Vaillant Thermocompact 615/2 E User guide

For the installer
824/2 E
828/2 E
837 E
615/2 E
620/2 E
624/2 E
637 E
GB
Instructions for Installation and Servicing
turboMAX plus and thermoCOMPACT
Wall hung room sealed fan assisted
combination and system boilers
Table of Contents
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R12
Page
1 List of Contents . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Contents included with boiler (turboMAX plus) 4
1.2 Contents included with boiler (thermoCOMPACT) 4
2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1
General Information . . . . . . . . . . . . . . . . 5
2.2 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 EC designation . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Boiler Specification . . . . . . . . . . . . . . . . . . . . . . 6
3.1
Technical data . . . . . . . . . . . . . . . . . . . . 6
3.2Boiler connections (turboMAX plus) . . . . . . . . 8
3.3Boiler connections (thermoCOMPACT) . . . . . . 8
3.4Functional diagram (turboMAX plus) . . . . . . . . 8
3.5Functional diagram (thermoCOMPACT) . . . . . . 9
4 General Requirements . . . . . . . . . . . . . . . . . . . . 10
4.1Related documents . . . . . . . . . . . . . . . . . . . . . . 10
4.2Boiler location . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4 Flue system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4.1Top outlet flue system . . . . . . . . . . . . . . . . . . . . 11
4.4.2Rear outlet flue system . . . . . . . . . . . . . . . . . . . 11
4.4.3 Extended top outlet flue system . . . . . . . . . . . 11
4.4.4 Flue termination . . . . . . . . . . . . . . . . . . . . . . . . 12
4.5 Air supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.6Cupboard or compartment ventilation . . . . . . 12
4.7 Electrical supply . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.8 Guide to system requirements . . . . . . . . . . . . . 13
4.8.1 Water circulation system . . . . . . . . . . . . . . . . . . 13
4.8.2 Filling and make up . . . . . . . . . . . . . . . . . . . . . . 13
4.8.3 Pressure relief valve . . . . . . . . . . . . . . . . . . . . . 13
4.8.4 Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.8.5 Expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . 13
4.8.6 Circulating pump . . . . . . . . . . . . . . . . . . . . . . . . 14
4.8.7 System by-pass . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.8.8 Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5 Boiler Installation Sequence . . . . . . . . . . . . . . . 15
5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.2 Using boiler template . . . . . . . . . . . . . . . . . . . . 16
5.3 Fitting the boiler hanging bracket . . . . . . . . . . 16
5.4 Install the flue system . . . . . . . . . . . . . . . . . . . . 17
5.5 Fitting the boiler . . . . . . . . . . . . . . . . . . . . . . . . 17
5.6Removing boiler casing . . . . . . . . . . . . . . . . . . . 17
5.7 Gas supply (turboMAX plus) . . . . . . . . . . . . . . . 17
5.8Cold water mains inlet and hot water outlet
(turboMAX plus) . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.9Central heating flow and return pipework
(turboMAX plus) . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.10 Gas supply (thermoCOMPACT) . . . . . . . . . . . . . 19
5.11 Central heating flow and return pipework
(thermoCOMPACT) . . . . . . . . . . . . . . . . . . . . . . 19
5.12 Connection to a Vantage unvented cylinder .
(thermoCOMPACT) . . . . . . . . . . . . . . . . . . . . . . 20
Page
5.13 Connect the flue system to the boiler . . . . . . . 20
5.14 Electrical installation . . . . . . . . . . . . . . . . . . . . . 20
5.15 Connection to the main supply . . . . . . . . . . . . 20
5.16 Electronic board layout . . . . . . . . . . . . . . . . . . . 21
5.17 Controls (turboMAX plus boiler) . . . . . . . . . . . . 22
5.18 Controls (thermoCOMPACT boiler) . . . . . . . . . 23
5.19 Thermostatic radiator valves . . . . . . . . . . . . . . 24
5.20 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.21 Circulating pump . . . . . . . . . . . . . . . . . . . . . . . . 24
5.22 Anti-cycling ‘economiser’ control . . . . . . . . . . . 24
6 Commissioning Part I . . . . . . . . . . . . . . . . . . . . 25
6.1 Preliminary electrical checks . . . . . . . . . . . . . . 25
6.2 Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.3 Cold water supply (turboMAX plus only) . . . . . 25
6.4 Filling the heating system (turboMAX plus) . . 25
6.5 Filling the heating system (thermoCOMPACT) 26
6.6 Initial system flush ("cold“) . . . . . . . . . . . . . . . . 26
7 Gas supply adjustments (Commissioning Part II) 26
7. 1 Gas inlet working pressure . . . . . . . . . . . . . . . . 26
7. 2 Main burner pressure . . . . . . . . . . . . . . . . . . . . 27
7. 3Adjusting the central heating output
(range rating) . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7. 4Adjusting to the maximum heat load
(nominal load) . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7. 5Adjusting the ignition rate . . . . . . . . . . . . . . . . 29
7. 6 Checking and adjusting to the operating point (turboMAX plus 837E and
thermoCOMPACT 637E only) . . . . . . . . . . . . . . 30
7.7Setting or adjusting the mid-setting point . . . 31
7. 8 Fit combustion chamber cover . . . . . . . . . . . . . 33
7. 9 Fit boiler casing . . . . . . . . . . . . . . . . . . . . . . . . . 33
8 Functional checks (Commissioning Part III) 33
8.1 Functional checks . . . . . . . . . . . . . . . . . . . . . . . 33
8.2 Functional check of operation
(turboMAX plus only) . . . . . . . . . . . . . . . . . . . . . 33
8.3 Functional check of operation
(thermoCOMPACT only) . . . . . . . . . . . . . . . . . . 34
8.4 Adjusting pump speed . . . . . . . . . . . . . . . . . . . . 34
8.5 Handing over to the user . . . . . . . . . . . . . . . . . 35
9 Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.1 Initial inspection . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.2 Cleaning the burner and primary heat
exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table of Contents
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 3
Page
10 Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
10.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
10.2 Indicator lights (turboMAX plus only) . . . . . . . 37
10.3 Indicator lights (thermoCOMPACT only) . . . . . 37
10.4 Logical fault finding procedure . . . . . . . . . . . . 36
10.5 Status Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.6 Diagnostic Mode . . . . . . . . . . . . . . . . . . . . . . . . . 39
10.7 Fault codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
10.8 Fault memory . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
10.9 Fault finding charts . . . . . . . . . . . . . . . . . . . . . . 41
11 Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
11.1
Functional flow diagrams . . . . . . . . . . . . . 48
12.2 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . 50
1 List of contents
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R14
1.2 Contents included with boiler (thermoCOMPACT)
Ensure that all contents are included before commencing installation.
Note! DO NOT remove the boiler from the polystrene base at this stage.
Fig. 1.2: Items supplied with unit (thermoCOMPACT)
9
8
7
1
6
5
2
10
11
V
R
C-
V
C
C
o
0
I
C
o
3
4
1 List of contents
1.1 Contents included with boiler (turboMAX plus)
Ensure that all contents are included before commencing installation.
Note! DO NOT remove the boiler from the polystrene base at this stage.
Fig. 1.1: Items supplied with unit (turboMAX plus)
4
10
9
8
1
2
7
6
11
12
V
RC
-VC
C
o
0
I
C
o
3
5
Item Quantity Description
11 Boiler
21 Flue restriction ring
31 Controls cover door
41 Lower cover plate (packed in bottom
packaging)
51 Cold water inlet valve
63 Flow and return service value, gas service
valve
75 Copper tails for gas and water pipework
81 Template
92 Guarantee Card and Benchmark log book
10 1 Installation and connection accessories and
PRV packages incl. DHW outlet union nut
11 3 Installation and Servicing, Users and Flue
Installation Instructions
12 1 Hanging bracket
Item Quantity Description
11 Boiler
21 Flue restriction ring
31 Controls cover door
41 Lower cover plate (packed in bottom
packaging)
53 Flow and return service value, gas service
valve
63 Copper tails for gas and water pipework
71 Template
82 Guarantee Card and Benchmark log book
91 Installation and connection accessories and
PRV packages
10 3 Installation and Servicing, Users and Flue
Installation Instructions
11 1 Hanging bracket
Introduction 2
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 5
2 Introduction
2.1 General Information
Note! This boiler must be installed and serviced by a competent person in accordance with the Gas Safety (Installation and Use) Regulations 1998. In the UK "CORGI“ registered installers undertake the work to a safe and satisfactory standard.
turboMAX plus boiler
The turboMAX plus is a fully automatic, wall mounted, room sealed combination boiler for central heating and domestic hot water. Domestic hot water is supplied directly from the boiler, without requiring a copper cylinder, cold water tank, feed and expansion tank and associated pipework. Domestic hot water has priority over central heating. The turboMAX plus range consists of models with outputs for domestic hot water of 24 kW , 28 kW and 37 kW. All turboMAX plus boilers are available in Natural Gas. The 24 and 28 kW versions are also available in LPG. turboMAX plus combination boilers incorporate a warmstart facility that keeps the domestic hot water heat exchanger hot, providing an instantaneous delivery of domestic hot water. The temperature in the domestic hot water heat exchanger is limited by the boiler control system and it is not necessary to install a scale reducer on the cold mains to the boiler. However, in exceptionally hard water areas to prevent scale formation in the property hot water system pipework, a scale reducer may be fitted. The heating system can be filled using the built-in filling loop contained within the boiler.
thermoCOMPACT boiler
The thermoCOMPACT is a fully automatic, wall mounted, room sealed system boiler for central heating and domestic hot water (where a separate indirect hot water storage cylinder is also incorporated in the system). The thermoCOMPACT range consists of models with outputs of 15, 20, 24, 28 kW and 37 kW. All thermoCOMPACT boilers are available in Natural Gas. The 20 and 28 kW versions are also available in LPG.
2.2 General Notes
The boilers have been designed for use with a sealed central heating system, and come fully tested and assembled with a built in circulating pump, expansion vessel and diverter valve (turboMAX plus only). The boilers are not suitable for use on open vented systems.
The boilers are easily sited on any internal wall and can be installed with either a horizontal or vertical RSF (room sealed fan assisted) flue. Two types of flue
systems are available, the standard concentric flue system (100 mm outside diameter) and a larger diameter concentric flue system (125 mm outside diameter) which allows longer flue lengths to be achieved. Flue extensions and additional bends and elbows are available for both flue systems to increase the siting flexibility. There is also a 100 mm diameter concentric flue accessory which connects to the alternative rear flue outlet on the boiler for direct through the wall installations. The boilers are not suitable for external installation. If desired, an inhibitor may be used in the system. Guidance on the use of inhibitors is contained in these instructions. All boilers have a built in diagnostic system which indicates the operational status of the boiler. This feature provides key information to aid commissioning and fault finding. The data badge is fitted on the rear of the control panel. See text of General Requirements for installation requirements or notes. Vaillant Ltd. support the Benchmark initiative. Within the information pack, you will find a Benchmark Log Book. It is very important that this is completed correctly at the time of installation, commissioning and handover to the user.
2.3 EC designation
turboMAX plus (824/828/837) and thermoCOMPACT boilers (615/620/624/628/637) carry the "CE" Mark. This demonstrates that the boilers fulfil the essential requirements of the Gas Appliance Directive(90/396/EEC) and the Gas Appliance (Safety) Regulations 1992.
The "CE" Mark also demonstrates that the boilers comply with the requirements of the Electromagnetic Compatibility Directive (89/336/EEC), the Low Voltage Directive (72/23/EEC), the Boiler Efficiency Directive (92/42/EEC) and the Boiler (Efficiency) Regulations
1993.
