Vaillant Mixer module VR 60 Installation Instructions Manual

For the heating engineer
For the heating engineer
Installation instructions
Installation instructions
Mixer module VR 60
Mixer module VR 60
Bus module control system
Bus module control system
VR 60
GB
Contents 1 Notes on the documentation 2 Description of the device
1 Notes on the documentation .........................2
2 Description of the device ...............................2
2.1 Identification plate ..................................................3
2.2 CE-mark/conformity ...............................................3
2.3 Intended use .............................................................3
3 Safety instructions and regulations ............3
3.1 Safety instructions .................................................3
3.2 Regulations ...............................................................3
4 Fitting ...............................................................4
4.1 Scope of delivery ....................................................4
4.2 Accessories ...............................................................4
4.3 Assembling VR 60 mixer module ........................4
5 Electrical installation .....................................5
5.1 Connecting the mixer module to the
building ......................................................................5
5.2 Connecting the heating circuit as a cylinder charging circuit (not with Vaillant
geoTHERM VW.. .../2 heat pump.) .......................6
5.3 Setting the Bus address ........................................7
6 Start-up ............................................................7
7 Technical data ................................................. 7
8 Warranty and customer service ...................8
8.1 Vaillant warranty.....................................................8
8.2 Vaillant service ........................................................8
1 Notes on the documentation
The following information is intended to help you throughout the entire documentation. Further documents apply in combination with this instal­lation manual.
We accept no liability for any damage caused by fail­ure to observe these instructions.
Other applicable documents
Observe the individual operating and installation manu­als of the various components of the plant when install­ing, commissioning and starting up.
Storage of the documents
Pass on this installation manual to the owner of the sys­tem in order for him/her to store it so that it is available whenever it is required.
Symbols used
Please observe the safety instructions in this installation manual for the installation of the appliance. The symbols used in the manual are explained below:
Danger!
d
Immediate risk of serious injury or death
Danger!
e
Danger of death by electric shock!
Caution!
a
Potentially dangerous situation for the product and environment.
Note!
h
Useful information and instructions
• Symbol for a necessary task
Applicability of the instructions
These installation instructions apply exclusively to units with the following part numbers: – 306782 – 0020076591 The part number of the unit can be found on the identi­fication plate.
2 Description of the device
The VR 60 mixer module is used for system expansion of the auroMATIC 620 or VRC 630 controllers and
Vaillant geoTHERM VW.. .../2 heat pumps.
Up to a maximum of six mixer modules can be connect­ed. Two additional mixer circuits can be controlled per VR 60 mixer module.
Installation instructions Mixer module VR 60 0020020171_022
Description of the device 2
Safety instructions and regulations 3
These mixer circuits can be programmed via the auroMATIC 620 or VRC 630 controllers, or the operating section of the Vaillant geoTHERM
VW.. .../2 heat pumps or, if required, via a separate
VR 80 or VR 90 remote control unit.
Each mixer circuit can, as required, be switched be­tween: – Heating circuit (radiator circuit, floor circuit, etc.) – Fixed value control – Return flow boost – Hot water circuit (storage tank charging circuit, in ad-
dition to integrated hot water circuit). The "Return flow boost" and "Hot water circuit" options
are not available with the Vaillant geoTHERM VW.. .../2
heat pumps.
With the telephone remote contact connection (floating contact) on the auroMATIC 620 or VRC 630, the con­troller’s operating mode can be changed by telephone by means of the teleSWITCH telephone remote switch.
2.1 Identification plate
The identification plate for the VR 60 mixer module is located on the outside on the left hand side of the cas­ing.
2.2 CE-mark/conformity
The CE label documents that the mixer module VR 60, in connection with Vaillant boilers, fulfils the basic re­quirements of the following directives: – Directive relating to electrical equipment designed for
use within certain voltage limits (2006/95/EWG) – Directive relating to electromagnetic compatibility
(2004/108/EWG)
2.3 Intended use
The mixer module VR 60 is a state-of-the-art appliance which has been constructed in accordance with recog­nised safety regulations. Nevertheless, there is still a risk of death or serious injury to the user or others or of damage to the device and other property in the event of improper use or use for which it is not intended.
3 Safety instructions and regulations
The mixer module VR 60 must be installed by a qualified engineer, who is responsible for adhering to the existing standards and regulations. We accept no liability for any damage caused by failure to observe these instructions.
3.1 Safety instructions
Danger of death by electric shock!
e
Before carrying out work on the controller, switch off the power supply and secure it against being switched on again. Operating the mains switch on the VR 60, auroMATIC 620 or
VRC 630 or the Vaillant geoTHERM VW.. .../2
heat pumps is not in itself sufficient to ensure that all the terminals on the system are volt­age free.
