 230 V~ is present between boiler terminals „L“ and „N“.
3)Check that gas supply to the boiler is on and that it has been correctly purged.
4)Ensure the heating system is full of water and charged to approx. 1 bar. If not refill the system and vent system. Ensure boiler flow and return service valves are open.
5)Check that boiler main on/off control is set to position (I)
6)Ensure that the Maximum Radiator Temperature and Maximum Hot Water Temperature controls are set to high position.
7)Check that all the external controls are on and calling for heat (if no external controls are fitted, boiler termi­nals 3 and 4 must be linked). Check that boiler anti­cycling „economiser“ control is not engaged.
Procedure
Fan operation indicator (yellow)
Illuminates to indicate that the fan is operating and has been checked by the fan pressure switch. (A flashing indicator shows that the air pressure switch has not made.)
Ignition indicator (yellow)
Illuminates when gas valve, operator and ignition trans­former are energised. This indicator remains on during burner operation. (A flashing indicator shows lack of water or poor water circulation in central heating system.)
Flame indicator (yellow)
Illuminates when flame is recognised by the flame moni­toring system. (A flashing indicator shows that an NTC sensor is bro­ken, not connected or shorted to earth.)
Burner lockout indicator (red)
Illuminates if the burner fails to light within 10 seconds of illumination of the ignition indicator after the 3rd igni­tion cycle. (A flashing indicator shows a failure in the electronic boards.)
Note! Always check the operation of the boiler for central heating first before checking hot water operation. Do not open a hot tap unless instructed to by the fault finding guide.
Instructions for Installation and Servicing turboMAX pro R3 29
10 Fault Finding
Ensure boiler main
ON/OFF control is set
to position "1"
Ye s Go to sheet C
Check electrical supply, appliance fuses and on/off control
No
Is 230VAC present across
terminals L and N?
Ye s
Is 230VAC present across
terminals 3 and 5?
Ye s
Is voltage between
16-26 VDC present across
terminals 8 and 9?
Ye s
Is 5 VDC present between
5V and GND test points
on electronic board?
Replace LCD display
Ye s
NoRepair external fault
Is the continuity
across fuse F1?
Go to sheet B
Does ON/OFF knob
operate switch on
electronic board
Boiler ON/OFF control
defective,
change electronic
board
Replace switch
mechanism
No
No
No
Ye s
Ye s
Note 1:
For test purposes, disconnect external controls from terminal 3 - 4 and replace with a bridge between these terminals. It appliance then operates, the fault is with the external controls.
Sheet A
Is there continuity
across fuse F3?
No
No
Replace electronic
board
No
Check transformer
Replace if necessary
Ye s
Does green power on
indicator glow?
Instructions for Installation and Servicing turboMAX pro R330
Instructions for Installation and Servicing turboMAX pro R3 31
Sheet BCheck operation of pump and fan
Turn off the main ON/OFF control to the
"0" position
Diconnect the power supply to the boiler
Go to sheet A
Check transformer 230 VAC primary
(black/red) and approx. 17 VDC secondary
(blue/brown)
Check/replace pump
Replace fuse F1
If fan commences operation, exchange
gas valve
After approx. 20 secs.
Does fuse F1 blow?
Produce central heating demand.
Does fuse blow immediately?
Turn the main ON/OFF control to the "1" position
Does green power on indicator glow?
Ye s
No
No
No
Ye s
Check/replace fan Replace electronic board
No
Ye s
Ye s
Does green power on indicator glow?
Fault Finding 10
10 Fault Finding
Check central heating and controls
Ensure that radiator temperature control knob
is set to vertical position and that any internal
timer (if fitted) is calling for heat
No
Is 230 VAC present across terminals 4 and 5
No
External fault: Check all external controls are
calling for heat, replace or repair as necessary
(see also note 1 sheet A)
Ye s
Ye s Disconnect built in timer (if fitted)
No Go to sheet D
Does ignition
commence?
No
Ye s
Replace defective
timer
Sheet C
Does yellow central heating demand
indicator glow?
Does yellow flame indicator flash?
Instructions for Installation and Servicing turboMAX pro R332
Instructions for Installation and Servicing turboMAX pro R3 33
Does fan run after approx. 30 secs.?
Check flue and ignition system
No
Check pitot tube (in fan outlet) and air
hoses are not obstructed and correctly
aligned.
Check or replace air pressure switch.
Does the fan run now?
Is 230 VAC present across fan
terminals?
Replace electronic board
Ye s
No
No
Ye s
No
Ye s
Ye s Check/replace fan
Does the boiler
commence ignition
Check air/flue gas system
is correctly fitted and not
obstructed
Ye s
No
Replace electronic board
No
Ye s
Are electrodes sparking at
the burner?
Ye s Go to sheet E
No
Check electrodes and
electrode leads.
Replace as necessary.
Sheet D
Does yellow fan operation
indicator glow?