3 Boiler Specification
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R16
turboMAX plus turboMAX plus turboMAX plus 824/2 E 828/2 E 837 E Units (VUW GB 242/2-5) (VUW GB 282/2-5) (VUW GB 362/2-5)
Maximum CH heat input (net) 26.7 (91,200) 31.1 (106,200) 31.1 (106,200) kW (Btu/h)
CH heat output range (80/60 °C) 8.9 - 24 10.4 - 28 10.9 - 28* (36,.9)
(30,400 - 81,900) (35,500 - 95,500) (37,200 - 95,500) kW (Btu/h)
Maximum DHW heat input (net) 26.7 (91,200) 31.1 (106,200) 40.5 (138,300) kW (Btu/h)
SEDBUK Band D D D
SAP Seasonal Efficiency 79.6 79.7 79.8 %
DHW heat output 24 28 36.9 kW
DHW flow rate T = 35 °C rise 9.8 11.5 15.1 l/min
DHW flow rate at factory set
temperature rise (T 42 °C) 8.2 9.5 12.6 l/min
Mains water pressure required
for max. flow rate 0.5 0.5 0.5 bar
Minimum water flow rate 1.5 1.5 1.5 l/min
Mains water pressure required
for min. flow rate 0.15 0.15 0.15 bar
Maximum inlet water pressure 10 10 10 bar
Inlet gas working pressure
required (natural gas) 20 20 20 mbar
Gas supply (G20) Gross CV (s.t.) 37.8 37.8 37.8 MJ/m
3
Gas burner pressure max. rate 9.8 10.5 12.0 mbar
Gas burner pressure ignition rate 1.9 1.8 1.2 mbar
Gas rate max. (DHW) 2.8 3.3 4.3 m3/h
CH temperature flow range 35 - 82 35 - 82 35 - 82 °C
Minimum CH water flow
(for 20 °C rise) 1032 1203 1203 ** l/h
Pump pressure available 0.25 (25) 0.25 (25) 0.25 (25) bar (KPa)
Expansion vessel
pre-charge pressure 0.75 0.75 0.75 bar
Maximum CH system pressure 3 3 3 bar
Weight 43 45 48 kg
Primary water content 2.0 2.0 2.2 l
Electrical supply 230/50 230/50 230/50 V~/Hz
External fuse 3 3 3 A
Power input 150 150 130 W
Case height 800 800 800 mm
Case width 440 440 440 mm
Case depth 338 338 338 mm
3 Boiler Specification
3.1 Technical Data
* factory setting; ** at factory setting
Boiler Specification 3
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 7
thermoCOMPACT thermoCOMPACT thermoCOMPACT thermoCOMPACT thermoCOMPACT 615/2 E 620/2 E 624/2 E 628/2 E 637 E Units (VU GB 152/2-5) (VU GB 202/2-5) (VU GB 242/2-5) (VU GB 282/2-5) (VU GB 362-5)
Maximum CH heat input 16.5 22.0 26.7 31.1 40.5 kW
(net)(56,100) (74,800) (91,200) (106,200) (138,300) (Btu/h)
CH heat output range 6.5. - 15 7.7 - 20 8.9 - 24 10.4 - 28 10.5 - 36.9 kW
(80/60 °C) (22,300-51,200) (26,300 - 68,300) (30,400 - 81,900) (35,500 - 95,500) (35,800 - 126,000) (Btu/h)
SEDBUK Band D D D D D
SAP Seasonal Efficiency 79.0 79.7 79.7 79.8 79.8 %
Inlet gas working pressure
required (natural gas) 20 20 20 20 20 mbar
Gas supply (G20) 37.8 37.8 37.8 37.8 37.8 MJ/m
3
Gross CV (s.t.)
Gas burner pressure 9.9 9.0 9.8 10.5 12.0 mbar
max. rate
Gas burner pressure 2.2 1.5 1.9 1.8 1.2 mbar
ignition rate
CH temperature 35 - 82 35 - 82 35 - 82 35 - 82 35 - 82 °C
flow range
Minimum CH water flow
(for 20 °C rise) 650 860 1032 1203 1587 l/h
Pump pressure available 0.25 (25) 0.25 (25) 0.25 (25) 0.25 (25) 0.17 (17) bar
(KPa)
Expansion vessel
pre-charge pressure 0.75 0.75 0.75 0.75 0.75 bar
Maximum CH 3 3 3 3 3 bar
system pressure
Weight 38 39 41 43 45 kg
Primary water content 2.0 2.0 2.0 2.0 2.2 l
Electrical supply 230/50 230/50 230/50 230/50 230/50 V~/Hz
External fuse 3 3 3 3 3 A
Power input 150 150 150 150 130 W
Case height 800 800 800 800 800 mm
Case width 440 440 440 440 440 mm
Case depth 338 338 338 338 338 mm
3 Boiler Specification
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R18
Key: 1Heating system return (22 mm tail) 2 Gas connection (15 mm tail) 3Heating system flow (22 mm tail, 22 mm for 637) 4 Flue outlet (100 mm flue with turret) 5 Hanging bracket 6Rear flue outlet
3.4 Functional Diagram (turboMAX plus)
Fig. 3.3: Functional Diagram turboMAX plus
Key: 1 Air duct 2Fan 3 Main heat exchanger 4Temperature sensor (NTC I) 5 Flame sensing electrodes 6 Modulating burner 7Fully modulating automatic gas value 8 Maximum hot water temperature control 9 Maximum radiator temperature control 10 Diverter valve 11 DHW heat exchanger 12 Automatic bypass valve 13 CH flow service valve 14 Hot water outlet 15 Gas service valve 16 Cold water service valve 17 CH return service valve 18 Pressure relief valve 19 Aqua sensor (DHW flow switch) 20 Temperature sensor (NTC III) 21 Main on/off control
u
C
C
i
1
2
3
4
5 6
7
8
9
10
11
12
13 14
15
17 16
18
19
20
21
22
23
24
25
26
27
28
29
30
31
3.2 Boiler connections (turboMAX plus)
Fig. 3.1: Connection diameters turboMAX plus
Key: 1Heating system return (22 mm tail) 2Cold water connection with shut off valve
(15 mm tail) 3 Gas connection (15 mm tail, 22mm for 837) 4Hot water connection (15 mm tail) 5Heating system flow (22 mm tail) 6 Flue outlet (100 mm flue with turret) 7 Hanging bracket 8Rear flue outlet
3.3 Boiler connections (thermoCOMPACT)
Fig. 3.2: Connection diameters thermoCOMPACT
7
543 21
102
6
8
264
638
902
145
6
5
100
100
55 55
432
130
180
1
80
6
100
8
145
7
130
432
5
264
102
902
638
543 21
35 35
100
6
180
1
Boiler Specification 3
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 9
22 Pressure gauge 23 Display 24 Expansion vessel 25 Expansion vessel charging valve 26 Circulating pump 27 Automatic air vent 28 Ignition electrode 29 Temperature sensor (NTC II) 30 Air pressure switch 31 Flue gas duct
3.5 Functional Diagram (thermoCOMPACT)
Fig. 3.4: Functional Diagram thermoCOMPACT
Key: 1 Air duct 2Fan 3 Main heat exchanger 4Temperature sensor (NTC I) 5 Flame sensing electrodes 6 Modulating burner 7Fully modulating automatic gas value 8This control has no function on this boiler 9 Maximum radiator temperature control 10 Automatic bypass valve 11 CH flow service valve 12 Gas service valve 13 CH return service valve 14 Pressure relief valve 15 Main on/off control 16 Pressure gauge 17 Display 18 Expansion vessel
1
2
3
4
5 6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
19 Expansion vessel charging valve 20 Circulating pump 21 Automatic air vent 22 Ignition electrode 23 Temperature sensor (NTC II) 24 Air pressure switch 25 Flue gas duct
4 General Requirements
4.2 Boiler location
The location chosen for the boiler must permit the provision of a satisfactory flue termination. The location must also provide adequate space for servicing and air circulation around the boiler. The boiler may be installed in any room, although particular attention is drawn to the requirements of BS7671 (IEE Regulations), the electrical provisions of the Building Regulations (Scotland) and in IE the current edition of IS 813 and the current ETCI rules, in respect of the installation of a boiler in a room containing a bath or shower.
Note! Where a room sealed boiler is installed in a room containing a bath or shower, any electrical switch or boiler control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
Where the installation of the boiler will be in an unusual location, special procedures may be necessary and BS 5546 and BS 6798 give detailed guidance on this aspect. The boiler must be mounted on a flat, vertical wall, which must be sufficiently robust to take the weight of the boiler. The boiler may be installed on a combustible wall, subject to the requirements of the Local Authorities and Building Regulations. A compartment used to enclose the boiler must be designed and constructed specifically for this purpose. (An existing cupboard or compartment may be used provided that it is modified for the purpose). Details of essential features of cupboard/compartment design including airing cupboard installations are given in BS
6891. In IE the current edition of IS 813. If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with Institute of Gas Engineers Publication IGE/UP/7/1998 "Guide for Gas Installation in Timber Framed Housing“.
4.3 Gas Supply
The gas supplier should ensure the availability of an adequate supply of gas. A gas meter may only be connected to the service pipe by the supplier of gas or their contractor. An existing meter should be checked to ensure that it is capable of passing the rate of gas supply required. Installation pipes should be fitted in accordance with BS
6891. Pipework from the meter to the boiler must be of an adequate size. Do not use pipes of a smaller size than the boiler gas connection (15 mm, 22 mm for 837/637). The complete installation must be tested for soundness and purged as described in BS 6891.
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R110
4 General Requirements
4.1 Related Documents
The installation of the boiler must be in accordance with the relevant requirements of Gas Safety (Installation and Use) Regulations 1998, Health and Safety Document No. 635 (The Electricity at Work Regulations 1989), BS7671 (IEE Wiring Regulations) and the Water Supply (Water Fittings) Regulations 1999, or the Water Bylaws 2000 (Scotland). It should also be in accordance with the relevant requirements of the Local Authority, Building Regulations, Building Regulations (Scotland), Building Regulations (Northern Ireland) and the relevant recommendations of the following British Standard; Including current amendments to Approved Documents Part L and J.:
BBSS 55444400::
Flues and ventilation of gas fired boilers not
exceeding 70 kW net:
- Part 1: Flues
- Part 2: Ventilation
BBSS 55444499::
Specification for forced circulation hot water for domestic premises. BBSS 55554466::
Specification for gas hot water supplies for domestic premises. BBSS 66770000::
Services supplying water for domestic use within buildings and their curtilages. BBSS 66779988::
Specification for installation of gas fired boilers not exceeding 70 kW input net. BBSS 66889911::
Specification for installation of low pressure gas pipework up to 28 mm (R1) in domestic premises (2
nd
family gas).
BBSS 77559933::
Tre atment of water in domestic hot water central heating systems.Institute of Gas Engineers Publication IGE/UP/7/1998: Guide for Installation in Timber Framed Housing. Benchmark Code of Practice. Building Regulations Approved Documents Part L 2002 Part J 2002.
Important! The appliance must be installed and serviced by a competent person as stated in the Gas Safety (Installation and Use) Regulations 1998. In IE, the installation must be in accordance with the current edition of IS 813 'Domestic Gas Installations', the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
Preliminary remarks
This appliance should only be installed in conjunction with a Vaillant flue system. Install the flue system as detailed in the separate flue installation instructions supplied with this boiler.
General Requirements 4
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 11
4.4.2 Rear outlet flue system (100 mm outside diameter)
The rear outlet horizontal flue system (Art. No. 303 817) is suitable for installations up to 600 mm wall thickness.
Fig. 4.3: Art.-No. 303 817
4.4.3 Extended top outlet flue system (125 mm outside diameter)
A top outlet horizontal flue system of 125 mm outside diameter is also available (Art. No. 303 609) and can be used to achieve flue lengths of up to 12.9 m for 15/20/24 kW; 10 m for 28/37 kW. Both 45° and 90° bends and elbows are also available to increase siting flexibility. A vertical 125 mm concentric flue system is also available (Art. No. 303 600). Refer to flue system installation instructions for full details.
Fig. 4.4: Art.-No. 303 609
70
1103
70
15
4.4 Flue system
Note! The boilers are delivered ready for installation utilising a top outlet flue assembly. For installation with a rear outlet flue assembly refer to the boiler flue outlet adaptation in the flue instructions.
4.4.1 Top outlet flue system (100 mm outside diameter)
The top outlet horizontal flue system (Art. No. 303 807) is suitable for installations up to 720mm measured from the centre of the boiler flue outlet to the outside face of the wall. Flue extensions are available to extend this length up to 5.3 m for 15/20 kW; 4.5 m for 24 kW and 3.2 m for 28/37 kW. Both 90° bends and 45° elbows are also available to increase siting flexibility. A vertical flue system is also available (Art. No. 303
800).
Refer to flue system installation instructions for full details.
Fig. 4.1: Art.-No. 303 807
A vertical flue system is also available (Art. No. 303
800).
Refer to flue system installation instructions for full details.
Fig. 4.2: Art.-No. 303 800
48
1285
603
750
48
4
48
750
4 General Requirements
1) In addition, the terminal should not be nearer than 150mm to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window.
* BS 5440-1 It is recommended that a fanned flue terminal should
be positioned as follows: a) at least 2m from an opening in a building directly opposite, and b) so that the products of combustion are not directed to discharge across a boundary.
4.5 Air supply
Detailed recommendations for air supply are given in BS 5440: Part 2. It is not necessary to have an air vent in the room or internal space in which the boiler is installed.
4.6 Cupboard or compartment ventilation
The boilers are very high efficiency appliances. As a consequence the heat loss from the appliance casing during operation is very low. For cupboard or compartment installations it is therefore not necessary to provide any high or low level permanent air vents for cooling purposes.
4.7 Electrical supply
A 230 V, ~ 50 Hz single phase electricity supply fused to 3 Amp. must be provided in accordance with the latest edition of BS7671 (IEE Wiring Regulations) and any other local regulations that may apply. In IE, reference should be made to the current edition of the ETCI rules.
The method of connection to the mains electricity supply must provide a means of completely isolating the boiler and its ancillary controls. Isolation is preferably by the use of a fused three pin plug and unswitched shuttered socket outlet, both complying with the
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R112
4.4.4 Flue termination
The following details refer to both flue systems. a. The terminal must be positioned such that the pro-
ducts of combustion can disperse freely at all times.
b. In certain weather conditions a plume of water
vapour may be visible from the flue terminal. Positions where this could be a nuisance should be avoided.
c. If the terminal is fitted less than 2 m above a
balcony, above ground or above a flat roof to which people have access then a suitable terminal guard; must be provided and fitted (Model K3 - made by Tower Flue Components, Tonbridge, TN9 1TB).
Note! Vertical flues must not terminate within 600 mm of an openable window, air vent or any other ventilation opening.
The flue assembly shall be so placed or shielded as to prevent ignition or damage to any part of the building.
