Vaillant geoTHERM exclusive Operating Manual

Page 1
For the owner
Operating manual
geoTHERM exclusive
Heat pump with integrated domestic hot water cylinder and additional cooling function
VWS
GB
Page 2
Contents
Contents
General information ..................................................... 3
Data badge .............................................................................. 3
1 Notes on this manual ....................................... 3
1.2 Document storage .................................................... 3
1.3 Symbols used ............................................................. 4
1.4 Applicability of the manual ..................................... 4
2 Safety instructions .......................................... 4
2.1 Coolant ......................................................................... 4
2.2 Prohibition on alterations ....................................... 5
3 Information on installation and operation ..... 5
3.1 Intended use ............................................................... 5
3.2 Requirements of the installation site .................. 6
3.3 Cleaning and care .................................................... 6
3.4 Checking the operating condition of the heat
pump ............................................................................. 6
3.4.1 Filling pressure of the heating installation ......... 6
3.4.2 Filling level and filling pressure of the brine
circuit ........................................................................... 6
3.4.3 Accumulation of condensate (condensation
water) ........................................................................... 7
3.5 Energy saving tips .................................................... 7
3.5.1 General energy saving tips ..................................... 7
3.5.2 Economising by the correct use of the control
system .......................................................................... 7
3.6 Recycling and disposal ............................................ 8
3.6.1 Appliance ..................................................................... 8
3.6.2 Packaging .................................................................... 8
3.6.3 Coolant ......................................................................... 8
5.10 Troubleshooting and Diagnosis ............................. 25
5.10.1 Error messages on the Controller ........................ 25
5.10.2 Activating emergency mode .................................. 26
5.10.3 Errors/malfunctions that you can resolve ......... 26
5.10.4 Warnings ...................................................................... 26
5.10.5 Temporary malfunctions ......................................... 26
5.10.6 Fault-induced shutdown .......................................... 27
6 Warranty and customer service ..................... 28
6.1 Vaillant warranty....................................................... 28
6.2 Vaillant Service .......................................................... 28
7 Appendix ............................................................ 29
7.1 Technical data ............................................................ 29
7.2 Identification plate .................................................... 31
4 Equipment and functional description ........... 9
4.1 Principle of operation .............................................. 9
4.2 Mode of operation of the coolant circuit ............ 9
4.3 Automatic auxiliary functions ................................ 10
4.4 Design of the geoTHERM exclusive heatpump 11
5 Operation ........................................................... 13
5.1 Familiarising yourself with and operating the
controller ..................................................................... 13
5.1.1 Calling up the screens ............................................. 13
5.2 Setting menus and parameters ............................. 14
5.3 Controller description .............................................. 14
5.3.1 Possible system circuits .......................................... 14
5.3.2 Energy balance control ........................................... 15
5.3.3 Buffer cylinder charging principle ........................ 15
5.3.4 Resetting to factory settings ................................. 15
5.3.5 Control structure ...................................................... 15
5.3.6 Adjusting the energy saving functions ................ 15
5.4 Flow diagram .............................................................. 16
5.5 User level displays .................................................... 17
5.6 Special functions ....................................................... 23
5.7 Starting up the heat pump ..................................... 25
5.8 Shutting down the heat pump ............................... 25
5.9 Inspection .................................................................... 25
Page 3
General information
Notes on this manual 1
General information
The Vaillant geoTHERM exclusive heat pumps in this manual are referred to in general as heat pumps and are available in the following models:
Type name Article number
VWS 63/2 230V 0010007274 VWS 83/2 230V 0010007275 VWS 103/2 230V 0010007276
Table 0.1 Type designations and article numbers
The heat pumps state-of-the-art appliances which have been constructed in accordance with recognised safety regulations.
Conformity with the applicable standards has been demonstrated.
'DACH' seal of approval
VDE seal and Tested Safety
1 Notes on this manual
The following information is intended to help you throughout the entire documentation. Further docu­ments apply in combination with this operating manual.
We accept no liability for any damage caused by fail­ure to observe these instructions.
Other applicable documents For the owner of the system:
Guarantee card No. 802922
For the heating engineer:
Installation instructions geoTHERM exclusive No. 0020051614
Other applicable documents are all manuals that de­scribe the operation of the heat pump, and the manuals supplied with the accessories used.
1.2 Document storage
Store this operating manual and all related documents in such a way that they are available whenever required. You can store the documents inside the pillar cover. If you move out or sell the appliance, pass on the docu­ments to the buyer.
With the CE mark, we confirm as equipment manufac­turers that the appliances in the geoTHERM exclusive range satisfy the requirements of the Directive on Elec­tromagnetic Compatibility (Council Directive 89/336/ EEC). The appliances meet the basic requirements of the Low Voltage Directive (Council Directive 73/23/ EEC). Furthermore, the appliances satisfy the requirements of EN 14511 (Heat pumps with electrically-driven compres­sors, heating, specifications for appliances for space heating and for warming drinking water) as well as EN 378 (safety and environmentally related specifications for refrigerating systems and heat pumps).
Data badge
An identification plate is attached to the baseplate on the inside of the geoTHERM exclusive heat pump. The type designation is located at the top of the front clad­ding (see also Fig. 4.3, Item 1). In Chapter 7.2 of the Ap­pendix there is a picture of an identification plate for the benefit of technically-interested customers, and a table explaining the symbols shown on it.
Fig. 1.1 Removing the pillar cover
3Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 4
1 Notes on this manual 2 Safety instructions
1.3 Symbols used
The following hazard classification symbols are used for information, activities and energy saving tips in this op­erating manual.
Danger!
Immediate risk of serious injury or death
d
Danger!
Danger of burning and scalding!
H
Caution!
Potentially dangerous situation for the
a
product and environment.
Note!
Useful information and instructions.
h
This symbol points you to energy saving tips. You can put this setting into effect by means of the heat pump control system, among other things.
• Symbol for a necessary task
1.4 Applicability of the manual
This operating manual applies exclusively to units with the following article numbers: 0010007274 0010007275 0010007276 The part number of your unit can be obtained from the identification plate.
2 Safety instructions
Observe the following safety instructions and regula­tions when operating the heat pump:
• Take advantage of the extensive instruction in the op­eration of the heat pump provided by your specialist technician.
• Carefully read through this operating manual.
• Only carry out activities that are described in this op­erating manual.
Danger!
Risk of burning as a result of contact
H
2.1 Coolant
The heat pump is delivered with an operational filling of R 407 C coolant. This is a chlorine-free coolant which does not affect the Earth's ozone layer. R 407 C is nei­ther a fire hazard nor an explosion risk.
a
with heat pump components! High temperatures can appear on heat pump components. Do not touch any uninsulated pipes on the heat pump. Do not remove any of the cladding sec­tions (apart from the pillar cover, see Chap. 1.2).
Caution!