Does yellow fan
operation indicator flash?
Fault Finding 10
10 Fault Finding
Check gas valve and central heating system pressure
Does burner light 1st
attempt?
Does burner light within 3
ignition attempts?
No
Ye s
Check gas supply
Does burner light?
Ye s
Check burner pressure
settings are correct
Ye s
No Reset boiler
No
Check/replace gas valve
as necessary and
Does burner light?
No
Replace electronic board
Ye s
Is burner indicator
illuminated?
No
Check flame
rectification lead and
electrode
Is burner indicator
illuminated
No
Ye s
Does burner shut down after
approx. 15 secs.
No Go to sheet F
Ye s
Check water pressure in
central heating system, refill
and vent. as necessary
Check pump is running?
Ye s
Ye s Replace pump
No
Is 230 VAC present at the
pump plug connection?
No
Replace electronic board
Sheet E
Does yellow ignition indicator flash?
check water pressure
Instructions for Installation and Servicing turboMAX pro R334
Instructions for Installation and Servicing turboMAX pro R3 35
Does flame indicator glow and
flames increase in size to full gas
rate after approx. 2 mins?
Ye s
Does burner flame modulate/ go
out when radiator temperature
control is turned left to the
horizontal position at flow
temperature of approx. 50 C?
Ye s
Does heating flow pipe
temperature rise?
Go to sheet GYe s
Check operation of burner and modulation
Ensure flow and return service
valves are open
No
No
No
Replace electronic board
No
Check operation of boiler in DHW
mode, does flame increase in size
to full rate?
Ye s
Check partial load
setting
No
No
Go to sheet G
Ye s
Check connections and
modulatior, replace gas valve if
burner still fails to increase to full
rate
Turn main ON/OFF control to
the "0" position
Ye s
Insert a small screwdriver
through the hole in the front of
the diverter valve and hold
blade lightly against spindle
Turn "ON" the main ON/OFF
control
Does spindle move?
Ye s
Replace electronic board
Replace diverter valve
No
Sheet F
Does yellow hot water
demand indicator glow?
Fault Finding 10
10 Fault Finding
Draw hot water at high rate
Ye s
Check hot water flow rate and temperature.
Compare with technical data, if flow is not
sufficient check incoming main and cold water
filter.
Normal operation carry out
electrical safety checks
No
Check cold water inlet pressure is sufficient and that cold water inlet
filter is clear
Check cold water inlet is fully open
and adjustment is at maximum
flow rate
Check/Clear impeller in
Aquasensor, replace if necessary
Check/replace hall sensor
Replace electronic board
Does hot water indicator
glow/flash now?
No
No
Ye s
Ye s
No
Sheet G
No
Check D.H.W operation
Does yellow hot water demand indicator glow?
Does yellow hot water
demand indicator glow now?
Does yellow hot water
demand indicator glow now?
Instructions for Installation and Servicing turboMAX pro R336
power supply
F2A
L
2
N
1
main switch
main
transformer
230V 20V
air
pressure
switch
fan
pump
NTC flow
temperature
sensor
flame
sensor
gas
valve
aqua
sensor
F1,25A
NTC return
temperature
sensor
Burner lock out indicator (red)
Hot water demand indicator
Central heating demand indicator
Fan operation indicator
Ignition indicator
Flame indicator
Power on indicator (green)
main switchboard
ignition
electrodes
Legend
b blue br brown y/g yellow/green rred p pink t transparent bl black gr grey w white
gr
b
br
y/g
bbr
y/g
br
t
w
p
t
br
br
r
b
br
y/g
Reset button
gr
p p
r
control box
diverter
valve
bl
bl
bl
bl
wps
11.1 Functional Flow diagram: turboMAX pro 24 E and 28 E
Diagrams 11
Instructions for Installation and Servicing turboMAX pro R3 37
11 Diagrams
Switchgear cabinet
U100
X3
T 2
= F2
T 1,25
= F3
X2
X2
X1
24
23
11213
14
15
16
17
18
19
20
21
22
2
3
4
5
6
7
8
9
10
11
X6
Diagnosis
X2
Aqua
sensor
Pressure sensor
NTC return
NTC
earth
Ionisation
electrode
Coding resistor
NTC flow
NTC return
Lifting magnet
24
23
11213
14
15
16
17
18
19
20
21
22
2
3
4
5
6
7
8
9
10
11
Fan unit
Ignition
electrodes
Gas valveDiverter valveAir pressure switch
Ionisation
electrode
Pump
Aqua
sensor
NTC flow
NTC return
X8X4 (VUV)
X12
X14 X13
97 L 48N35
1234
EV1
Water pressure switch
11.2. Wiring diagram: turboMAX pro 24 E, 28 E
Instructions for Installation and Servicing turboMAX pro R338
833792_42 GB R3 03 2005 Subject to alteration
Loading...