Fig. 4.5: Flue termination
A
BCD
A G
H, I
F
J
B
F
M
L
L
K
K
G
G
F
F
E
A
A
Terminal position for fan-assisted flue (minimum distance) mm
A1)Directly below an openable, above an opening
or horizontal to an opening i.e. air brick, opening
window or other, etc 300
BBelow gutters, soil pipes or drain pipes 25
CBelow eaves 25
DBelow balconies (below car port roof) 25
EFrom vertical drain pipes and soil pipes 25
FFrom internal or external corners 25
G Above ground or balcony level 300
HFrom a surface or boundary facing a terminal 600*
HFrom a terminal facing a terminal 1200
JFrom an opening in a car port (e.g. door, window)
into a dweling 1200
KVertically from a terminal on the same wall 1500
L Horizontally from a terminal on the same wall 300
M Distance from adjacent wall for vertical Flue 500
General Requirements 4
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 13
(Alternative methods of filling sealed systems are given in BS 5449).
4.8.3 Pressure relief valve
A pressure relief valve is provided with the boiler. This safety device is required on all sealed C.H. systems and is preset at 3 bar and provided with a 15 mm compression connection for a discharge pipe, which must be of no less than 15 mm in diameter. The Pressure Relief Valve must not be used for draining purposes.
4.8.4 Pressure gauge
This is factory fitted to the boiler and indicates the primary circuit pressure to facilitate filling and testing.
4.8.5 Expansion vessel
The 15 and 20 kW thermoCOMPACT boilers as well as the 24 kW turboMAX plus boiler incorporate a 6 litre expansion vessel which is suitable for a sealed heating system with a maximum water content of 60 litres. A 10 litre expansion vessel kit is available as an optional accessory for for the turboMAX plus 24 kW boiler and the 15 and 20 kW thermoCOMPACT boilers. The 28, 37 turboMAX plus and 24, 28, 37 kW thermoCOMPACT boilers incorporate a 10 litre expansion vessel which is suitable for a sealed heating system with a maximum water content of 100 litres. If the nominal capacity of the built in expansion vessel is not sufficient for the heating system (for instance in case of modernization of old open systems) an additional expansion vessel can be installed external to the boiler. It should be fitted in the return pipe as close as possible to the boiler in accordance with BS 5449: Part 1. Guidance on the sizing of an additional expansion vessel is given in Table on page 14.
requirements of BS 1363. Alternatively, a 3 Amp. fused doublepole switch with a 3 mm contact separation on both poles may be used.
Important! This appliance must be earthed.
4.8 Guide to system requirements
4.8.1 Water circulation system
Detailed recommendations for the water circulation system are given in BS 6798 and BS 5449: Part 1 (for small bore and micro bore central heating systems).
Pipework not forming part of the useful heating surface should be insulated to help prevent heat loss and possible freezing, particularly where pipes are run through roof spaces and ventilated underfloor spaces. Draining taps must be located in accessible positions which permit the draining of the whole system including the boiler and the hot water system. Draining taps should be at least 1/2 in. BSP nominal size and be in accordance with BS 2879. The boiler is suitable for use with minibore or microbore systems. Copper tubing to BS 2871: Part 1 should be used for water carrying pipework. All capillary joints in all DHW pipework must be made with lead free solder.
Particularly where a new boiler is to be fitted to an existing system, it is good practice that the system is thoroughly cleansed. This cleansing should take place prior to the fitting of the new boiler and be in accordance with BS 7593.
For advice on the application of system cleansers contact either Sentinel, GE Betz. Widnes, Cheshire, WA8 8UD. Tel: 0151 420 9595 or: Fernox Alpha-Fry Technologies Tandem House Marlow Way, Beddington Farm Road Croydon CRO 4xS Tel. 0870 601 5000 Fernox technical help line 01799 550811
4.8.2 Filling and make up
The system can be filled using the built in filling loop (turboMAX plus only) or via a separate filling point fitted at a convinient position on the heating circuit (thermoCOMPACT). The connection must be removed when filling is completed. Where local Water Authority regulation does not allow temporary connection, a sealed system filler pump with break tank must be used. The heating system will not be filled automatically from the domestic hot water side.
4 General Requirements
Fig. 4.6: Pump specifications 37 kW
4.8.7 System by-pass
An automatic system by-pass is included within the boiler. The boiler is suitable for use in systems with thermostatic radiator valves and no additional by-pass is required.
4.8.8 Venting
The boiler is fitted with an automatic air vent. Additional provision should be made to enable the heating system to be vented during filling and commissioning either by automatic air vents or manually.
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400
50
100
150
200
250
300
350
400
450
500
550
600
650
700
Volume flow [l/min]
Lift [mbar]
Pump switch in position III (pre-delivery setting)
Pump switch in position II
1500 1600 1700
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R114
4.8.6 Circulating pump
The circulating pump is included in the boiler. The pump head available for the heating system is shown in fig. 4.6.
Fig. 4.6: Pump specifications 12-28 kW
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400
50
100
150
200
250
300
350
400
450
500
550
600
650
700
Volume flow [l/hr]
Lift [mbar]
Pump switch in position III (Factory setting)
Pump switch in position II
Vessel Volume [L] Initial system pressure (bar) 1.0 1.5 Pressure relief valve setting (bar) 3.0
To tal water content of system ltres
25 2.7 3.9
50 5.4 7.8
100 10.9 15.6
125 13.6 19.5
150 16.3 23.4
175 19.1 27.3
200 21.8 31.2
225 24.5 35.1
250 27.2 39.0
275 30.0 42.9
30032.7 46.8
325 35.7 50.7
350 38.1 54.6
375 40.958.5
400 43.6 62.4
425 46.3 66.3
450 49.0 70.2
475 51.8 74.1
500 54.5 78.0 For system volumes other than those given above, multiply the system volume by the factor across 0.109 0.156
Boiler Installation Sequence 5
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 15
Selecting position of boiler
Refer to "Boiler location“ for information regarding siting the appliance. In general the boiler must be positioned such that.
•There is adequate space around the boiler for service and maintenance.
•The boiler can be correctly flued, i.e. the flue terminal position is sited in accordance with the flue termination section and the air/flue duct can be installed in accordance with the flue installation instructions supplied.
• All necessary pipework can be connected, including the pressure relief valve.
Note! Should it be necessary to run system pipework to above the boiler within the width of the casing, use the optional top connection accessory (Art.No. 306 251).
5 Boiler Installation Sequence
5.1 General
Preparation of boiler location
Clearances required Mount the boiler on a flat and vertical area of wall of sufficient area for the boiler plus the required clearances for installation and servicing. The clearances are as detailed below and are shown on the installation template supplied with the boiler:
- 150 mm below the boiler
- 5 mm on either side of the boiler
- 210 mm on top of the boiler
- 500 mm in front of the boiler*
* Clearance is only required to enable easier access to
the boiler for servicing and may be provided by an openable door, etc.
Note! If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with Institute of Gas Engineers Publication IGE/UP/7/1998 "Guide for Gas Installations in Timber Framed Dwellings“.
Fig. 5.1: Dimensions of boiler
Fig. 5.2: Free space required for installation
440
800
338
5 Boiler Installation Sequence
Note! Use alternative fixing holes where necessary.
Identify correct flue exit
Mark the centre of the selected air/flue duct and its circumference, e.g. by drilling through the template. For installation of a rear exit outlet please refer to the installation instructions of the rear exit outlet kit (Art. No. 303 817).
Other flue options
Flue instructions for other flue systems such as vertical RSF flues, flues run to the side of the boiler and the use of additional bends etc. are detailed in the flue installation instructions provided with the boiler. Remove the template from the wall and plug the drilled holes using the wallplugs supplied.
5.3 Fitting the boiler hanging bracket
Fix the hanging bracket (1) to the wall using the screws supplied (2). (it may be necessary to use additional or alternative fixings to ensure adequate support).
Fig. 5.4: Free space required for installation
Note! If the boiler is to be fitted in a timber framed building ensure that the bracket is secured to a substantial part of the timber frame capable of taking the weight of the boiler.
3
402
171
174,5
12,5
1
1
2
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R116
5.2 Using boiler template
Fix the paper template to the wall ensuring that the correct flue exit point has been identified, ensure that the template is vertical. The template shows
- The position of the fixing holes for the boiler mounting bracket (1).
- The position of the connections.
- The position of the flue exit hole.
- Upper hole (2) indicates top outlet flue with flue turret facing rearward.
- Lower hole (3) indicates rear outlet flue exiting directly through wall.
• Mark the position of the hanging bracket fixing holes (1).
• Drill 2 holes Ø 8 mm for the hanging bracket.
Fig. 5.3: Using Boiler template
5
5
210
124163 21200/202/240/242/280/282/824/828 Pro/Plus
60/100
07/2002
210
2
3
1
turboMAX only
Boiler Installation Sequence 5
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 17
5.7 Gas supply (turboMAX plus)
•Connect the 15 mm compression gas service cock (1) and 15 mm copper outlet tail (22mm copper tail with
837) (3) as supplied with the appliance (2) and tighten.
•Connect a gas supply pipe of not less than 15 mm diameter to the copper tail (minimum 22 mm gas supply pipe with 837).
•Tighten all connections. (Ensure the gas supply pipework is adequately sized such that a 20 mbar gas pressure is available at the boiler inlet at full flow rate).
Fig. 5.6: Fitting the gas connection turboMAX plus
I
0
3
1
2
5.4 Install the flue system
Fit the flue restrictor to the boiler (if required) and install the flue system (refer to separate air/flue duct installation instructions for further information).
5.5 Fitting the boiler
• Lift the boiler (3) up to the wall so that it is slightly above the hanging bracket (1).
Note! Lift the boiler from either side at the bottom edge.
•Lower the boiler slowly onto the hanging bracket so that the cross member at the rear of the boiler fully engages onto the hanging bracket.
5.6 Removing boiler casing
•Turn both securing fasteners (1) anti-clockwise by 90° to release control panel (2).
• Pull the case (3) forward at the bottom to disengage from the securing clips.
• Lift the case slightly to clear the top locations and pull forward to remove.
Fig. 5.5: Remove of boiler casing
VRC-VC
3
I
0
2
I
0
90°90°
1
5 Boiler Installation Sequence
5.9 Central heating flow and return pipework (turboMAX plus)
Before connecting the heating circuit to the boiler appliance, all pipework and radiators must be thoroughly flushed to remove any installation debris.
•Connect the central heating flow (6) and return (1)
service valves to the appliance (8 and 3) with the washers provided (2 and 7) and tighten the nuts. Ensure that the valve spindles face downwards and the drain points face to either side of the boiler.
•Connect the 22 mm copper pipe tails to the service
valves as shown in the illustration and tighten the nuts.
•Connect the central heating pipework to the flow (9)
and return (4) tails.
Pressure Relief Valve
Connect a discharge pipe not less than 15 mm diameter to the outlet of this valve. The discharge pipework should be as short as possible and installed with a continuous fall away from the boiler. The pipe should terminate in a position which ensures that any discharge of water or steam from the valve cannot create a hazard to persons in or about the premises, or cause damage to any electrical components or external wiring, and the point of discharge should be clearly visible (see diagram in plastic bag).
Fig. 5.8: Central heating flow and return pipework turboMAX plus
9
I
0
4
1
2
3
8
7
6
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R118
5.8 Cold water mains inlet and hot water outlet (turboMAX plus)
Flush all foreign matter from the mains supply before connecting to the boiler.
•Connect the cold water service valve (1) to the cold
inlet water connection (3) of the appliance with the washer (2) provided and tighten.
•Connect the 15 mm cold water inlet pipe copper tail
(4) to the cold water service valve (1) and tighten.
•Connect the 15 mm hot water outlet copper tail (6) to
the hot water outlet connection of the appliance (8) with the washer provided (7) and tighten.
Note! The hot water outlet union nut is packed in with the PRV fitting pack.
•Connect the cold water service pipe and hot water
outlet pipework to the copper tails.
Fig. 5.7: Fitting the hot and cold water connections turboMAX plus
1
2
3
4
6
7
8
I
0
Boiler Installation Sequence 5
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 19
5.11 Central heating flow and return pipework (thermoCOMPACT)
Before connecting the heating circuit to the boiler appliance, all pipework and radiators must be thoroughly flushed to remove any installation debris.
•Connect the central heating flow (6) and return (1)
service valves to the appliance (8 and 3), with the washers (2 and 7) provided and tighten the nuts. Ensure that the valve spindles face downwards and the drain points face to either side of the boiler.
•Connect the 22 mm copper pipe tails to the service
valves as shown in the illustration and tighten the nuts.
•Connect the central heating pipework to the flow (9)
and return (4) tails.
Pressure Relief Valve
Connect a discharge pipe not less than 15 mm diameter to the outlet of this valve. The discharge pipework should be as short as possible and installed with a continuous fall away from the boiler. The pipe should terminate in a position which ensures that any discharge of water or steam from the valve cannot create a hazard to persons in or about the premises, or cause damage to any electrical components or external wiring, and the point of discharge should be clearly visible (see diagram in plastic bag).
Fig. 5.10: Central heating flow and return pipework
thermoCOMPACT
9
I
0
4
1
2
3
8
7
6
5.10 Gas supply (thermoCOMPACT)
•Connect the 15 mm compression gas service cock (1) and 15 mm copper outlet tail (22 mm copper tail with
637) (3) as supplied with the appliance and tighten.