This appliance contains R 407 C coolant. The coolant must not be allowed to es­cape into the atmosphere. R 407 C is a fluorinated greenhouse gas covered by the Kyoto Protocol, with a GWP of 1653 (GWP = Global Warming Potential). Before the appliance is disposed of, the coolant it contains must be completely drained into a suitable vessel so that it can then be recycled or disposed of in accordance with the regulations.
d
h
Danger!
Risk of injury from freezing as a result of contact with the R 407 C coolant! Escaping coolant can cause freezing if the exit point is touched: Do not inhale gases or vapours emanat­ing from leaks in the coolant circuit. Avoid contact with the skin and eyes.
Note!
R 407 C presents no danger in normal use and under normal conditions. With improper use, however, it can cause inju­ry and damage.
Operating Manual geoTHERM exclusive VWS 0020071929_004
Page 5
Safety instructions 2
Information on the installation and operation 3
2.2 Prohibition on alterations
Danger!Inappropriate alterations can
cause injuries!
d
The prohibition applies to: — geoTHERM exclusive heat pumps, — the Vicinity of geoTHERM exclusive heat pumps, — the Supply lines for water and power. For alterations to the heat pump or its peripherals, you must call on a qualified engineer.
• Do not damage or remove seals or locking devices on components. Only suitably qualified heating engineer or our customer service may remove sealed compo­nents.
Under no circumstances should you at­tempt to make changes or alterations to the heat pump or other parts of the heating and hot water system yourself.
3 Information on installation and
operation
Vaillant geoTHERM exclusive heat pumps are built using state-of-the-art technology and according to standard safety regulations and must be installed by a qualified expert technician taking the applicable specifications, regulations and guidelines into account.
Danger!
Risk to life as a consequence of using
d
3.1 Intended use
Vaillant heat pumps are built using state-of-the-art tech­nology and according to standard safety rules and regu­lations. Nevertheless, there is still a risk of injury or death to the user or others or of damage to the device and other property in the event of im-proper use or use for which it is not intended. This unit is not intended for use by persons (including children) having limited physical, sensory or mental ca­pacities or who have inadequate experience and/or knowledge, unless supervised by a person responsible for their safety or who has been given instructions from them as to how to operate the unit. Children must be supervised to ensure that they do not play with the unit. The units are intended as heaters for closed hot-water central heating installations and for hot water genera­tion. Any other use or extended use is considered to be improper. The manufacturer or supplier is not liable for any resulting damage. The user alone bears the risk. It is also considered as intended use to observe: — the operating and installation instructions — all other applicable documents — adherence to the inspection and care conditions.
unqualified personnel! Installation, inspection and repair may only be carried out by a qualified engi­neer. In particular, working on the elec­trical components and on the coolant circuit requires an appropriate qualifica­tion.
5Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 6
3 Information on the installation and operation
Danger!
Risk to life as a consequence of improper
d
3.2 Requirements of the installation site
The installation site must be dimensioned such that the heat pump can be properly installed and maintained.
• Ask your heating engineer which currently applicable national building regulations must be observed.
The installation site must be dry and generally frost­proof.
3.3 Cleaning and care
Do not use any scouring or cleaning agents that could damage the cladding.
h
3.4 Checking the operating condition of the heat
In contrast to heaters that operate using fossil fuels, no complex maintenance work is necessary for the Vaillant geoTHERM exclusive heat pump.
h
3.4.1 Filling pressure of the heating installation
The filling pressure of the heating installation should be checked at regular intervals. The filling pressure of the heating installation can be checked from the reading on the heat pump controller (see sect. 5.5). It should be be­tween 1 and 2 bar. If the water pressure falls below 0.5 bar, the heat pump will be shut down automatically and an error message will be displayed.
use of the installation. There is a risk of death or serious injury to the user or third parties or of damage to the device and other property in the event of improper use or use for which it is not intended.
Note!
Clean the exterior of your heat pump with a damp cloth and a little soap.
pump
Note!
Have your installation checked regularly by an expert technician company to en­sure efficient operation of your heat pump.
Caution!
Risk of damage from water escaping
a
h
3.4.2 Filling level and filling pressure of the brine
Check the brine level or pressure in the brine circuit at regular intervals. The filling pressure of the brine circuit ("Pressure Heat Source"“) can be checked from the reading on the heat pump controller (see sect. 5.5). It should be between 1 and 2 bar. If the brine pressure falls below 0.2 bar, the heat pump will be shut down auto­matically and an error message will be displayed.
a
a
If the filling level of the brine has fallen so far that it is no longer visible in the expansion tank, you must have the brine refilled.
from leaks in the system. Close the cold water stop valve in the event of leaks in the hot water pipework. In the event of leaks in the heating in­stallation switch off the heat pump to avoid any further leaking. Have the leaks repaired by an expert technician.
Note!
The cold water stop valve is not part of the heat pump scope of supply. It is fit­ted on site by your heating engineer. He will explain the location and handling of the component to you.
circuit
Caution!
Risk of damage from brine escaping from leaks in the system. In the event of leaks in the brine circuit switch off the heat pump to avoid any further leaking. Have the leaks repaired by an expert technician.
Caution!
The brine circuit must be filled with the correct quantity of fluid; otherwise the system can be damaged.
Operating Manual geoTHERM exclusive VWS 0020071929_006
Page 7
Information on the installation and operation 3
Fig. 3.1 Filling level of the brine expansion tank
It is normal for the filling level of the brine to fall a little in the first month after the start-up of the system. The filling level can also vary depending on the temperature of the heat source. However it should never sink so far that it is no longer visible in the expansion tank.
Caution!
Danger of damage
a
3.4.3 Accumulation of condensate (condensation
The evaporator, the brine pumps and the pipes in the heat source circuit, as well as some components in the coolant circuit, are insulated in the interior of the heat pump, so that no condensate can accumulate. If a small amount of condensate does form, it falls into the con­densate pan. The condensate pan is located on the in­side, in the lower part of the heat pump. As a result of the heat generated inside the heat pump, the conden­sate in the condensate pan evaporates. Small amounts of the accumulating condensate can be drained off under the heat pump. In small amounts, accumulating condensate should not be seen as a fault in the heat pump.
The brine circuit of your heat pump sys­tem must only be filled by authorised technical personnel. Check the filling level of the brine circuit at regular intervals and inform your ex­pert technician company if the filling level in the brine expansion tank is too low.
water)
3.5 Energy saving tips
Below you will find important tips to help you operate your heat pump system in an energy and cost-saving manner.
3.5.1 General energy saving tips
You can even save energy by your general behaviour: — Ventilate correctly: Do not leave windows or French windows tilted open,
but rather open the windows wide 3 or 4 times a day for 15 minutes and turn down the thermostatic valves or room thermostats while ventilating.