3.2 Regulations
All wiring must be in accordance with Building Regula­tions Part P and BS 7671 (IEE Wiring Regulations), and must be carried out by a suitably qualified person.
Standard cable must be used for wiring. Minimum cross-section of the cable: – 230 V connecting cable
(pump or mixer connection cable) 1.5 mm solid conductor – Low-voltage leads
(sensor or Bus leads) 0.75 mm
Do not exceed following maximum wire lengths: – Sensor connection 50 m – Bus lead 300 m
If sensor and eBus leads run parallel to 230 V leads over a distance greater than 10 m, they must be laid sepa­rately at a spacing of at least 25 mm. 230 V connection leads must be implemented with
2
1.5 mm cable clamps supplied.
solid cable and fastened in the casing using the
2
2
The VR 60 mixer module is a system component in the auroMATIC 620 or VRC 630 modular bus control sys­tems for controlling hot water central heating installa­tions with integrated hot water generation. The VR 60 mixer module can also be used as a system component
with the Vaillant geoTHERM VW.. .../2 heat pumps for
controlling hot water central heating installations. Any other use or extended use is considered to be improper. The manufacturer or supplier is not liable for any result­ing damage. The owner alone bears the risk. Intended use includes the observance of the installation manual.
Do not use free terminals of the appliances as support terminals for other wiring. The unit must be installed in a dry room.
3Installation instructions Mixer module VR 60 0020020171_02
4 Fitting
4 Fitting
The VR 60 mixer module should be mounted on the wall in a suitable position close to the mixer circuits to be controlled. Using the VR 60 mixer module, extension of the heating installation by two mixer circuits is possible. Up to a maximum of six mixer modules can be connect­ed. A unique bus address is set on the VR 60 mixer module using the rotary switch. Setting the heating programmes and all the required parameters is done via the auroMATIC 620 or VRC 630 controller using the eBus or the operating section of the Vaillant geoTHERM VW...2 heat pump. All heating circuit specific connections (sen­sors, pumps) are made directly on the mixer module via ProE connectors.
4.1 Scope of delivery
Before starting the installation, check the scope of deliv­ery for completeness and lack of damage.
Pos. Amount Component
1 1 Mixer module VR 60 2 2 VR 10 standard sensor 3 1 eBus lead, 3 m long
Table 4.1 Scope of delivery of the mixer module VR 60
4.2 Accessories
VR 90 remote control device
For the first eight heating circuits (HK 1 ... HK 8) its own remote control unit can be connected. It permits the ad­justment of the method of operation and the target room temperature and takes account of the room tem­perature using the integrated room sensor. It is also possible to adjust the parameters for the asso­ciated heating circuit (time programme, heating curve etc.) and to select the special functions (party etc.). In addition, it is possible to call up the displays of heating circuit and maintenance and faults on the boiler. Com­munication with the heating control unit is via the eBus.
VR 80 remote control device
The VR 80 is a remote control unit for controlling a heating circuit within a control system with an auroMATIC 620 or VRC 630 controller or the Vaillant
geoTHERM VW.. .../2 heat pump. Regardless of whether
this remote control unit is used, all the settings for this heating circuit are possible using the auroMATIC 620 or VRC 630 controllers, or the operat-
ing section of the Vaillant geoTHERM VW.. .../2 heat
pump.
Fig. 4.1 Opening the casing
• Release the screw on the top of the casing.
• Tilt the casing cover forwards slightly and remove.
230 V~
230 V~
HKa HKa-P HKb-P AF
PE N L PE N L PE N LPE N Auf Zu PE N L AF 0
HKb
PE N Auf Zu
VFb
BUS
VFa
2 1
+ -
2 1
1
2
Fig. 4.2 Fitting the mixer module VR 60
• Mark the two fixing points at a suitable position in ac-
cordance with the fixing openings (1).
• Drill two holes for the suitable plugs and screw the
casing securely in position.
• The electrical installation is carried out as described in
Chapter 5.
• Insert the casing cover back into the hinges and hinge
the casing cover back up into position.
• Screw the casing cover in position in accordance with
Fig. 4.1.
4.3 Assembling VR 60 mixer module
The connection rails of the mixer module VR 60 are of the type System ProETechnik. All onsite connections must be made using these rails.
4
Installation instructions Mixer module VR 60 0020020171_024
5 Electrical installation
The electrical connection must be done by a suitably qualified heating engineer who is responsible for com­plying with the existing standards and guidelines.
Danger of death by electric shock!
e
Before carrying out work on the controller, switch off the power supply and secure it against being switched on again. Operating the mains switches on the VR 60 mixer module and on the auroMATIC 620 or VRC 630 controllers or the Vaillant
geoTHERM VW.. .../2 heat pumps is not in itself
sufficient to ensure that all the terminals on the system are voltage free.
If the casing of the VR 60 mixer module is closed, open it as described in Chapter 4.3.