•Connect a gas supply pipe of not less than 15 mm diameter to the copper tail (minimum 22 mm with
637).
•Tighten all connections. (Ensure the gas supply pipework is adequately sized such that a 20 mbar gas pressure is available at the boiler inlet at full flow rate).
Fig. 5.9: Fitting the gas connection thermoCOMPACT
I
0
3
1
2
5 Boiler Installation Sequence
Fig. 5.11: Wiring system
Fig. 5.12: Exposed rear view of switchgear cabinet (picture
shows turboMAX appliance)
•Connect the power supply cord as follows (Fig. 5.13).
Green/yellow (earth) wire: boiler terminal Earth sign Blue (neutral) wire: boiler terminal N Brown (live) wire: boiler terminal L
Note! DO NOT use boiler terminal connections 7-8-9.
•Refit the terminal box cover by pushing into place until it clips back into position.
•Raise the control panel and secure in place.
2
1
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R120
5.12 Connection to a VANTAGE unvented cylinder (thermoCOMPACT)
•For connecting a Vaillant VANTAGE unvented cylinder
please refer to the VANTAGE installation instructions provided with the cylinder.
5.13 Connect the flue system to the boiler
•Refer to separate air/flue duct installation instructions
included with the boiler.
5.14 Electrical installation
General requirements
Important! All electrical work shall be carried out by a competent person and shall comply with BS7671 (IEE Regulations).
The boiler is supplied for connection to 230 V, ~ 50 Hz supply fused at 3 A rating. Connection to the mains supply shall be made via a fused 3 pin plug to an unswitched shuttered socket, both complying to the requirements of BS1363. (Alternatively, connection may be made via a 3 A fused double pole isolator having a contact separation of at least 3 mm in all poles and supplying the boiler and controls only). The point of connection to the mains supply must allow complete electrical isolation of the boiler and its ancillary controls. It should be readily accessible and adjacent to the boiler. A 3 core flexible cord according to BS6500 tables 6, 8 or 16 (3 x 0.75 to 3 x 1.5 mm
2
)
should be used.
Warning! This appliance must be earthed.
Important! Ensure that all cords pass through the cable clamps in the rear of the control box and are securely fixed. Ensure that the power supply is connected such that the current carrying conductors become taut before the earth conductor should the supply cord slip from the cable clamp.
Warning! Mains connection terminals L and N remain live even when the boiler on/off control is switched off.
5.15 Connection to the main supply
•Lower the control panel.
• Unclip the terminal box cover (1) from the control
panel.
•Feed the power supply cord in to the appliance as
shown (fig 5.11).
•Use cable clamps.
3
RT 24V 230V RT 230V
NL987543
Boiler Installation Sequence 5
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 21
Abb. 0.0 Bildunterschrift
Fig. 5.13: Connection wiring
NL987
F3
543
24V
230V
F1
5.16 Electronic board layout
Socket X2 for internal unit components
Socket X4 for diverter valve
Socket X7 for accessory box connection
Socket X8 for VRC-VC connection
Room thermostat, 230 V: connections 3, 4 and 5
Mains power supply: connections L, N and earth
Socket X12: pump connection
Socket X14: gas valve connection
Socket X13: fan connection
Do not use!
Socket for fan control cable (637 and 837 only)
5 Boiler Installation Sequence
Connection details for external time switches and boiler terminal strip.
Fig. 5.15 shows the connection details where a time switch is used without a room thermostat to control the boiler.
Attention! The arrowed numbers indicate connection into the relevant terminal in the boiler terminal strip.
If a room thermostat is to be connected in addition to a time switch the wire between the time switch "ON“ terminal and boiler terminal 4 should be broken by the contacts of the room thermostat (see schematic layout, Fig. 5.16).
Vaillant optional plug in timer accessories
Refer to the instructions supplied with the optional accessories for connection details. Upon completion of all electrical connections refit the terminal box cover by pushing into place. The cover is secured by two locking clips.
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R122
Fig. 5.15 Connection details for time switch
LN
234
LN3
4
1
ACL Drayton Tempus 1, Tempus 2 Lyfestyle LP111, LP711
ACL Drayton Switchmaster SM300
ACL Drayton Switchmaster 980
Danfoss Randall 103 Series
Danfoss Randall Set 1E, TS975
Danfoss Randall TS715
Grässlin Towerchron QE1, QM1
Honeywell ST610A, ST6100C
Horstmann Channel Plus H11, H17, 425 Coronet
Horstmann Centaur Plus C11, C17
LN
234
LN4
3
1
Potterton Myson EP 4002, EP 5002
Smiths Timeguard SupplyMASTER FST11, FST17
Sunvic Select 107
N1
AB C
N4
2
L
L
3
34
12
65E
4L3
N
3
E
NE
234
NE
1
L
L
3
56
4
LN
234
LN3
4
1
LN
234
LN 3
4
1
LN
234
LN3
4
1
NE
234
NE
1
L
L
3
56
4
NE
234
NE
1
L
L
3
4
LN
234
LN 3
4
1
LN
234
LN3
4
1
AB
DL N
LN
C
N
E
3
12
4
345E
12
4
432/L
1/N
3
65
mains supply
LNE
E
Landis & Staefa RWB7, RWB30
5.17 Controls (turboMAX plus boiler)
External electrical controls
The boiler terminals 3, 4 and 5 are for connecting external electrical controls such as a time switch and/or room thermostat. Te rminals 3 and 4 are linked together when the boiler is supplied. If external controls are used, this link must be removed and the controls connected across terminals 3 and 4. Terminal 5 is an additional neutral connection for external neutrals such as from the anticipator of a room thermostat.
Connection of external controls
Connection details for programmable room thermostats.
Fig. 5.14 shows the connection details where a programmable room thermostat (time switch with built in room thermostat) is used to control the boiler.
Attention! The arrowed numbers indicate connection into the relevant terminal in the boiler terminal strip.
Fig. 5.14 Connection details for programmable thermostats
LN
234
LN3
4
1
ACL Drayton Lyfestyle PT271, PT371
ACL Drayton Digistat 2, 3, 4
ACL Drayton Digistat RF - SCR Receiver
Danfoss Randall TP4, TP5, TP5E
Danfoss Randall TP5E RF with receiver RX1
Danfoss Randall TP75
Grässlin Towerchron RTC7
Honeywell CM61, CM67, CM31, CM37
Horstmann Centaurstat 1, 7
Landis & Staefa REV 11, REV 15, REV 22
12
34
3
Sunvic TLX 6501
Sunvic TLX RFP, TLX RFD
Vaillant VRT 230, 220
N1
3
N3
2
L
L
4
32
43
1
LN
234
LN 3
4
1
BC
2341
A
3
56
4
12
34
3
AB
34
C
12
4
34
3
LL1
34
Smiths Timeguard ProgramaSTAT PRT11, PRT17
LN
4
LN
3
34
12
34
3
LN
234
LN 3
4
1
3
45
3
45
Boiler Installation Sequence 5
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 23
Fig. 5.16
5.18 Controls (thermoCOMPACT boiler)
External electrical controls
The boiler terminals 3, 4 and 5 are for connecting external electrical controls such as a programmer, room thermostat, etc. Te rminals 3 and 4 are linked together when the boiler is supplied. If external controls are used, this link must be removed, and the controls connected across terminals 3 and 4. Terminal 5 is an additional neutral connection for external controls.
Connection of external electrical controls
Connection details using an external wiring centre
The boiler should be connected to the system controls using an external wiring centre. Fig. 5.17, 5.18 shows connection details for a system utilising a 3 port mid position motorised valve, figure 5.19, 5.20 shows the connection details for a system utilising two 2 port motorised valves connected via an external wiring centre (Important: the arrowed numbers indicate connection into the relevant terminal of thre external wiring centre).
3
987
MAINS SUPPLY 230 V
50 Hz
L
L
LN
N
N
N
20 VDC
DO NOT USE IN UK!
3 A FUSE
SWITCH CONTACTS
ROOM THERMOSTAT
CLOCK
4
5
Fig. 5.17
Key:
XCentral heating on YHot water on ZHot water off
Connection details for control systems utilising 3 port motorised valve via external wiring centre/junction box
Diagram only applies to the specific controls mentioned
LN
LN
345
ENL
X** Y** Z**
3 amp fused main supply
THERMOcompact terminal strip
Programmer for programmer connections see fig. 16.b
LN
LN
345
E53678
External wiring centre/junction box*
345678910
NNL
L
*Do not use pre-wired printed circuit board type
not used
EARTH BLUE
BROWN OR WHITE
GREY ORANGE
3 Port mid position motorised valve
4E5 89
ECA
N
4
N 4 2 4
4
3 3
3
3
3
2
2
2 2 1
1 L
2 1
L 1 1 1 1 3
CB
E
E E E
Vaillant VRT 9090
ACL Drayton Digistat 2, 3, 4
ACL Drayton RTS 1, 2
Danfoss Randall RX-1
Danfoss Randall RMT 230
Danfoss Randall RET 230
Tower SS
Honeywell T6360
Horstmann HRT 1
Siemens-Landys & Staefa RAD 1
Sunvic TLX 2000 series
5 9 6 L N E
Room thermostat
21C
YL
3
3 2
2 BK
1
2
2
1
1
RED
C 1
1 3
ACL Drayton HTS3
Danfoss Randall ATC
Tower CS1
Honeywell L641
Horstmann HTC1
Siemens-Landis & Staefa RAM 1
Sunvic SA 2452
8 4 7 E
Cylinder thermostat
3E
2
E
** see key below
Fig. 5.18
NL
234
53 8
76
1
not used
Lifestyle LP241, LP 522, LP 722
Tempus 6, Tempus 7
Danfoss Randall CP 715, FP715
Note: *Earth not required
Danfoss Randall Set 2E, Set 3E Note: *Earth not required,
Link L - 2 - 5
Grässlin Towerchron QE2
Honeywell ST699B, ST799A
Note: Link L - 5 - 8
Honeywell ST6200, ST6300, ST6400
Horstmann Channel Plus H21, H27 Note: *Ear th not required,
Link L - 2 - 5
Siemens-Landis & Staefa RWB2, RWB9
Potterton Myson EP 2002, EP 3002, EP 6002
Note: Link L - 5
Sunvic Select 207
NL
234
53 8
76
1
E
NL
234
53 8
76
1
E
*
NL
234
53 7
86
1
E
*
56
NL
234
53 8
76
1
N3
567
56
78
4
L
3
8
NL
234
53 8
76
1
NL
234
53 7
86
1
E
*
56
NL
234
53 8
76
1
NL
234
53 8
76
1
NL
234
53 8
76
1
E
5
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
5 Boiler Installation Sequence
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R124
5.19 Thermostatic radiator valves
The boiler has a built in automatic bypass valve making it ideal for use in systems with thermostatic radiator valves (no separate system bypass is required). For optimum fuel economy it is recommended that where TRV’s are used they are used in conjunction with a programmable room thermostat or separate timer and room thermostat to ensure complete boiler shut down when the heating demand is satisfied. (The radiator in the room containing the room thermostat should not be fitted with a TRV).
5.20 Frost protection
The boiler has an integral frost thermostat which is designed for protection of the boiler.To protect remote or exposed parts of the heating system or property additional frost protection measures must be taken such as the installation of an external frost thermostat. This frost thermostat should be connected across the boiler terminals 3 and 4, in parallel with any external heating controls. External frost protection cannot be used when plug in timers have been fitted.
5.21 Circulating pump
The boiler incorporates a built in circulating pump that is fully prewired (no additional wiring is necessary). The pump incorporates an automatic overrun period after the boiler switches off.
5.22 Anti-cycling ‘economiser’ control
The boiler incorporates a built in anti-cycling control to ensure that energy wasteful short cycling of the boiler cannot occur. This control prevents the boiler from re­igniting for a preset period of 5 minutes after central heating operation (the hot water operation is unaffected by this control and hot water can be drawn at any time).
Note! To temporarily override the anti-cycling control turn the main boiler on/off switch to the off position “0“ and then back to the on position “I“ after a few seconds.
Automatic pump spin control (APS)
The boiler incorporates a built in control which will spin the built in circulating pump and operate the diverter valve (turboMAX only) once in a 24 hour period. This control helps to prevent seizure when the boiler is not operated for a period of time. This control is not active when the power supply to the appliance is turned off.