— Do not block the radiators to ensure that heated air
can circulate in the room. — Use a ventilation system with heat recovery. The optimum exchange of air in the building is always
guaranteed by the use of a ventilation system with
heat recovery (windows no longer need to be opened
for ventilation purposes). If necessary, the air flow can
be matched to your individual requirements with the
ventilation unit's remote control. — Check that windows and doors are airtight: Keep shut-
ters and blinds closed at night, so that as little heat as
possible is lost. — If a VR 90 remote control unit is installed as an acces-
sory, do not obstruct it with furniture, etc., so that it
can measure the circulating room air unhindered. — Think when using water, for example, take a shower
instead of a bath, promptly renew the seals on drip-
ping taps.
3.5.2 Economising by the correct use of the
control system
Further economies can be made by the correct use of the control system on your heat pump. The heat pump control system helps you to make sav­ings by: — Correct selection of the heating flow temperature: Your heat pump controls the heating flow tempera-
ture depending on the room temperature you have
set. Therefore select a room temperature that is just
sufficient for your comfort, for example 20 °C. Every
degree over and above that means an increase in en-
ergy consumption of around 6 % per annum.
7Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 8
3 Information on the installation and operation
— For floor heating use heating curves of < 0.4. For radi-
ator heating, we recommend that they are laid out to manage with a maximum flow temperature of 50 °C at the lowest outside temperature; this corresponds to
heating curves of < 0.7. — An appropriate setting of the hot water temperature: Only heat hot water as much as is required for con-
sumption. Any further heating results in unnecessary
power consumption, and hot water temperatures of
more than 60 °C also lead to increased lime scale pro-
duction. We recommend that hot water generation be
achieved without the electric auxiliary heating; by this
method, the maximum hot water temperature is de-
termined by the high pressure cut-out in the heat
pump cooling circuit. This cut-out corresponds to a
maximum hot water temperature of approx. 58 °C. — Setting of individually suited heating times. — Select the correct operating mode: For the times that you are asleep or away, we recom-
mend that you switch the heating to set-back mode. — Heat uniformly: By means of a meaningfully constructed heating pro-
gramme, you can arrange for all the rooms in your
house to be uniformly heated in accordance with your
pattern of use. — Set the thermostatic valves: You can adjust the room temperature to suit your in-
dividual requirements and ensure effective operation
of your heating installation using the thermostatic
valves in combination with a room temperature regu-
lator (weather compensator). — The operating times of the circulation pump can thus
be optimally matched to the actual need. — Consult a qualified engineer. He will adjust your heat-
ing installation to suit your personal requirements. — These and more energy saving tips are provided in
Chap. 5.5. Descriptions of the controller settings and
their energy-saving potential are provided here.
Caution!
Environmental hazard due to improper
a
3.6.1 Appliance
at the end of their useful life. As this heat pump is not covered by the law regarding the marketing, return and environmentally friendly dis­posal of electrical and electronic equipment (ElektroG in Germany), free disposal at a municipal collection point is not provided.
3.6.2 Packaging
Leave the disposal of the transport packaging to the qualified servicing company which installed the appli­ance.
3.6.3 Coolant
The Vaillant heat pump is filled with R 407 C coolant.
d
disposal! The disposal of coolant must only be by qualified specialists.
If your heat pump is identified with this sym­bol, it does not belong in your household waste at the end of its useful life. In this case, make sure that the Vaillant appliance and any accessories present are properly disposed of
Danger!
Risk of injury from freezing as a result of contact with the R 407 C coolant! Escaping coolant can cause freezing if the exit point is touched. Do not inhale gases or vapours emanat­ing from leaks in the coolant circuit. Avoid contact with the skin and eyes. The disposal of coolant must only be by qualified specialists.
3.6 Recycling and disposal
Most of the raw materials used to manufacture your heat pump and all its accessories and associated trans­port packaging can be recycled, and thus have no place in your household waste.
Note!
Please observe the applicable national
h
legal regulations. Make sure the old appliance and any ac­cessories are disposed of properly.
h
Note!
R 407 C presents no danger in normal use and under normal conditions. With improper use, however, it can cause inju­ry and damage.
Operating Manual geoTHERM exclusive VWS 0020071929_008
Page 9
Equipment and functional description 4
4 Equipment and functional
description
4.1 Principle of operation
Heat pump systems consist of separate circuits in which liquids or gases transport the heat from the heat source to the heating system. As these circuits operate with differing media (brine/water, coolant and heating water), they are coupled to one another by means of heat exchangers. In these heat exchangers the heat passes from a medium at a high temperature to a medi­um at a lower temperature.
The Vaillant geoTHERM exclusive heat pump uses geo­thermal energy as its heat source.
1/4 Electrical energy
3/4 Environmental energy 4/4 Heating energy
4.2 Mode of operation of the coolant circuit
Cold water
Heating
system
Auxiliary
Umschaltventil
Heizkreispumpe
3
Condenser
Expansion valve
Evaporator
4
Brine pump
Heat source
Fig. 4.2 Operating principle of the heat pump
heating
Diverter valve
2
Compressor
1
Mixer valve
Cooling heat exchanger
Coolant circuit
Heat source circuit
Hot water
Domestic hot water cylinder
Heating water circuit
Fig. 4.1 Using a geothermal heat source
The system consists of separate circuits which are cou­pled to one another by means of heat exchangers. These circuits are:
- The heat source circuit, by means of which the energy
from the heat source is transported to the coolant cir-
cuit.
- The coolant circuit, which releases its heat to the
heating water circuit by means of evaporation, com-
pression, liquefaction and expansion.
- The heating water circuit, which supplies the heating
and the hot water generator for the domestic hot
water cylinder.
The coolant circuit is connected by means of the evapo­rator (1) to the environmental heat source, from which it extracts thermal energy. At the same time, the physical state of the coolant changes; it evaporates. The coolant circuit is connected by means of the condenser (3) to the heating system, to which it releases the heat again. In so doing, the coolant becomes liquid again; it con­denses. As thermal energy can only pass from a body at a high­er temperature to a body at a lower temperature, the coolant in the evaporator must have a lower tempera­ture than the environmental heat source. On the other hand, the temperature of the coolant in the condenser must be higher than that of the heating water in order to be able to release the heat to it.
9Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 10
4 Equipment and functional description
These different temperatures are produced in the cool­ant circuit by means of a compressor (2) and an expan­sion valve (4), which are situated between the evapora­tor and the condenser. The coolant flows in vapour form from the evaporator into the compressor, where it is compressed. This causes the pressure and temperature of the coolant vapour to rise sharply. After this process it flows through the condenser, where it releases its heat to the heating water by condensation. It flows as a liquid to the expansion valve, where it expands signifi­cantly and in so doing loses much of its pressure and temperature. This temperature is now lower than that of the outside air which flows through the evaporator. The coolant can thus take up more heat in the evapora­tor, turning into vapour in the process and flowing to the compressor. The cycle starts again.
If required, the electric auxiliary heating can be switched in by means of the integrated controller.