5.1 Connecting the mixer module to the building
• Wire up the VR 60 mixer module as shown in Fig. 5.1.
• Use the supplied eBus connection cable to incorporate the mixer module VR 60 in the communication sys­tem. The eBUS can be branched at any part of the system.
Electrical installation 5
In the entire system the mains infeed should be provid­ed by the building works on one component.
Note!
h
Please make sure that the VR 60 mixer module has a mains switch with which you can switch off the internal electronics as well as all con­nected actuators (pumps, mixers) for the pur­poses of tests and maintenance.
5Installation instructions Mixer module VR 60 0020020171_02
5 Electrical installation
230 V~
PE N L PE N L PE N L PE N Auf Zu PE N L AF 0
230 V~ on-site connection
230 V~
Fig. 5.1 Connecting the VR 60 mixer module
HKa HKa-P HKb-P AF
HKb
PE N Auf Zu
BUS
+ -
VFa
2 1
VFb
2 1
auroMATIC 620 VRC 630 Vaillant geoTHERM
heat pump VW.. .../2
VR 60
5.2 Connecting the heating circuit as a cylinder
charging circuit (not with Vaillant geoTHERM
VW.. .../2 heat pump.)
You can also configure the heating circuits of the mixer module VR 60 as storage tank charging circuits (addi­tional hot water circuits).
• Wire up the VR 60 mixer module as shown in Fig. 5.2.
230 V~
230 V~
PE N L PE N L PE N LPE N Auf Zu PE N L AF 0
Fig. 5.2 Connection of a heating circuit as a cylinder charging
circuit
HKa HKa-P HKb-P AF
1
PE N Auf Zu
2
3
HKb
BUS + -
VFa 2 1
VFb 2 1
Key
1 Cylinder charging pump 2 Circulation pump 3 Cylinder sensor
6
Installation instructions Mixer module VR 60 0020020171_026
Electrical installation 5
Start-up 6
Technical data 7
5.3 Setting the Bus address
Communication within the system takes place via an eBus. To ensure flawless communication between all the components it is necessary to allocate a unique address to the individual mixer circuit. To do this set the value 4, 6, 8, 10, 12 or 14 on the address switch (Fig. 5.3 (3)) de­pending upon whether the VR 60 mixer module has al­ready been integrated in the system. Addresses 0 to 3 are used by the system circuits in the auroMATIC 620 and VRC 630 controllers or the Vaillant
geoTHERM VW.. .../2 heat pump and are not therefore
available for addressing.
Assignment in the auroMATIC 620/
Addresses to be set
4 HK 4 HK 5 6 HK 6 HK 7 8 HK 8 HK 9 10 HK 10 HK 11 12 HK 12 HK 13 14 HK 14 HK 15
Table 5.1 Bus addresses to be set
VRC 630
Heating circuit a Heating circuit b
3
6 Start-up
Starting up the VR 60 mixer module is carried out in conjunction with starting up the auroMATIC 620 or
VRC 630 controller or the Vaillant geoTHERM VW.. .../2
heat pump. To do this, proceed in accordance with the instructions in the manual for the auroMATIC 620 or VRC 630 controller or the Vaillant
geoTHERM VW.. .../2 heat pump.
7 Technical data
Unit VR 60
Operating voltage Power consumption Contact load of the output relays (max.) Maximum total current
Maximum permissible ambient temperature °C 40
Operating voltage sensor V 5 Minimum cross-section of the sensor cables,
eBUS cables Minimum cross-section of power cable (rigid cable, NYM) Dimensions of wall mounting base Height Width Depth Level of protection Protection rating for regulator
Table 7.1 Technical data
V VA A A
mm2 mm
mm mm mm
230 2 2 4
0.75
2
1.5
174 272 52 IP 20 II
VFb
AF
2 1
AF 0
Fig. 5.3 Setting the bus address
After connecting the electrical installation:
• Fix all cables with the accompanying cable clamps (Fig. 4.2 (2)).
• Insert the casing cover back into the hinges and hinge the casing cover back up into position.
• Screw the casing cover in position in accordance with Fig. 4.1.
7Installation instructions Mixer module VR 60 0020020171_02
8 Warranty and customer service
8 Warranty and customer service
8.1 Vaillant warranty
We only grant a Vaillant manufacturer's warranty if a suitably qualified engineer has installed the system in accordance with Vaillant instructions. The system owner will be granted a warranty in accordance with the Vaillant terms and conditions. All requests for work dur­ing the guarantee period must be made to Vaillant Service Solutions (0870 6060 777).
8.2 Vaillant service
To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement. Please contact Vaillant Service Solutions (0870 6060 777) for further details.
Installation instructions Mixer module VR 60 0020020171_028
0020020171_02 GB 052009 - Subject to alterations