Fig. 5.19
Key:
XCentral heating on YHot water on ZHot water off
Connection details for control systems utilising 2 x 2 port motorised valves via external wiring centre/junction box
Diagram only applies to the specific controls mentioned
LN
LN
345
N L
X** Y** Z**
3 amp fused main supply
THERMOcompact terminal strip
Programmer for programmer connections see fig. 16.d
LN
LN
345
5367 8
External wiring centre/junction box*
345678910
NNL
L
*Do not use pre-wired printed circuit board type
not used
EARTH BLUE BROWN GREY ORANGE
Hot water 2 port motorised valve
4E5 310
ECA
N
4
N 4 2 4
4
3 3
3
3
3
2
2
2 2 1
1 L
2 1
L 1 1 1 1 3
CB
E
E E E
Vaillant VRT 9090
ACL Drayton Digistat 2, 3, 4
ACL Drayton RTS 1, 2
Danfoss Randall RX-1
Danfoss Randall RMT 230
Danfoss Randall RET 230
Tower SS
Honeywell T6360
Horstmann HRT 1
Siemens-Landys & Staefa RAD 1
Sunvic TLX 2000 series
5 9 6 L N E
Room thermostat
21C
YL
3
3 2
2
BK
1
2
2
1
1
RED
C 1
1 3
ACL Drayton HTS3
Danfoss Randall ATC
Tower CS1
Honeywell L641
Horstmann HTC1
Siemens-Landis & Staefa RAM 1
Sunvic SA 2452
10 7 E
Cylinder thermostat
3E
2
E
E
EARTH BLUE BROWN GREY ORANGE
Central heating 2 port motorised valve
4E5 39
** see key below
Fig. 5.20
NL
234
53
not used
76
1
not used
Lifestyle LP241, LP 522, LP 722
Tempus 6, Tempus 7
Danfoss Randall CP 715, FP715
Note: *Earth not required
Danfoss Randall Set 2E, Set 3E Note: *Earth not required,
Link L - 2 - 5
Grässlin Towerchron QE2
Honeywell ST699B, ST799A
Note: Link L - 5 - 8
Honeywell ST6200, ST6300, ST6400
Horstmann Channel Plus H21, H27 Note: *Ear th not required,
Link L - 2 - 5
Siemens-Landis & Staefa RWB2, RWB9
Potterton Myson EP 2002, EP 3002, EP 6002
Note: Link L - 5
Sunvic Select 207
NL
234
53
not used
76
1
not used
NL
234
53
not used
76
1
E
5
not used
NL
234
53
76
1
E
not used
not used
NL
234
53
76
1
not used
E
*
not used
NL
234
53 7
6
1
E
*
not used
56
not used
NL
234
53
76
1
not used
not used
N3
567
56not used
7
4
L
3
8
not used
NL
234
53
76
1
not used
not used
NL
234
53 7
6
1
E
*
not used
56
not used
NL
234
53
76
1
not used
not used
Commissioning Part I 6
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 25
6 Commisioning Part I
6.1 Preliminary electrical checks
Check the electrical installation by carrying out short circuit, earth continuity and resistance to earth tests and a check for correct polarity.
6.2 Gas supply
The complete gas installation including the gas meter must be inspected, tested for soundness and purged in accordance with BS 6891. In IE the current edition of IS
813. The gas supply to the boiler can be purged by slackening the gas service valve beneath the boiler. Ensure that there is adequate ventilation, extinguish all naked flames and do not smoke whilst purging. After purging, the gas service valve connection must be retightened and tested for soundness. (The boiler itself does not require purging as this will be done by the automatic burner sequence control).
6.3 Cold water supply (turboMAX plus only)
Open all domestic hot water taps supplied by the boiler, turn on the mains water supply to the boiler and open the mains water isolating valve below the boiler. Water will now flow through the boiler to the hot taps. Starting with the lowest tap supplied, turn the hot taps off one at a time until the hot water pipework is purged of air. Check all hot and cold water pipework for leaks.
6.4 Filling the heating system (turboMAX plus)
Proceed as follows to fill the system:
• Open all radiator valves on the system.
• Check flexible filling loop is connected.
•Locate the filling valve handle on the cold water inlet filling valve as shown (1).
• Open valve (1) fully.
•Remove filling valve handle and locate on return filling valve (2).
• Open the valve slowly and fill the unit with water until the required pressure has been acheived (3).
•Turn off valve (2).
•Remove valve handle and refit on cold water inlet filling valve (1).
•Fully close valve (1).
•Bleed the air from the radiators.
•The boiler is equipped with an automatic air release valve. To allow this to vent the boiler, the cap top must be slackened by 1 - 2 turns. (This cap must be left slackened during operation to ensure any residual air or system gases are released).
Fig. 6.1: Fit boiler casing
3
1
90°
2
6 Commissioning Part I Gas supply adjustments (Com. Part II) 7
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R126
7 Gas supply adjustments
7.1 Gas inlet working pressure
To check the gas inlet working pressure:
•Lower the front panel of the boiler.
•Lower the control panel.
• Slacken the sealing screw (1) located at measuring point ”P.IN”.
•Attach U-gauge to the inlet test point on the gas valve (2).
• Ensure that the gas service valve is open.
•Turn off the boiler at the main ON/OFF control.
•Press and hold the ”+” button, while pressing the button turn the main ON/OFF control to the ”1” ON position.
•Continue holding ”+” button until display alternates between ”P1” and ”P2”. Release ”+” button.
•Press ”+” button until ”P1” (full gas rate) is shown in display.
•Press ”i” button to operate boiler at full gas rate.
• Check that the U-gauge is reading in the range between 18 and 20 mbar. If the pressure is not within this range this should be investigated before continuing with the commissioning procedure. Lower pressures than this range are indicative of an incorrectly sized or partially blocked gas supply.
•Switch off the boiler at the main ON/OFF control.
•Remove U-gauge, tighten test point sealing screw (1).
•Test for soundness.
•Record appliance working gas inlet pressure (mbar) in the Benchmark Installation, Commissioning and Service Log Book.
Fig. 7.1: Gas inlet working pressure
1
1
2
6.5 Filling the heating system (thermoCOMPACT)
The boiler and the heating system should be filled using a filling method as described on page 13.
• Ensure that the boiler CH service valves are open.
•Partially open the filling valve and allow water to enter the system. Starting with the lowest radiator, open the radiator air release until water (clear of bubbles) is emitted.
•Repeat this at all radiators until the complete system is full, all air locks have been cleared and the boiler pressure gauge reads 1.5 bar. Release any air from the pump by slackening the centre screw.
•The boiler is equipped with an automatic air release valve. To allow this to vent the boiler, the cap on the top must be slackened by 1 - 2 turns. (This cap must be left slackened during boiler operation to ensure any residual air or system gases are released).
• Check the heating system and boiler connections are sound.
6.6 Initial system flush (“cold“)
The whole of the heating system must be flushed out at least twice: once cold, and once hot as instructed later. Open all radiator and heating valves and the boiler CH service valves and drain the heating system and boiler completely from the lowest points of the system via 1/2” BSP drain taps (opened full bore to remove any installation debris prior to lighting the boiler). Refill the heating system. Check the operation of the pressure relief valve by rotating the knob on the valve. Now check the water pressure in the unit again (and add more water if necessary).
Gas supply adjustments (Commissioning Part II) 7
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 27
7.2 Main burner pressure
The burner pressure on this appliance has been factory set and does not require adjustment. To check the main burner pressure connect the U-Gauge as follows depending on the gas type.
•Remove front case and combustion chamber cover.
Note!
All measurements and adjustments to the gas valve must be done with the combustion chamber cover removed.
For natural gas appliances:
• Slacken the sealing screw (1) at test point on the gas valve and attach one arm of a U-gauge (2) to the test point.
For LPG appliances:
• Slacken the sealing screw (1a) at test point on the burner inlet gas pipe and attach one arm of a U-gauge (2a) to the test point.
Fig. 7.2
1
1a
2
2a
Connection for Natural gas
Connection for LPG
•Turn off the boiler at the main ON/OFF control.
•Press and hold the ”+” button, while pressing the button turn the main ON/OFF control to the ”1” ON position.
•Continue holding ”+” button until display alternates between ”P1” and ”P2”. Release ”+” button.
•Press ”+” button until ”P1” is shown in the display. ”P1” indicates the maximum gas rate and ”P2” indicates the ignition rate.
•Press ”i” button to operate boiler at maximum gas rate.
Check that the burner pressure is correct as shown in table 7.1 for the appropriate boiler. To cancel selected ”P1” or ”P2” mode press the ”i” and ”+” buttons simultaneously.
turboMAX plus only
Measure the domestic hot water burner operating pressure (mbar), the heat input (kW), the inlet/outlet domestic hot water temperatures (°C) and flow rate (l/min) by fully opening a hot water tap and record details in the boiler logbook.
thermoCOMPACT only
Record the heat input in the boiler logbook.
After completion of all tests tighten sealing screw, and check all test points for soundness (1/1a).
7. 3 Adjusting the central heating output
(range rating)
The boilers are fully modulating for central heating, and it is therefore not necessary to range rate the boiler. However, if desired, it is possible to range rate the boiler, as follows:
•Connect the U-gauge to check burner pressure.
•Use Table 7.1 (page 31-32) on to determine the central heating output required.
•Note the burner pressure setting.
•Turn on the central heating.
• Ensure that any thermostatic radiator valves are open and set to high.
• Simultaneously press and release the ”+” and ”-” buttons to activate burner pressure mode.
•The boiler will light at the factory set nominal gas rate.
Attention! DO NOT open any hot water tap while carrying out this procedure (turboMAX plus only).
• Check that the U-gauge reading corresponds to the maximum burner pressure as detailed on the table.
• Identify required range rating setting and note main burner pressure in mbar for that output.
•Adjust central heating output range as shown on page
29.
7 Gas supply adjustments (Commissioning Part II)
Note! Following adjustment of the central heating output, the new output can be checked using the gas rate table as detailed.
Fig. 7.3: Using burner pressure to check and adjust the heating system partial load (picture shows a turboMAX plus boiler)
Note! This illustration shows the U-tube pressure gauge connected to a system configured to run on natural gas. When connecting the U-tube pressure gauge to a system running on LPG, please refer to Fig. 7.2 on page 27.
• Simultaneously press the ”i” and ”+” buttons keys.
•Keep the ”+” button pressed until ”d.0” is displayed. (The display runs from ”d.0” to ”d.99” before restarting again at ”d.0”.)
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R128
•Press the ”i” button and a value between 1 and 15 will be displayed.
•Use the ”+” or ”-” buttons to increase or decrease the value. Observe the U-gauge as the button is pushed and stop pushing when the required main burner pressure has been achieved.
•After setting, press and hold the ”i” button for five seconds - or until the display stops flashing. The new setting value is now memorised. The new main burner pressure can now be checked. If the new output is not correct repeat steps 3 to 5.
•To return to normal mode, press the ”i” and ”+” buttons simultaneously. The adjustment mode is also cancelled if no button is pushed for a period of four minutes.
•Record central heating operating pressure in the Benchmark Log Book along with the heat input (kW) and temperature difference between flow and return.
1
~ 5 s
Gas supply adjustments (Commissioning Part II) 7
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 29
7. 4 Adjusting to the maximum heat load (nominal load)
• Undo screw and remove the cap (1)
turboMAX only:
•Set the DHW temperature control to maximum and
fire the boiler at full rate by fully opening a hot water tap.
thermoCOMPACT only:
•Turn off the boiler at the main ON/OFF control.
•Press and hold the ”+” button, while pressing the
button turn the main ON/OFF control to the ”1” ON position.
•Continue holding ”+” button until display alternates
between ”P1” and ”P2”. Release ”+” button.
•Press ”+” button until ”P1” (full gas rate) is shown in
display.
•Press ”i” button to operate boiler at full gas rate.
•Using a 10 mm spanner turn nut (2) to adjust the
burner operating pressure.
-Turn the nut (2) clockwise to increase the nominal
load
-Turn the nut (2) anticlockwise to decrease the nominal
load.
•Adjust the burner pressure until it matches the
maximum output as detailed.
•Now turn the 10 mm nut (2) anticlockwise until the
burner pressure drops by approx. 0.3 - 0.4 mbar.
Nominal load is now correctly adjusted.
•Refit the plastic cap (1).
Attention!
The plastic cap (2) must be fitted for the gas valve assembly to function correctly.
turboMAX only:
•Turn off the hot water tap.
thermoCOMPACT only:
•To cancel selected ”P1“ or ”P2“ mode press the ”i“ and
”+“ buttons simultaneously.
Fig. 7.4: Adjusting the ignition rate
1
2
7.5 Adjusting the ignition rate
• Undo screw and remove the cap (1).
turcoMAX only:
• Disconnect the modulating coil wires from the gas valve, set the DHW temperature control to maximum and fire the boiler at full rate by fully opening a hot water tap.
thermoCOMPACT only:
•Turn off the boiler at the main ON/OFF control.
•Press and hold the ”+” button, while pressing the button turn the main ON/OFF control to the ”1” ON position.
•Continue holding ”+” button until display alternates between ”P1” and ”P2”. Release ”+” button.
•Press ”+” button until ”P2” (ignition rate) is shown in display.
•Press ”i” button to operate boiler at full gas rate.
•Use a suitably sized screwdriver to turn the inner screw (2).
•Turn the screw (2) clockwise to increase the ignation rate
•Turn the screw (2) anticlockwise to decrease the ignation rate
•Adjust the burner pressure until it matsches the ignition rate as detailed on page 31 or 32.
turboMAX only:
•Turn off the hot water tap and reconnect the wires to the modulating regulator.
thermoCOMPACT only:
•To cancel selected “P1“ or “P2“ mode press the “i“ and “+“ buttons simultaneously.
Note! If installing/commissioning a turboMAX plus 837 or a thermoCOMPACT 637 boiler go to page
30.
Attention! The main burner pressure must be rechecked after adjusting the ignition rate.
Refit cap (1) and replace screw. Re-check ignition and main burner pressures. After completion of these tests tighten the sealing screw and check all joints and test points for soundness.