To prevent the formation of condensate in the interior of the unit, the pipes of the heat source circuit and the coolant circuit are insulated. Should condensate appear, however, it is collected in a pan inside the unit and fed away underneath it. Drop formation under the unit is thus possible.
geoTHERM exclusive heat pumps by Vaillant are equipped with an auxiliary cooling function that ensures a comfortably cool living environment in the summer when outside temperatures are high. Vaillant heat pumps with a cooling function utilise the principle of "passive" cooling which means that the heat is removed from the rooms and absorbed by the soil via an under­floor heating system, for example. The heating water absorbs the heat from the rooms during this process and transfers it via the special switching technology on the inside of the heat pump to the colder brine which then transfers the heat to the soil.
4.3 Automatic auxiliary functions
Frost protection
Your controller is equipped with a frost protection func­tion. This function ensures that your heating installation is protected from frost in all operating modes. If the outside temperature falls below a value of +3 °C, a minimum temperature of 5 °C is automatically pro­grammed for each heating circuit.
Cylinder frost protection
This function starts automatically when the actual tem­perature of the cylinder falls below 10 °C. The cylinder is then heated to 15 °C. This function is also active in the "Off" and "Auto" operating modes, regardless of the timer programmes.
Checking the external sensors
The sensors required are determined by the basic hy­draulic circuit arrangement specified during commis­sioning. The heat pump constantly checks automatically that all sensors are installed and functioning.
Protection from loss of heating water
A pressure sensor recognises a potential loss of water and switches the heat pump off if the water pressure is below 0.5 bar gauge pressure. The pressure sensor switches the heat pump on again when the water pres­sure rises above 0.7 bar gauge pressure.
Pump seizing and valve seizing protection
To prevent the sticking of the heating, circulation and brine pump or of the hot water diverter valve UV1, the pumps and the valve, which have not been in operation for 24 hours, are switched on every day for approx. 20 sec.
Protection against loss of brine
An analogue pressure sensor monitors possible low brine pressure and switches the heat pump off if the brine pressure is ever less than 0.2 bar on the pressure gauge and error 91 is displayed on the error memory. The heat pump switches on again when the brine pres­sure rises above 0.4 bar gauge pressure. If the brine pressure drops below 0.6 bar on the pres­sure gauge for more than one minute a warning appears in menu
Floor protection circuits in all hydraulic systems without buffer cylinders (with hydraulic plan 6)
If the heating flow temperature in the underfloor heat­ing circuit measured by sensor VF2 continuously ex­ceeds a value of (max. HK temp. + compressor hystere­sis + 2 K, default setting: 52 °C) for more than 15 min­utes, the heat pump switches off with error message F.72 (see Chap. When the heating flow temperature falls below this value again and the error has been reset the heat pump switches back on. The maximum heating flow temperature can be changed via vrDIALOG with the "Maximum heating circuit tem­perature" parameter.
a
1.
Caution!
Danger of damage to the floor. Set the value for the floor protection cir­cuit ensuring that it is not high enough to damage the floor as a result of exces­sively high temperatures.
Operating Manual geoTHERM exclusive VWS 0020071929_0010
Page 11
Equipment and functional description 4
Freezing protection function
The outlet temperature of the heat source is constantly measured. If the heat source outlet temperature falls below a specific value, the compressor temporarily shuts off with the error message 20 or 21. If these er­rors occur three times in a row there is a fault-induced shutdown. For the geoTHERM VWS heat pumps you can set the value (Default setting -10 °C) for the freezing protection in the installation assistant A4.
Cooling
In cooling mode the heat pump performs a cooling func­tion. You can use the cooling function to set the number of consecutive days (0 - 99) on which you wish the cooling system to be in operation.
4.4 Design of the geoTHERM exclusive heat
pump
A domestic hot water cylinder with a capacity of 175 li­tres is integrated into the Vaillant geoTHERM exclusive heat pump. The heat pump is available in three versions, which differ mainly in their output.
Type name Heating output (kW)
Brine water heat pumps (S0/W35) VWS 63/2 230V 6.0 VWS 83/2 230V 8,1 VWS 103/2 230V 10.5
Table 4.1 Type summary
1
2
Fig. 4.3 Front view
Key to Fig. 4.3
1 Sticker with the heat pump type designation 2 Operating console
11Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 12
4 Equipment and functional description
1
9
8
7
2
6
5
Fig. 4.4 Rear view
Key to Fig. 4.4
1 Hot water connection, domestic hot water cylinder 2 Cold water connection, domestic hot water cylinder 3 Heat source to the heat pump 4 Heat source from the heat pump 5 Heating return 6 Heating flow 7 Handle trough 8 Handle trough/cable grommet, electrical connection 9 Ventilation, heating flow to domestic hot water cylinder
3
4
Operating Manual geoTHERM exclusive VWS 0020071929_0012
Page 13
5 Operation
5.1 Familiarising yourself with and operating the
controller
Operation 5
1
Basic data
Date Day of week
6
5
Fig. 5.1 Sample illustration no. 3Fig. 7.1 Overview of operation
Key
1 Menu name 2 Cursor indicating the selected parameter 3 Menu number 4 Dial
,
Set parameter (turn), Select parameter (press)
5 Dial ,
select menu (turn), activate special operating mode (press)
6 Information line (handling request shown in example)
Time
Set day
2
3
4
Typical operating sequence on the operator level
• Turn the dial until the menu required has been selected.
• Turn the dial until the pa­rameter to be modified has been selected.
All programming of the heat pump is carried out by means of the two dials ( The dial
is used to select the parameter (by pressing)
and ) on the controller.
and to alter the parameter (by turning). The dial used to select the menu (by turning) and to activate special functions (by pressing).
5.1.1 Calling up the screens
The menus are identified by a number at the top right of the display. You can access the next menu by turning
dial. The numbers make it easier to find individual
the menus during programming.
is
• Press the dial to mark the parameter to be modified. The parameter will be high­lighted on a dark background.
• Turn the dial to modify the parameter setting value.
• Press the dial to mark the setting value to be accepted.
• Repeat this sequence until all the settings have been made.
13Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 14
5 Operation
5.2 Setting menus and parameters
Setting to date Modified setting
Select menu:
Holiday programming for cpl. System
Period of time
1 >06.01.08 08.01.08
2 14.01.08 30.01.08 Room Temp. setpoint 12°C >Set start day
Basic data
6
Turn the dial: Select
menu e.g. from menu 6 to
7.
Select parameter:
7
Basic data
Date >21.04.08 Day of
week Time 09:35
>Set day
Basic data
7
Mo
7
Date >21.04.08 Day of
week Time 09:35
>Set day
Basic data
Date 21.04.08 Day of
week Time 09:35
>Set weekday
Mo
>Mon
Turn the dial: select the
parameter to be modified e.g. from line 1 day to line 2 weekday (in this example continue to turn 3 snap-in points).
Modify parameter weekday
7
from Monday to Tuesday:
Push the dial:
Select parameter:
Turn the dial:
Modify parameter,
Push the dial:
Accept modification.
Fig. 5.2 Setting menus and parameters
5.3 Controller description
The heating engineer will have set all the operating pa­rameters to preset values during commissioning, so that the heat pump can function optimally. However you can individually set and adapt the operating modes and functions afterwards.
Date 21.04.08 Day of
week Time 09:35
>Set weekday
Basic data
Date 21.04.08 Day of
week Time 09:35
>Set weekday
>Mon
7
>Tues
5.3.1 Possible system circuits
The controller can control the following system circuits: – a heating circuit, – an indirectly heated hot water storage tank, – a hot water circulation pump, – a buffer circuit.
In order to extend the system a buffer circuit can be used to connect up to six additional mixer circuit mod­ules VR 60 (accessories) each with two mixer circuits. The controller on the operating panel of the heat pump is used to programme the mixer circuits. In order to op­erate under comfortable conditions you can connect the remote control units VR 90 for the first eight heating circuits.
Operating Manual geoTHERM exclusive VWS 0020071929_0014
Page 15
Operation 5
5.3.2 Energy balance control
Energy balance control applies only to hydraulic sys­tems without buffer cylinders (e.g. hydraulic plan 6). For economical and fault-free operation of a heat pump, it is important to regiment the starting of the compres­sor. The start-up of the compressor is the point at which the highest loading occurs. With the help of the energy balance controller it is possible to minimise starts of the heat pump without compromising the comfort of a pleasant room atmosphere. As with other weather-controlled heating controllers the controller determines a supply set target temperature by capturing the outside temperature through a heating curve. The energy balance calculation is carried out based on this supply set target temperature and the supply real temperature the difference of which is measured per minute and added up:
1 Degree minute [°min] = 1 K Temperature difference in the Course of 1 Minute
The heat pump starts up at a defined heat deficit and only switches off again when the supplied heat is equal to the heat deficit. The larger the preset negative numerical value is, the longer the periods for which the compressor is kept run­ning or at standstill.
5.3.3 Buffer cylinder charging principle
The buffer cylinder is controlled depending on the sup­ply set target temperature. The heat pump heats when the temperature of the buffer cylinder head tempera­ture sensor VF1 is smaller than the set target tempera­ture. It continues to heat until the buffer cylinder floor temperature sensor RF1 has reached the set target tem­perature plus 2 K. In the connection to a hot water cylinder charging the buffer cylinder is also charged when the temperature of the head temperature sensor VF1 is less than 2 K higher than the set target temperature (premature reheating): VF1 < T VL set + 2 K.
• In the basic display on the graphic display press both dials at the same time for min. 5 sec.
After that you can select whether to reset only the timer programme or all values to the default settings.
5.3.5 Control structure
The Top level display is a Graphics display. It is the starting point for all the available displays. This display reappears automatically if you do not actuate any of the dials for a long time when setting values.
Controller operation is subdivided into four levels:
The Operator level is specified for the operator. In Sect. 5.4 all of the controller's displays are shown as a flow diagram. A detailed description of the displays is contained in Sect. 5.5.
The Code level (menu C1 - C9, D1 - D5, I1 - I5 and A1 - A9) is reserved for the engineer and protected by a code to protect it from unintentional modification. As the operator you can scroll through the menus of the code level and view the system-specific setting parame­ters however without changing the values. In the menus C1 to C9 the engineer sets system-specific parameters. The menus D1 to D5 enable the engineer to operate and test the heat pump in the diagnosis mode. In menus I1 to I5 you are given general information on the settings of the heat pump. Menus A1 to A9 take the engineer through the installa­tion menu to put the heat pump into operation.
The display and selection of Special function (e.g. the energy-saving function) is also possible for the operator. Instructions are given in Sect. 5.6 as to how to activate the special functions.
The fourth level contains functions for the optimisation of the system and can only be set by the engineer using
vrDIALOG 810/2.
5.3.4 Resetting to factory settings
Caution!
Inadvertent deletion of specific settings!
a
When you reset the control system to the default settings, specific system settings can be deleted and the system can sut down. The system does not suf­fer damage.
5.3.6 Adjusting the energy saving functions
Also described in Chap. 5.5 are heat pump settings that will enable a reduction in your energy costs. This is achieved by optimum setting of the heat pump's weath­er-controlled energy balance controller.
This symbol points you to these energy saving tips.
15Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 16
5 Operation
5.4 Flow diagram
Graphics display
Graphics display cooling*
Energy input display
Mo 21.04.08 Flow Temp. CH
System pressure 1,2bar Brine pressure CH : Comp only
Warning message Warning message
16:49
28ºC
1,4bar
Reset to default
settings
We 16.02.08 9:35
> 5 sec.
Factory setting Cancel
Time programme Everything
> Select
NO/YES NO/YES NO/YES
Installer Menu
We 16.02.08 9:35
Sparen aktiviert for > 12:00
> Select stop time
We 16.02.08 9:35
Party function enabled
We 16.02.08 9:35
One-time DHW tank loading enabled
1
Cooling settings *
We 16.02.08 9:35
Cooling function active for >3days
> Set duration
HK2 Parameters
HK2
Heating mode
Parame ter
>Auto
Betriebsart Heizen
Set value day
>Auto
Night set back temp.
Raumsolltemp.
>Select operation mode
Night set back temp.
Domestic hot water Parameters
Operation mode DHW > Auto
Max. DHW temp.
Min. DHW temp. Current DHW temp.
>Select operation mode
HK2 Time programme
HK2 Time programme
>Mo
HK2
1 00:00 24:00
Time programme
>Mo
2 : :
1 00:00 24:00
>Mo
3 : :
2 : :
1 00:00 24:00
3 : :
>Select day of the week
2 : : 3 : :
>Select day of the week
>Select day of the week
20 ºC
15 ºC
60 ºC
44 ºC
51 ºC
Fig. 5.3 Displays in the User level
2
20 ºC
15 ºC
4
5
2
5
5
Domestic hot water Time programme
>Mo 1 06:00 22:00 2 : : 3 : :
>Select day of the week
Circulation pump Time programme
>Mo 1 06:00 22:00 2 : : 3 : :
>Select day of the week
Holiday programming for cpl. System
Periods 1 >06.01.08 08.01.08 2 14.01.08 31.01.08 Room Temp. setpoint
>Set starting day
12 ºC
5
Basic data 7
Date 21.04.08 Day of week > Mo Time 09:35
5
6
> Set day of the week
Code layer 8
Code-Nummer: > 0 0 0 0
Standard code:
1 0 0 0 >Adjust numeric character
Code level only for
expert technicians
Operating Manual geoTHERM exclusive VWS 0020071929_0016
Page 17
5.5 User level displays
The individual displays on the operating panel are de­scribed and explained below.
Display shown Description
Graphics display (Top-level display)
You can read off the instantaneous state of the system from this dis­play. This is always shown if you have not actuated either of the dials for a long time while another display is showing.
Operation 5
Outside temperature (here 10 °C)
Source inlet temperature: Temperature sensor; in the example 9 °C
Under the arrow the output of the heat source (in the example 10 KW) is displayed. The extent of darkening of the arrow graphically shows the energy efficiency of the heat pump under the given operating conditions.