7 Gas supply adjustments (Commissioning Part II)
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R130
7.6 Checking the gas valve mid setting point (turboMAX plus 837 and thermoCOMPACT 637 only)
To ensure the most efficient operation of the boiler a gas valve mid setting point is necessary. This mid setting point has been factory set and adjustment of this point is only required after exchanging either the electronic circuit board or gas valve or converting the boiler to another gas type.
To check the mid setting point proceed as follows.
•Turn off the boiler at the main ON/OFF control.
•Press and hold the ”+” button, while pressing the
button turn the main ON/OFF control to the ”I” ON position.
•Continue holding ”+” button until display starts to
alternate between the P numbers (P1, P2, P3, P11, P12 and P13). Release ”+” button.
•Press ”+” button until ”P3 ” (mid setting point) is
shown in display.
•Press ”i ” button to operate boiler at mid setting
point.
•The burner pressure should now read the mid setting
point pressure for the gas type used, as detailed in the table below.
7.7 Setting or adjusting the mid-setting point
Turn off the boiler at the main ON/OFF control.
•Press and hold the ”+” button, while pressing the
button turn the main ON/OFF control to the ”I” ON position.
•Continue holding ”+” button until display starts to
alternate between the P numbers (P1, P2, P3, P11, P12 and P13). Release ”+” button.
•Press ”+” button until ”P11” (for natural gas) or "P 13"
(for LPG) is shown in display.
•Press ”i ” button to operate boiler at mid setting
point.
•The mid setting point burner pressure is now adjusted
by pushing the "+" button until the gauge equals the pressure as detailed in the table below.
Note!
The "-" button has no function in this mode, if the required pressure is exceeded during set up, this operation should be recommenced from the beginning.
When the pressure is correct, to save the setting to memory, press and hold the "i" button until the display stops flashing.
To cancel selected mode press the "i" and "+" buttons simultaneously.
Refit cap and replace screw. Re-check ignition and main burner pressures. After completion of these tests tighten the sealing screw and check all joints and test points for soundness.
Gas type Mid setting point presure
Natural Gas (G20) 5.3 mbar
LPG (G30/31) 15.3 mbar
Program No. Gas type Mid setting point
P.1 1 Natural Gas (G20) 5.3 mbar
P.12 Not applicable for GB -
P.13 LPG (G30/31) 15.3 mbar
Gas supply adjustments (Commissioning Part II) 7
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 31
Burner Pressure and gas rate
Burner Pressure thermoCOMPACT 615/2 E
Output[kW]
Gas type Ignition rate 6.5 8.0 10.0 12.0 14.0 15.0
Natural gas 2H Burner pressure1)[mbar]
Main burner jet mark
2)
for G20
2.2 2.2 3.2 4.7 6.6 8.7 9.9
7 / 120
LPG 3 B/P
Burner pressure1)[mbar]
Main burner jet mark
2)
for G30 4.1 4.1 6.2 9.6 13.6 18.1 20.6
7 / 072 for G31 5.8 5.8 8.7 13.3 18.7 24.9 28.3
Burner Pressure thermoCOMPACT 620/2 E Output[kW]
Gas type Ignition rate 7.7 8.0 10.0 12.0 14.0 16.0 18.0 20.0
Natural gas 2H Burner pressure1)[mbar]
Main burner jet mark
2)
for G20
1.5 1.5 1.6 2.4 3.4 4.6 5.9 7.4 9.0
7 / 120
LPG 3 B/P
Burner pressure1)[mbar]
Main burner jet mark
2)
for G30 2.0 2.0 3.2 5.0 7.3 9.9 12.8 16.1 19.7
7 / 072 for G31 4.3 4.3 4.5 71 10.1 13.7 17.6 22.0 26.9
Burner Pressure thermoCOMPACT 624/2 E, turboMAX plus 824/2 E Output[kW]
Gas type Ignition rate 8.9 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0
Natural gas 2H Burner pressure1)[mbar]
Main burner jet mark
2)
for G20
1.9 1.9 2.1 2.9 3.7 4.7 5.86.7 8.49.8
7 / 120
LPG 3 B/P
Burner pressure1)[mbar]
Main burner jet mark
2)
for G30 3.9 3.9 4.8 6.8 9.0 11.6 14.3 17.4 20.6 24.1
7 / 072 for G31 5.2 5.2 6.4 8.8 11.6 14.8 18.3 22.1 26.2 30.6
Burner Pressure thermoCOMPACT 628/2 E, turboMAX plus 828/2 E Output[kW]
Gas type Ignition rate 10.4 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0
Natural gas 2H Burner pressure1)[mbar]
Main burner jet mark
2)
for G20
1.8 1.8 2.3 3.0 3.9 4.8 5.8 6.8 8.0 9.2 10.5
7 / 120
LPG 3 B/P
Burner pressure1)[mbar]
Main burner jet mark
2)
for G30 4.1 4.1 5.3 7.1 9.0 11.2 13.5 16.1 18.8 21.7 24.8
7 / 072 for G31 5.5 5.5 7.1 9.5 12.1 15.0 18.1 21.6 25.2 29.1 33.2
Table 7.1: Burner pressure
1) 15 °C, 1013mbar, dry
2) The nozzles are stamped with the mark shown in this table. The marking corresponds to the nozzle hole diameter multiplied by 100
7 Gas supply adjustments (Commissioning Part II)
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R132
Gas Rate thermoCOMPACT 615/2 E Output[kW]
Gas type 6.5 8.0 10.0 12.0 14.0 15.0
Natural gas 2H Gas Rate1)[m3/h]
Main burner jet mark
2)
for G20
0.8 1.0 1.3 1.4 1.7 1.7
7 / 120
Gas Rate thermoCOMPACT 620/2 E Output[kW]
Gas type 7.7 8.0 10.0 12.0 14.0 16.0 18.0 20.0
Natural gas 2H Gas Rate1)[m3/h]
Main burner jet mark
2)
per G20
0.9 1.0 1.2 1.4 1.7 1.9 2.1 2.3
7 / 120
Gas Rate thermoCOMPACT 624/2 E, turboMAX plus 824/2 E Output[kW]
Gas type 8.9 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0
Natural gas 2H Gas Rate1)[m3/h]
Main burner jet mark
2)
for G20
1.1 1.2 1.4 1.7 1.9 2.1 2.4 2.6 2.8
7 / 120
Gas Rate thermoCOMPACT 628/2 E, turboMAX plus 828/2 E Output[kW]
Gas types 10.4 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0
Natural gas 2H Gas Rate1)[m3/h]
Main burner jet mark
2)
per G20
1.3 1.5 1.7 1.9 2.1 2.4 2.6 2.8 3.1 3.3
7 / 120
Gas Rate thermoCOMPACT 637E, turboMAX plus 837 E Output[kW]
Gas type 10.5 12.0 16.0 18.0 20.0 24.0 28.0 30.0 33.0 36.9
Natural gas 2H Gas Rate1)[m3/h]
Main burner jet mark
2)
per G20
1.3 1.5 1.9 2.2 2.4 2.8 3.3 3.5 3.9 4.3
7 / 120
Burner Pressure thermoCOMPACT 637, turboMAX plus 837 E Output[kW]
Gas type Ignition rate 10.5 12.0 16.0 18.0 20.0 24.0 28.0 30.0 33.0 36.9
Natural gas 2H Burner pressure1)[mbar]
Main burner jet mark
2)
for G20
1.2 1.2 1.5 2.5 3.1 3.8 5.3 7.1 8.1 9.7 12.0
7 / 120
Setting-up program: P.11 mid. setting point pressure: 5.3 mbar
LPG 3 B/P
Burner pressure1)[mbar]
Main burner jet mark
2)
for G30 2.8 2.8 3.5 5.9 7.3 8.9 12.6 16.8 19.1 22.9 28.2
7 / 072 for G31 3.5 3.5 4.4 7.3 9.1 11.1 15.6 20.8 23.7 28.3 34.9
Setting-up program: P.13 mid. setting point pressure: 15.3 mbar
Table 7.1: Burner pressure
Table 7.2: Gas flow rate 1) 15 °C, 1013mbar, dry
2) The nozzles are stamped with the mark shown in this table. The marking corresponds to the nozzle hole diameter multiplied by 100
Gas supply adjustments (Com. Part II) 7
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 33
7. 8 Fit combustion chamber cover
Carefully re-fit the combustion chamber cover to the boiler ensuring it is correctly sealed. Secure cover with retaining clamps.
7.9 Fit boiler casing
•Carefully push case (1) onto the boiler such that the locating points either side at the top of the boiler engage. Push the casing onto the securing clips at the bottom of the boiler.
• Close control panel (2).
•Secure control panel by turning both securing fasteners (3) clockwise by 90°.
• Fit and close front door (4).
• Fit lower cover plate (5).
Fig. 5.21: Fit boiler casing
VRC-VC
1
4
2
I
0
90°90°
3
5
8 Functional Checks
8.1 Functional checks
Procedure
Once the unit has been installed and the gas supply has been checked, operate the system to ensure that it is working correctly.
• Operate the system, following the operating instructions supplied with the boiler.
• Check the system for water leaks and escaping gas.
• Check that the flue has been correctly installed, according to the fitting instructions supplied with the flue assembly.
• Check the burner for correct ignition and flame picture.
ttuurrbbooMMAAXX pplluuss oonnllyy::
Check the hot water system
for correct operation.
• Check the heating system for correct operation.
Fig. 8.1 Test for correct functioning
8.2 Functional check of operation
(turboMAX plus only)
This boiler is fitted with indicator lights to display the operating status of the boiler. The status of the indicators in normal operation will be as follows.
Boiler in stand by mode
•Red lock out indicator (1) OFF.
•Yellow flame indicator (2) OFF.
•Green warmstart indicator (3):
- ON – Warmstart ON
- OFF – Warmstart OFF
Hot water operation
•Fully open hot water tap.
If boiler is operating correctly, the status of the indicators will be as follows:
•Red lock out indicator (1) OFF.
I
0
8 Functional Checks (Commissioning Part III)
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R134
•Yellow flame indicator (2) ON.
•Green warmstart indicator (3) FLASHING (hot water is being drawn from the system).
Central Heating operation
• Operate the heating system.
If boiler is operating correctly, the status of the indicators will be as follows:
•Red lock out indicator (1) OFF.
•Yellow flame indicator (2) ON (burner active).
•Green warmstart indicator (3) ON, OFF or FLASHING (see above).
The LCD display indicates the flow temperature (in °C) of the boiler in normal operation.
Fig. 8.2 Functional check turboMAX plus
8.3 Functional check of operation
(thermoCOMPACT only)
This boiler is fitted with indicator lights to display the operating status of the boiler. The status of the indicators in normal operation will be as follows.
Boiler in stand by mode
•Red lock out indicator (1) OFF.
•Yellow flame indicator (2) OFF.
•Green indicator (3) has no function.
Central Heating/hot water operation
• Operate the heating/hot water system.
If boiler is operating correctly, the status of the indicators will be as follows:
•Red lock out indicator (1) OFF.
•Yellow flame indicator (2) ON (burner active).
•Green indicator (3) OFF.
The LCD display indicates the flow temperature (in °C) of the boiler in normal operation.
Fig. 8.3 Functional check turboMAX plus
1
2
3
8.4 Adjusting pump speed
The unit is fitted with a two-speed pump. The pump is delivered with the switch (1) set to position III (Fig. 8.4.).
Attention! Important note:
The boiler should only be operated at pump setting III because the heating capacity for hot water is reduced when operated at pump setting II!
It is possible, however, to change the pump setting from Level III to Level II manually when there is noise coming from the heating system.
Final system flush (“HOT“)
•Turn on the boiler for central heating and allow the boiler and system to reach operating temperature.
• Check that the heating system is watertight.
•Turn the boiler off and rapidly drain both boiler and system while still hot.
•Refill the system and release all air. Release water from the system until the system design pressure of
1.0 bar is attained.
(The actual reading on the pressure gauge should ideally be 0.5 bar plus an additional pressure corresponding to the highest point of the system above the base of the boiler - 10 m head equals an additional 1 bar reading on the pressure gauge. The minimum pressure should not be less than 1 bar in any installation.)
If the system is to be treated with an inhibitor it should be applied at this stage in accordance with the manufacturers instructions.
Fur ther information can be obtained from Sentinel, GE Betz. Widnes, Cheshire, WA8 8UD. Tel: 0151 420 9595 or Fernox, Alpha-Fry Technologies, Tel: 0870 6015000.
• Disconnect the temporary filling connection.
•Refit the boiler casing.
•Attach the bottom cover to the boiler. It may be necessary to apapt the bottom cover by removing the easy break sections.
1
3
2
Functional Checks (Commissioning Part III) 8
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 35
Fig. 8.4: Pump speed
8.5 Handing over to the user
•Set the maximum radiator temperature control to the desired setting.
•Set the maximum hot water temperature control to the desired setting.
• Instruct the user in the safe and efficient operation of the boiler, in particular the function of:
-The boiler on/off control
-The maximum radiator temperature control
-The maximum hot water temperature control
((ttuurrbbooMMAAXX pplluuss oonnllyy))
-The pressure gauge
• Show the user how to operate any external controls.