The output of the heat source must not be equated with the heating output. The heating output corresponds to approx. the output of the heat source + compressor output
When the compressor or the electric auxiliary heating is switched on, the arrow is shown filled.
>>> Left and right flash when the compressor is switched on and energy is consequently being taken from the environment and fed to the heat­ing system.
>>> Right flashes when energy is being fed to the heating system (e.g. only from the electric auxil­iary heating).
The heat pump is in the CH mode. Moreover, the heating flow temperature is displayed (in the ex­ample 30 °C).
The symbol indicates that the domestic hot water cylinder is being heated or that the heat pump is in the ready state. The temperature in the domestic hot water cylinder is also dis­played.
The symbol indicates that the heat pump is in cooling operation. Under the symbol the actual heating flow temperature is displayed (in the example 20 °C).
Table 5.1 Settable parameters in the operator level
17Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 18
5 Operation
Display shown Description
Energy input display
Shows the energy extracted from the environment for each of the 12 months of the current year (black bar). White-filled bars represent the future months of the year; the height of the bar corresponds to the yield for the month in the previous year (comparison possible). On commissioning, the height of the bars is zero for all months, as no in­formation is available yet. The scaling (in the example, 4000 kWh) adapts automatically to the month's highest value. Top right the total of the environmental yield since commissioning is displayed (in the example: 13628 kWh).
Mon. 21.04.08 16:49 1 Current flow temp. 28°C CH pressure 1.2bar Brine pressure 1.4bar
Heating only comp.
Warning message Warning message
Day, date, time as well as flow temperature, heating system pressure and heat source pressure are displayed.
Current flow temp: Current flow temperature in the unit. Heating system pressure: Pressure sensor heating circuit. Pressure heat source: Pressure of the heat source (pressure sensor,
heat source circuit, brine pressure) Heating only comp.: this status message provides information on the current operating status. The following are possible: CH: Comp. only. CH: Comp+Aux CH: Aux only CH: Comp&aux off DHW: Comp&aux off DHW: Comp only DHW: aux only Peak Rate: WW Peak Rate: Stand-by Acceleration mode Frost prot. Heating Frost prot. Cylind. Legionella protect. Automatic pump spin Floor drying Venting mode Fault shutdown: heating Error shutdown: heating Fault shutdown: DHW Error shutdown: DHW Malfunction Blocking error Operation interlock CH Comp overrun WW Comp overrun Cooling & WW CH return too high
Table 5.1 Adjustable parameters at the operator level (contd.)
Under critical operating conditions a warning message is displayed in both lower display lines. These lines are empty when the operating conditions are normal.
Operating Manual geoTHERM exclusive VWS 0020071929_0018
Page 19
Operation 5
Display shown Description Factory setting
HK2 Parameters
Operating mode heating
>Auto Set value day 22°C Night set back temp. 15°C >Select operating mode
The Room set target temperature is the tempera-
2
ture to which the heating should be regulated in the operating mode "Heat" or during the time slots.
Note: Select a room temperature that is just high enough to ensure your personal well-being (e.g. 20 °C). Each degree over and above the set value means an increase in energy consumption of around 6 % per annum.
The Set-back temperature is the temperature to which the heating is regulated during the set-back period. An individual set-back temperature can be set for each heating circuit.
The set operating mode determines under which conditions the assigned heating circuit or hot water circuit should be regulated.
Room set target temp.: 20°C
Set-back temp.: 15°C
The following operating modes are available for heating circuits: Auto: The operation of the heating circuits alter­nates between the Heating and Energy Saving oper­ating modes in accordance with a settable timer pro­gramme. Eco: The operation of the heating circuits alternates between the Heating and Off operating modes in ac­cordance with a settable timer programme. The heating circuit is switched off during the set-back period provided the frost protection function (which depends on the outside temperature) is not activated. Heating: The heating circuit operates at the room set target temperature regardless of any settable timer programme. Energy sav: The heating circuit operates at the set­back temperature regardless of any settable timer programme. Off: The heating circuit is off, provided that the frost protection function (depending on the external tem­perature) is not activated.
Note:
Additional heating circuits are displayed, depending on the system configuration.
Table 5.1 Adjustable parameters at the operator level (contd.)
19Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 20
5 Operation
Display shown Description Factory setting
DHW loading Parameters
Operating mode WW Auto Auto
Max. DHW temp. 60°C 60°C
Min. DHW temp. 44°C 44°C Cylinder temp. REAL 51°C 51°C >Select set target temperature
For connected domestic hot water cylinders and the
4
circulation circuit the operating modes Auto, On and Off are possible.
The maximum WW temperature determines the temperature to which the domestic hot water cylin­der should be heated. The minimum WW temperature determines the limit below which the domestic hot water cylinder is heated. Note: The maximum WW temperature is only dis­played when the auxiliary hot water heating is ena­bled. Without electric auxiliary heating, the WW tempera­ture is limited by the pressure sensor control shut­off in the cooling circuit and cannot be adjusted! Cylinder temp. REAL: Current temperature in the domestic hot water cylinder.
We recommend that hot water generation be achieved without the electric auxiliary heating. by this method, the maximum WW temperature is de­termined by the high pressure cut-out in the heat pump cooling circuit. This cut-out corresponds to a maximum hot water temperature of 58 °C. In order to keep the heat pump starts to an absolute mini­mum as low a min. hot water temperature as possi­ble should be selected.
Min. hot water temp. 44 °C
You can set the heating times for each heating cir-
HK2 Time programme >Mon
1 00:00 24:00 2: : 3: :
>Select weekday/Block
5
cuit in the HK2-Timer programme menu. Up to three heating times can be programmed per day or block. The control system operates according to the heating curve and the room setpoint tempera­ture.
The set back times can be dispensed with, depending on the tariff agreement with power company (VNB) or the construction of the house. Power companies offer their own discounted tariffs for heat pumps. It can make sense on economic grounds to make use of the more favourable off­peak power. In low-energy houses (in Germany standard as from 1st February 2002 energy conservation regulation) the room temperature reduction can be dispensed with owing to low heat losses. The desired set-back temperature must be set in menu 2.
Table 5.1 Adjustable parameters at the operator level (contd.)
Mo. – Su. 0:00 – 24:00 hours
Operating Manual geoTHERM exclusive VWS 0020071929_0020
Page 21
Operation 5
Display shown Description Factory setting
DHW loading Time programme
>Mon
1 06:00 22:00 2: : 3: :
>Select weekday/Block
You can set the times at which the domestic hot
5
water cylinder is heated in the "WW Timer Pro­gramme" menu.
Up to three times can be programmed per day or block.
The hot water generation should only be active at times when really hot water is to be run. Please set this timer programme to your minimum require­ments. As an example, for working people a window from
6.00 – 8.00 hrs. and a second window from 17.00 –
23.00 hrs.can minimise the energy consumption due to hot water generation.
Mon – Fri 6:00 – 22:00 hrs.
Sat
7:30 – 23:30
Su. 7:30 – 22:00
You can set the times at which the circulation pump
Circulation pump Time programme
>Mon
1 06:00 22:00 2: : 3: :
>Select weekday/block
5
is to be operational in the "Circulation Pump Timer Programme" menu.
Up to three times can be programmed per day or block. If the hot water operating mode (see menu set to "ON", the circulation pump runs continuously.
The timer programme Circulation Pump should cor­respond to the timer programme Hot Water, if necessary the time slots could be selected even more restrictively. If the desired hot water temperature is obtained quickly enough without switching on the circulation pump, the circulation pump can likewise be deacti­vated. In addition, you can briefly activate the circulation pump by means of electronic pushbutton switches mounted in the immediate vicinity of the taps and connected to the heat pump (the same idea as stair­well lighting). The operating times of the circulation pump can thus be optimally matched to the actual need. Consult your expert technician about doing this.
Table 5.1 Adjustable parameters at the operator level (contd.)
3) is
Mon – Fri 6:00 – 22:00 hrs.
Sat 7:30 – 23:30
Su. 7:30 – 22:00
21Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 22
5 Operation
Display shown Description Factory setting
Holiday programming for cpl. System
Period of time
1 >06.01.08 08.01.08 2 14.01.08 30.01.08
Room Temp. setpoint 12°C >Set start day
For the controller and its connected system compo-
6
nents it is possible to programme two holiday peri­ods with the introduction of the date. Moreover, the desired target room temperature can be set for holi­days, i.e. regardless of the preset timer programme. After the holiday time has elapsed, the controller au­tomatically goes back to the previously selected op­erating mode. The holiday program can be activated only in auto and eco operating mode. Connected cylinder charging circuits or circulation pump circuits are automatically switched to OFF op­erating mode during the holiday timer programme.
Connected cylinder charging circuits or circulation pump circuits are automatically switched to OFF op­erating mode during the holiday timer programme. Prolonged periods of absence can be set in the dis­play "Programme holidays". The target temperature during this period should be selected to be as low as possible. During this period hot water generation is not in op­eration.
Period 1:
01.01.2003 –
01.01.2003
Period 2:
01.01.2003 –
01.01.2003
Room Temp. setpoint 15 °C
You can set the current Date, the Day of the week
Basic data
Date 21.04.08 Day of
week Time 09:35
>Settable values
Code layer
Code number:
Mo
>0 0 0 0
7
and the current Time, if DCF radio clock reception is not possible, in the “Basic Data”menu. These settings apply to all connected system compo­nents.
To access the Code level (Installer level), the appro-
8
priate code must be entered. To view setting parameters without entering the code, you must press the dial view all parameters of the code level by turning the dial
but not change them. As operator, without en-
tering the code, you can view all menus in the code
>Set figures
level however not modify them.
Caution! Do not try to access the code level by mak­ing arbitrary entries in the code level. Unintentional modification of the system-specific parameters can cause malfunctions or damage to the heat pump.
Table 5.1 Adjustable parameters at the operator level (contd.)
once. You can then
Operating Manual geoTHERM exclusive VWS 0020071929_0022
Page 23
5.6 Special functions
Special functions can be selected only from the basic display. To do so press the left-hand dial To change the parameter, you must turn the
.
dial. The
following special functions can be selected:
Operation 5
• Energy saving function: Press
• Party function: Press
dial twice.
• One-time charging: Press
• Cooling operation: Press
dial once.
dial 3 x.
dial 4 x
To activate one of the functions, you merely have to se­lect it. In the energy saving function it is additionally necessary to enter the time until which the energy sav­ing function (regulation to set-back temperature) is to apply.
The basic display appears either after the function has elapsed (reaching the time) or by pressing the
dial
again.
Display shown Description
We 16.02.08 9:35
Saving function: With the saving function you can set back the heating times for a set-
Energy saving enabled
table period.
Enter the time for the end of the saving function in the format hh:mm (hour:minute).
>Select end time
We 16.02.08 9:35
Party function enabled
Party function: With the party function you can continue the heating and hot water times beyond the next switch-off time up to the next heating start. The party function can only be used for the heating circuits or hot water circuits for which the operating mode "Auto" or "ECO" is set.
We 16.02.08 9:35
one-time DHW tank loading enabled
Table 5.2 Special functions
One-time charging: This function allows you to charge the hot water cylinder once, re­gardless of the current time program.
23Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 24
5 Operation
Display shown Description
We 16.02.08 9:35
Cooling operation:
Cooling duration: OFF/1 to 99 days.
Cooling function active for > 3 Days
Table 5.2 Special functions (ctnd.)
If the cooling operation is active, – the symbol of an ice crystal appears in the graphic display.
• Reset to default setting: Keep dial and dial pressed for longer than 5 seconds. After that you can select whether to reset only the timer programme or all values to the default settings.
Display shown Description
We 21.04.08 9:35
Factory setting Cancel NO/YES Time programme NO/YES Everything NO/YES >Settable values
The default settings are re-established.
Caution! Ensure that a qualified technician performs the default set­ting reset. The system-specific settings are reset. The system can be shut down. The system does not suffer damage.
Press both dials for at least 5 seconds to request the menu default setting.
Table 5.3 Re-establishing the default setting
Operating Manual geoTHERM exclusive VWS 0020071929_0024
Page 25
Operation 5
5.7 Starting up the heat pump
The start-up of your heat pump was carried out after in­stallation by your expert technician company. A repeated start-up will not even be necessary in the event that your heat pump disconnects from the mains unexpectedly, for example as a result of a voltage drop (power cut, circuit breaker defective, circuit breaker de­activated). Your geoTHERM heat pump has an automat­ic reset function, i.e. the heat pump reverts automatical­ly to its starting condition, provided no fault is present in the heat pump itself. Find out what to do in the event of a fault in Chap. 5.10.
5.8 Shutting down the heat pump
The heat pump can only be shut down via the control panel by deactivating the heating and hot water genera­tion functions in the respective menus (see Chap. 5.4 Displays at user level).
Note!
Should it be necessary to remove all
h
5.9 Inspection
An annual inspection/maintenance of the unit by a spe­cialist is a prerequisite for continuing operational safety, reliability and a long working life.
d
Only genuine Vaillant spare parts may be used for in­spections, maintenance and repair work to ensure the perfect long-term working order of all functions of your Vaillant appliance and to prevent the approved series condition from being changed. Any spare parts which might be required are listed in the relevant current spare parts catalogues. Information can be obtained from Vaillant Customer Service Centres.
electric power from the heat pump in­stallation, then switch off the circuit breaker on your heating system.
Danger!
Inspections / Maintenance work not car­ried out can result in damage to proper­ty and personal injury. Have inspections maintenance and re­pairs carried out only by a recognised expert technician company.
5.10 Troubleshooting and Diagnosis
5.10.1 Error messages on the Controller
Error messages appear roughly 20 seconds after the error has occurred in the display and are written in the error memory of the controller if the error persists for roughly 3 minutes. The engineer can then call up the error message from the memory at a later date.