• Explain to the user the importance of having the boiler regularly serviced by a competent servicing company. To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement. Please contact Vaillant Service Solutions (0870 6060 777) for further details.
• Ensure the boiler log book is fully completed and leave with the end user. Failure to install and commission this appliance to the manufacturers instructions may invaludate the warranty (Note: This does not affect your statutory rights).
•Leave the user instructions, the boiler log book and the installation and servicing instructions with the user.
1
9 Servicing
9.1 Initial Inspection
To ensure the continued safe and efficient operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once per year should be adequate. It is the law that all servic­ing work is carried out by a competent person (Corgi registered).
Improtant! Before starting any maintenance work:
•Isolate the mains electricity supply by disconnecting the plug at the socket outlet (if there is only an isolating switch remove the fuse from the switch).
•Turn OFF the gas supply at the gas service valve fitted to the boiler.
• Always test for gas soundness and always carry out functional checks after any service work and after exchanging any gas carrying component.
• Always check earth continuity, polarity and resistance to earth with a multimeter after any service work and after exchanging any electrical component.
Note! The boiler is fitted with a combustion analysis test points on the front of the combustion chamber cover. A suitable combustion analyser can be connected to these points to establish the combustion performance of the boiler.
Before commencing any servicing or maintenance work, carry out an initial inspection of the system as follows:
• Inspect the flue, pipework and electrical connections for indications of damage or deterioration.
• Inspect the air supply and ventilation arrangements of the installation.
• Check the heating and water system, in particular the condition of radiator valves, evidence of leakage from the heating system and dripping hot water taps.
Functional check of boiler operation
•Carry out a functional check of the boiler operation as prevoiusly detailed.
•Remove the appliance casing as detailed and operate the boiler by fully opening a hot water tap. Inspect the burner operation through the viewing window. Check that the flames are evenly covering the surface of the burner. Inspect for signs of excessive flame lift or sooting.
9.2 Cleaning the burner and primary heat exchanger
•Turn off the boiler.
•Isolate the electrical supply to the boiler.
•Remove the boiler case as described.
•Turn off the gas service valve.
9 Servicing
•Turn off the boiler CH service valves.
•Turn off the cold water inlet service valve.
•Release the three clamps (1), remove the combustion chamber cover (2).
9.2.1 For thermoCOMPACT 615, 637 and turboMAX
plus 837
•Remove the flue gas connector (2a) on the fan.
•Remove the retaining spring (3).
1155 kkWW::
Pull the three cables (4) and two tubes (5) from
the fan assembly.
3377 kkWW::
Remove both plugs (not illustrated) and both
hoses (5) from the fan.
•Remove the fan assembly (6).
•Remove the four screws (7) and detach the front cover panel from the combustion chamber (8).
• Check the burner (9) and heat exchanger fins (10) and remove any loose deposits with a soft brush.
9.2.2 For thermoCOMPACT 620, 624, 628,
turboMAX pro 24, 28 and turboMAX plus 824, 828
• Pull the three cables (4) and two tubes (5) from the fan assembly.
•Remove the fan assembly (6a, 6b, 6c).
•Remove the four screws (7) and detach the front cover panel from the combustion chamber (8).
• Check the burner (9) and heat exchanger fins (10) and remove any loose deposits with a soft brush.
•Reassemble in reverse order.
Check central heating expansion vessel.
Note! It is not necessary to carry out this check every year – a check every three years should be sufficient.
•Release the system water pressure from the boiler.
•Remove valve cap from expansion vessel charge point.
• Check that the internal charge pressure of expansion vessel is between 0.7 - 0.9 bar. If pressure is lower than this the vessel should be re-pressurised using an air pump.
•Refit valve cap.
• Open central heating service valves and re-pressurise the boiler and heating system if necessary.
• Open the gas service valve.
•Turn on the mains power supply.
• Operate the boiler and carry out soundness, safety and function checks.
•Complete the service interval record section in the log book and leave with the user.
Instructions for36
Fig. 9.1a Cleaning the burner and primary heat exchanger
(thermoCOMPACT 615, 637 and turboMAX plus 837)
Fig. 9.1b Cleaning the burner and primary heat exchanger
thermoCOMPACT 620, 624, 628, turboMAX pro 24, 28 and turboMAX plus 824, 828
6a
6b
7
9
10
8
2
1
5
5
4
6c
2
1
2a
3
4
4
8
4
5
5
6
10
9
7
Servicing 9
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 37
10.3 Indicator lights (thermoCOMPACT only)
The boiler control panel also contains three indicator lights whose function is as follows:
•Red lock out indicator (1), when illuminated boiler is at lock out.
•Yellow flame indicator (2), when illuminated main burner is ignited.
•Green indicator (3) is illuminated but has no function.
10.4 Logical fault finding procedure
These checks must be carried out before attempting to use the fault finding guide.
1. Carry out electrical safety checks (See Section ‘Preliminary Electrical Checks’).
2.Check that the external electricity supply to the boiler is on, and a supply of 230 V~ is present between boiler terminals ‘L’ and ‘N’.
3. Check that the gas supply to the boiler is on, that it has been correctly purged and that an inlet pressure of 20 mbar is available at the gas valve. (See Section ‘Gas Supply’).
4.Ensure the heating system is full of water and charged to between 1 and 1.5 bar. If not, refill and vent the system. (See Section ‘Filling the heating system’). Ensure boiler flow and return service valves are open.
5.Check that the main ON/OFF control is set to the ‘ON’ position.
6.Set the central heating temperature to maximum.
7. Set the domestic hot water temperature to maximum (turboMAX only).
8.Check that all external controls are on and calling for heat (if, no external controls are fitted, boiler terminals 3 and 4 must be linked). Check that the boiler anti-cycling economiser is not engaged.
Procedure
Note! Always check the operation of the boiler for central heating first before checking hot water operation. Do not open a hot water tap unless instructed to do so by the fault finding guide (turboMAX only).
1. If a fault code is showing in the boiler display follow the fault finding charts referring also to the fault code and diagnostic mode tables.
2.If the boiler is not functioning correctly and a fault code is not showing in the boiler display follow the fault finding charts referring also to the status mode table.
Note! If the boiler display is completely blank initially check the two fuses (Isolate the electrical supply before checking the fuses, spare fuses are located on the inside of the control box rear cover).
10 Fault Finding
10.1 Introduction
The turboMAX plus and thermoCOMPACT boilers have an inbuilt advanced multifunction diagnostic display to assist with fault finding in the unlikely event of a boiler malfunction. The display features the following four modes:
Normal Mode
Under normal conditions the boiler display will show the boiler flow temperature, this indicates that the boiler is operating correctly after an internal self check.
Status Mode
The status display is helpful in diagnosing faults where a fault code is not displayed.
Diagnostic Mode
In order to assist with the pinpointing of a particular fault it is possible to use the boiler display in a diagnostic mode to interrogate the boiler about the status of certain components.
Fault Mode
Should a fault develop in the boiler the display will show a fault code indicating what the problem may be.
10.2 Indicator lights (turboMAX plus only)
The boiler control panel also contains three indicator lights whose function is as follows:
•Red lock out indicator (1), when illuminated boiler is at lock out.
•Yellow flame indicator (2), when illuminated main burner is ignited.
•Green warmstart indicator (3):
Illuminated = Warmstart switched ON Not illuminated = Warmstart is switched OFF and there is no demand for hot water Flashing = There is either a demand for hot water or warmstart
Fig. 10.1 LED indicators
1
2
3
To access the various modes press the buttons on the control panel as follows:
Note! If no key is pressed for approx. 4 minutes the display will automatically change back to Normal mode.
10 Fault Finding
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R138
10.5 Status Modes
The status mode provides information about the current operating status of the boiler. To display status mode proceed as follows:
•Press the “i” button below the display, and a status code will appear in the display indicating the current operational status of the boiler (see table below).
To cancel the status code mode proceed as follows:
•Press the “i” button below the display
or
• Do not press any key for approximately four minutes.
•The display will now revert back to showing the current flow temperature.
Display Indication turboMAX plus thermoCOMPACT
S.00 No heat demand (heating operation) x x
S.01 Fan running (heating operation) x x
S.02 Pump running – pre ignition (heating operation) x x
S.03 Ignition sequence (heating operation) x x
S.04 Burner ignited (heating operation) x x
S.05 Fan and pump over run (837/637 only) x x
S.07 Pump over run (heating operation) x x
S.08 Anti cycling mode (heating operation) x x
S.10 Hot water demand (hot water operation) x
S.11 Fan running (hot water operation) x
S.13 Ignition sequence (hot water operation) x
S.14 Burner ignited (hot water operation) x
S.16 Fan over run (hot water operation) x
S.17 Pump over run (hot water operation) x
S.20 Warmstart demand (warm start) x
S.21 Fan running (warm start) x
S.23 Ignition sequence (warm start) x
S.24 Burner ignited (warm start) x
S.27 Pump over run (warm start) x
S.28 Anti cycling mode (warm start) x
S.30 No heating demand from external controls x x
S.31 Summer mode (heating control knob in off position) x x
S.32 Main heat exchanger anti freeze protection due to fan speed deviation x
too great (837/637 only)
S.33 Check air/flue system x x
S.34 Frost protection mode x x
S.36 No heating demand from low voltage controls x x
S.39 Contact thermostat has been activated (under floor systems) x x
S.53 Delay mode due to lack of water in system (~2,5 mins.) x x
S.54 Delay mode due to flow temperature gradient too steep
(approx 10 mins.) x x
Mode Status mode Diagnostic mode
To display Press “i“ button Press the “i“ and
the reqiured mode “+“ button
simultaneously
To return to Press “i“ button Press the “i“ and
Normal mode “+“ button
simultaneously
Table 10.1: Status modes
Fault Finding 10
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 39
Display Indication Displayed values/adjustment values
d.00 Part load setting 0 - 15 (0 - 30, 837/637 only) d.01 Water pump over run 1, 2, 3, …60 min (factory adjusted setting: 5 min) d.02 Maximum burner anti cycling period at 20 °C flow temperature 8 - 60 min (predelivery setting: 15 min) d.05 Flow temperature setting °C d.07* 1. Vantage hot water temperature (not applicable) 1. 15 - 75 °C
2. Warmstart temperature setting (applies to turboMAX plus only) 2. 40 - 65 °C d.08 External controls heat demand 0 = open, no demand; 1 = closed, demand d.10 Pump status 1 = ON; 0 = OFF d.11 External pump status 1 = ON; 0 = OFF d.21 Flame rectification 1 = ON; 0 = OFF d.22* Domestic hot water demand 1 = ON; 0 = OFF d.23 Summer/winter function (control knob) 1 = winter; 0 = summer d.24 Air pressure switch 1 = ON; 0 = OFF d.25* Warmstart status (turboMAX plus) 1 = ON; 0 = OFF d.30 Gas valve status 1 = ON; 0 = OFF d.33 Required value of the rotary speed of the fan r.p.m. (837/637 only) d.34 Actual value of the rotary speed of the fan r.p.m. (837/637 only) d.35* Diverter valve position 1 = hot water; 0 = heating system d.37 Modulator current mA d.40 Actual flow temperature °C d.41 Current return temperature (837/637 only) in °C d.50 Maximum flow temperature °C d.60 Number over heat cut off operations d.61 Number of lock outs s d.64 Average ignition time s d.65 Maximum ignition time s d.67 Remaining anti cycling period min d.68 Number of unsuccessful attempted 1st ignitions d.69 Number of unsuccessful attempted 2st ignitions d.71 Maximum target value for heating system flow temperature 0 = 82 ° C ; 1 = 87 °C (factory setting: 82 °C) d.72* Pump over run (for loading warmstart) 0, 1, 2, … 250 s (factory-adjusted to: 80 s)
d.73* Offset warmstart temperature value -15, -14.......+5 K (factory-adjusted - 5 K)
d.75 Maximum hot water priority operation time (Vantage only) 20, 21, 22 … 90 min (factory-adjusted to: 30 min) d.76 Gas type set (837/637 only) H36 (nat gas) P36 (LPG) E36 (E+ gas).
Factory setting H36 d.80** Number of heating system operating hours (Total) h d.81* Number of hot water system operating hours (Total) h d.82 Number of heating system cycles (Total) d.83* Number of hot water system cycles (Total)
10.6 Diagnostic Modes
In order to assist with the pinpointing of a particular fault it is possible to use the boiler display in a diagnostic mode to interrogate the boiler about the status of certain components.
•Press the “i“ and “+“ buttons below the display simultaneously. The display will now show “d.00“.
•Use “+“ or “-“ buttons to scroll up or down to the desired diagnosic number.
•Press “i“ button to display the corresponding diagnosic information.
• If necessary, you can now alter the value by pressing “+“ or “-“ buttons. (When altering values display will flash). Press and hold the "i” button to save the value to memory, when the value is saved the display will stop flashing.
Diagnosic mode is cancelled as follows:
•Press the “i“ and “+“ buttons simultaneously
or
• Do not press any key for approximately four minutes. The display will now revert back to showing the current flow temperature.
Table 10.2: Diagnostic Modes * turboMAX plus only
10 Fault Finding
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R140
10.7 Fault codes
Fault codes take priority over all other display functions in the event of a system fault occurring. If multiple faults occur, the corresponding fault codes are displayed alternately for about two seconds each.
10.8 Fault memory
The fault memory stores details of the ten most recent faults.
•Press the “i“ and “-“ buttons simultaneously.
•Use the “+“ button to scroll back through the list of memorised errors.
To cancel fault error memory display mode, proceed as follows:
•Press the “i“ button below the display.
or
• Do not touch any key for about four minutes. The display will now revert back to showing the current flow temperature.
Display Indication Displayed values/adjustment values
F. 00 Flow-NTC:
NTC broken; NTC cable broken; Defective connection at NTC Defective connection at electronics Flow-NTC cable defective/ broken NTC faulty
F. 01 Return NTC:
NTC broken; NTC cable broken; Defective connection at NTC
Defective connection at electronics Return-NTC cable defective/broken NTC faulty F.10 Short circuit - flow-NTC (<130°C) NTC-plug shorted to casing, NTC defective F.11 Short circuit - return-NTC (<130°C) NTC-plug shorted to casing, NTC defective F. 20 Over heat cut off activated Maximun temperature exeeded F. 22 Dry fire protection No water in appliance, pump cable defective, pump
blocked or defective, pump output too low
F. 23 Dry fire protection (difference between flow and No water in appliance, pump cable defective, pump
return NTC's too large) blocked or defective, pump output too low F. 24 Dry fire protection (temperature gradient of flow NTC too steep). Air in boiler/system, pump blocked or defective, pump
output too low F. 27 No demand to gas valve Electronic board defective; Gas valve defective F. 28 Boiler goes to lock out No gas; Isufficient gas; Incorrect gas valve
adjustment; Electrode defective; Ignition lead defect;
Electronic igniter defective F. 29 Flame extinguished re-ignition unsuccesful Gas supply absent or insufficient F. 32 Main heat exchanger anti freeze protection mode Check fan control cables/connections; Defective fan (837/637 only) due to fan speed deviation too great control cable; F. 33 Main heat exchanger anti freeze protection mode Check air pressure switch, fan, fan supply or flue (837/637 only) due to no switching signal from the air pressure switch system F. 37 The rotary speed of the fan is too high or too low Air pressure switch defect; fan defect; electronics defect (837/637 only) F. 41 No setting for the type of gas is stored Set gas type in PCB (see page 30) (837/637 only) F. 42 Faulty cable loom Faulty or incorrect loom fitted F. 43 Faulty cable loom Faulty or incorrect loom fitted F.60 Electronic fault Electronics defect F. 61 Electronic fault Electronics defect F. 62 Flame rectification present 4 secs. after gas valve turns off Check gas valve, burner tubes and injectors or
electronics defect F.63 EMC fault EMC or electronics defect F.64 Sensor or electronics fault Check NTC's/connections or electronics defect F. 65 PCB processor temperature too high Check earth connection or electronics defect F.66 Display fault Display defect; fault in the connection to the display;
electronics defect F. 67 Electronic fault Electronics defect
Table St.2: Fault codes
Fault Finding 10
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 41
Ensure boiler main
ON/OFF control is set
to position "1"
Is there a display on
the LCD Panel?
Yes Go to sheet C
Check electrical supply, appliance fuses and on/off control
No
Is 230VAC present across
terminals L and N?
Yes
Is 230VAC present across
terminals 3 and 5?
Yes
Is voltage between
16-26 VDC present across
terminals 8 and 9?
Yes
Is 5 VDC present between
5V and GND test points
on electronic board?
Replace LCD display
Yes
NoRepair external fault
Is the continuity
across fuse F1?
Go to sheet B
Does ON/OFF knob
operate switch on
electronic board
Boiler ON/OFF control
defective,
change electronic
board
Replace switch
mechanism
No
No
No
Yes
Yes
Note 1:
For test purposes, disconnect
external controls from terminal
3 - 4 and replace with a bridge
between these terminals.
It appliance then operates, the
fault is with the external controls.
Sheet A
Is there continuity
across fuse F3?
No
No
Replace electronic
board
No
Check transformer
Replace if
necessary
Yes
10 Fault Finding
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R142
Sheet BCheck operation of pump and fan
Turn off the main ON/OFF control to the
"0" position
Disconnect the power supply to the boiler
Go to sheet A
Is there a display on the LCD panel?
Check transformer 230 VAC primary
(black/red) and approx. 17 VDC secondary
(blue/brown)
Check/replace pump
Replace fuse F1
If fan commences operation, exchange
gas valve
After approx. 20 secs.
Does fuse F1 blow?
Produce central heating demand.
Does fuse blow immediately?
Turn the main ON/OFF control to the "1"
position
Is t here a display on the LCD panel?
Yes
No
No
No
Yes
Check/replace fan Replace electronic board
No
Yes
Yes
Fault Finding 10
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 43
Check central heating and controls
Ensure that radiator temperature control knob
is set to vertical position and that any internal
timer (if fitted) is calling for heat
Check diagnostic code D.08 (see page
53). Is heating demand present?
No
Is 230 VAC present across terminals 4 and 5
No
External fault: Check all external controls are
calling for heat, replace or repair as necessary
(see also note 1 sheet A)
Yes
Yes
Does failure code show on LCD display?
Disconnect built in timer (if fitted)
No Go to sheet D
Does ignition
commence?
No
Yes
Replace defective
timer
Sheet C
10 Fault Finding
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R144
Does fan run after approx. 30 secs.?
Check flue and ignition system
No
Check diagnostic code D.24
(see page 53) equal 1?
Check pitot tube (in fan outlet) and air
hoses are not obstructed and correctly
aligned.
Check or replace air pressure switch.
837/637 Check 4 pin connector for
fan speed control.
Does the fan run now?
Is 230 VAC present across fan
terminals?
Replace electronic board
Yes
No
No
Yes
No
Yes
Yes Check/replace fan
Does the boiler
commence ignition
Check status code
(see page 52) is S.33?
Check air/flue gas system
is correctly fitted and not
obstructed
Yes
No
Replace electronic board
No
Yes
Are electrodes sparking at
the burner?
Yes Go to sheet E
No
Check electrodes and
electrode leads.
Replace as necessary.
Sheet D
Check flue restrictor
correspond to flue length
Fault Finding 10
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 45
Check gas valve and central heating system pressure
Does burner light 1st
attempt?
Does burner light within 3
ignition attempts?
No
Yes
Check gas supply
Does burner light?
Yes
Check burner pressure
settings are correct
Yes
No Reset boiler
No
Check/replace gas valve
as necessary
Does burner light?
No
Replace electronic board
Yes
Is burner indicator
illuminated?
No
Check flame
rectification lead and
electrode
Is burner indicator
illuminated
No
Yes
Does burner shut down after
approx. 15 secs.
No Go to sheet F
Yes
Does status code (see page 52)
show S. 53?
Check water pressure in
central heating system, refill
and vent. as necessary
Check pump is running?
Yes
Yes Replace pump
No
Is 230 VAC present at the
pump plug connection?
No
Replace electronic board
Sheet E
10 Fault Finding
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R146
Does flame indicator glow and
flames increase in size to full gas
rate after approx. 2 mins?
Yes
Does burner flame modulate/ go
out when radiator temperature
control is turned left to the
horizontal position at flow
temperature of approx. 50 C?
Yes
Does heating flow pipe
temperature rise?
Go to sheet GYes
Check operation of burner and modulation
Ensure flow and return service
valves are open
No
No
No
Replace electronic board
No
Check operation of boiler in DHW
mode, does flame increase in size
to full rate? (TURBOmax Plus only)
Yes
Check partial load
setting
No
Check diagnostic code D.22
(see page 53) equals 1
(TURBOmax Plus only)
No
Go to sheet G
Yes
Check connections and
modulator, replace gas valve if
burner still fails to increase to full
rate
Turn main ON/OFF control to
the "0" position (TURBOmax
Plus only)
Yes
Insert a small screwdriver
through the hole in the front of
the diverter valve and hold
blade lightly against spindle
Turn "ON" the main ON/OFF
control
Does spindle move?
Yes
Replace electronic board
Replace diverter valve
No
Sheet F
Fault Finding 10
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 47
Draw hot water at high rate
Does green warmstart
indicator flash?
Yes
Check hot water flow rate and temperature.
Compare with technical data, if flow is not
sufficient check incoming main and cold water
filter.
Normal operation carry out
electrical safety checks
No
Check cold water inlet pressure is
sufficient and that cold water inlet
filter is clear
Check cold water inlet is fully open
and adjustment is at maximum
flow rate
Does green warmstart
indicator flash now?
Check/Clear impeller in
Aquasensor, replace if necessary
Check/replace hall sensor
Replace electronic board
Does hot water indicator
glow/flash now?
Does green warmstart
indicator flash now?
No
No
Yes
Yes
No
Sheet G
No
Check D.H.W operation (turboMAX plus only)
Note! turboMAX plus only
11 Diagrams
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R148
11.1 Functional Flow diagram: turboMAX plus 824/2 E, 828/2 E, 837 E
Fig. 11.1: Functional Flow diagram VUW
POWER SUPPLY
F2A
L
2
N
1
MAIN SWITCH
MAIN
TRANSFORMER
230V 20V
AIR
PRESSURE
SWITCH
PUMP
NTC FLOW
TEMPERATURE
SENSOR
FLAME
SENSOR
GAS
VA LV E
DHW
Aqua
Sensor
F1,25A
NTC RETURN
TEMPERATURE
SENSOR
Burner lock out indicator (red)
Hot water/warmstart demand indicator
Ignition indicator
MAIN SWITCHBOARD
IGNITION
ELECTRODES
Legend
b blue br brown y/g yellow/green r red p pink or orange t transparent bl black gr grey w white
gr
b
r
bl
b
gr
br
y/g
bbr
y/g
br
t
w
p
t
br
br
r
b
br
y/g
gr
p p
r
CONTROL BOX
DIVERTER
VA LV E
bl
bl
bl
bl
NTC
WARMSTART
TEMPERATURE
SENSOR
or
plug in
connector
display
plus / minus buttons
reset button
info button
FAN
837 only
Diagrams 11
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 49
Functional Flow diagram: thermoCOMPACT 615/2 E, 620/2 E, 624/2 E, 628/2 E, 637 E
Fig. 11.2: Functional Flow diagram VU
POWER SUPPLY
F2A
L
2
N
1
MAIN SWITCH
MAIN
TRANSFORMER
230V 20V
AIR
PRESSURE
SWITCH
FAN
PUMP
NTC FLOW
TEMPERATURE
SENSOR
FLAME
SENSOR
GAS
VA LV E
F1,25A
NTC RETURN
TEMPERATURE
SENSOR
Burner lock out indicator (red)
Ignition indicator
MAIN SWITCHBOARD
IGNITION
ELECTRODES
Legend
b blue br brown y/g yellow/green r red p pink or orange t transparent bl black gr grey w white
gr
b
br
y/g
bbr
y/g
br
t
w
t
br
br
r
b br
y/g
gr
r
CONTROL BOX
plug in
connector
display
plus / minus buttons
reset button
info button
r
bl
b
gr
637 only
11 Diagrams
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R150
Wiring diagram: turboMAX plus 824/2 E, 828/2 E, 837 E
Fig. 11.3: Wiring diagram VUW
Switchgear cabinet
U100
X3
T 2
= F1
T 1,25
= F3
X2
X2
X1
24
23
11213
14
15
16
17
18
19
20
21
22
2
3
4
5
6
7
8
9
10
11
432
1
X2
NTC
NTC
Warmstar t
earth
Ionisation
electrode
NTC
flow
NTC
return
Lifting magnet
24
23
11213
14
15
16
17
18
19
20
21
22
2
3
4
5
6
7
8
9
10
11
Fan unit
Ignition
electrodes
Gas valveDiverter valveAir pressure switch
NTC Warmstart
Ionisation
electrode
Pump
NTC return
12
EV1
EV2
34
X8X4 (VUV)
X12
X14 X13
79 L 48N35
X7 Accessories
NTC flow
Aqua
sensor
Aqua
sensor
Pressure sensor
X20
Coding resistor
(837 E only)
Diagrams 11
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R1 51
Wiring diagram: thermoCOMPACT 615/2 E, 620/2 E, 624/2 E, 628/2 E, 637 E
Fig. 11.4: Wiring diagram VU
Switchgear cabinet
U100
X3
T 2
= F1
T 1,25
= F3
X2
X2
X1
24
23
11213
14
15
16
17
18
19
20
21
22
2
3
4
5
6
7
8
9
10
11
X2
Pressure sensor
NTC
earth
Ionisation
electrode
Coding resistor
NTC flow
NTC return
Lifting magnet
24
23
11213
14
15
16
17
18
19
20
21
22
2
3
4
5
6
7
8
9
10
11
Fan unit
Ignition
electrodes
Gas valveAir pressure switch
Ionisation
electrode
Pump
NTC flow
NTC return
X8X4 (VUV)
X12
X14 X13
79 L 48N35
X7 Accessories
12
EV1
EV2
34
432
1
X20
Bridge
(637 E only)
83 37 86_30 GB R2 04/2003 Mü Printed on 100 % recycled paper · Subject to alteration
Head Office: Vaillant Ltd.
Service Solutions 0870 6060 777
Vaillant House
Trident CloseMedway City Estate
Rochester
Kent ME2 4EZ
Technical Advice 01634 292392
Loading...