Error History
Fault number >1 Fault code 41
16.02.08 07:18 Error CH circuit Sensor T3 heat source
Fig. 5.4 Error message in the error memory Menu I1
The geoTHERM control system has various malfunction types: – Malfunction of Komponents which are connected via
eBUS.
Temporary Shutdown
The heat pump remains in operation. The error is dis­played and disappears independently when the cause of the fault is removed.
Fault-induced Shutdown
The heat pump is shut down. It can only be restarted after the cause of the fault has been removed by the expert technician and the error reset.
– Moreover, Other Errors/Malfunctions can occur on
the unit or system.
Caution!
Heat pump malfunction.
a
h
Immediately notify your expert techni­cian if error messages appear on the dis­play on the operating panel which are not listed in tables 5.4 to 5.7. Do not attempt to remove the source of the malfunction yourself.
Note!
Not all of the following listed malfunc­tions have to be dealt with by an expert technician. If you are unsure whether you can reme­dy the fault yourself or not or if the error occurs repeatedly contact your ex­pert technician or Vaillant customer service.
I1
25Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 26
5 Operation
5.10.2 Activating emergency mode
Depending on the type of malfunction the expert techni­cian can set the heat pump to continue operation in emergency mode (via an integrated electric auxiliary heating) until the cause of the error is remedied, and ei­ther for heating operation (display "heating priority"), for hot water operation (display "hot water priority") or for both (display "heating priority/hot water priority"), see the following tables, column "emergency operation".
5.10.3 Errors/malfunctions that you can resolve
Malfunction sign Possible cause Solution
Noise in the heating circuit.
Table 5.4 Other Malfunctions
Dirt in the heating circuit. Faulty pump.
Air in the heating circuit.
Bleeding heating circuit.
5.10.4 Warnings
The following warning messages do not cause a mal­function in the operation of the heat pump. The heat pump is not shut down. Take note of the error code and text and discuss this during the next inspection with the expert technician.
Fault code Error text/description
26 Overheating on compressor pressure side 36 Low brine pressure
Table 5.5 Warning messages, no shutdown
5.10.5 Temporary malfunctions
The heat pump is shut down temporarily and starts up again independently when the cause of the fault is re­moved. Depending on the error the heat pump switches back on automatically after 5 or 60 minutes. Take note of the error code and text and discuss this during the next inspection with the expert technician.
Fault code Error text/description
20 Frost protection heat source monitoring source
outlet
Temperature difference of the heat source > set value "permitted temp. difference" This error message is deactivated as standard and can only be activated via vrDIALOG parameter "permitted temp. difference" (20 K difference means deactivated).
22 Frost protection heat source over. source outlet
Source outlet temperature too low (<parameter freezing protection in menu A4)
27 Coolant pressure too high
The integrated high pressure switch tripped at 30 bar (g).
The heat pump cannot be restarted until after 60 min. at the earliest.
28 Coolant pressure too low
The integrated low pressure switch tripped at
1.25 bar (g).
29 Coolant pressure outside the range
If the error occurs twice in a row the heat pump cannot be started until after 60 min. at the earliest.
Table 5.6 Temporary malfunctions
Operating Manual geoTHERM exclusive VWS 0020071929_0026
Page 27
5.10.6 Fault-induced shutdown
Errors could occur which result in the shutdown of the heat pump.
Fault code Error text/description
32 Error heat source sensor T8
Short-circuit in the sensor
33 Error heat circuit pressure sensor
short-circuit in the pressure sensor
34 Error brine pressure sensor
short-circuit in the pressure sensor
40 Error comp outlet sensorT1
Short-circuit in the sensor
41 Error heat source sensor T3
Short-circuit in the sensor
42 Error HP return sensor T5
Short-circuit in the sensor
43 Error HP flow sensor T6
Short-circuit in the sensor
44 Error external sensor AF
Short-circuit in the sensor
45 Error DHW tank sensor SP
Short-circuit in the sensor
46 Error HB flow sensor VF1
Short-circuit in the sensor
47 Error HB return sensor RF1
Short-circuit in the sensor
48 Error flow sensor VF2
Short-circuit in the sensor
52 Sensors are not suited to the
hydraulic plan
60 Frost protection heat source
monitoring source outlet
Error 20 has occurred three times in a row
62 Frost protection heat source
monitoring source outlet
Error 22 has occurred three times in a row
Emergency mode
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
WW operation possible
_
possible
possible
Operation 5
Fault code Error text/description
72 Flow temperature too high for
81 Coolant pressure too high
83 Coolant pressure too low check heat
84 Coolant pressure outside the range
90 Heating system pressure too low
91 Brine pressure too low
96 Error - sensor fault
97 no power for compressor possible
Table 5.7 Fault-induced shutdown (ctnd.)
underfloor heating
Flow temperature is for 15 min. higher than a set value (max. HK temp. + compr. hysteresis + 2 K).
Error 27 has occurred three times in a row
source
Error 28 has occurred three times in a row
Error 29 has occurred three times in a row
Pressure <0.5 bar Heat pump switches off and starts up automatically when the pressure increases to over 0.7 bar
Pressure <0.2 bar Heat pump shuts down and goes into operation automatically when the pressure rises above 0.4 bar
Short circuit in pressure sensor
• Consult your expert technician about doing this.
Note!
Only an expert technician can remedy
h
the fault and reset the error code.
Once the expert technician has remedied the error and reset the error he can restart the heat pump.
Emergency mode
_
possible
possible
possible
_
possible
possible
Table 5.7 Error shutdown
27Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 28
6 Warranty and customer service
6 Warranty and customer service
6.1 Vaillant warranty
Vaillant provide a full parts and labour warranty for this appliance. The appliance must be installed by a suitably competent person in accordance with the Gas Safety (Installation and Use) Regulations 1998, and the manufacturer’s in­structions. In the UK ‘CORGI’ registered installers under­take the work in compliance with safe and satisfactory standards. All unvented domestic hot water cylinders must be in­stalled by a competent person to the prevailing building regulations at the time of installation (G3). Terms and conditions apply to the warranty, details of which can be found on the warranty registration card in­cluded with this appliance. Failure to install and commission this appliance in com­pliance with the manufacturer’s instructions may invali­date the warranty (this does not affect the customer’s statutory rights).
6.2 Vaillant Service
To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agree­ment. Please contact Vaillant Service Solutions (0870 6060 777) for further details.
Operating Manual geoTHERM exclusive VWS 0020071929_0028
Page 29
Appendix 7
7 Appendix
7.1 Technical data
Caution!
R 407 C is a chlorine-free coolant which
a
Description Unit VWS 63/2 230 V VWS 83/2 230 V VWS 103/2 230 V
Article number - 0010007274 0010007275 0010007276 Height with connections
Width Depth without pillars Depth with pillars
Total weight
- With packaging
- Without packaging
- Ready for operation Transport weight
- Domestic hot water cylinder module
- Heat pump module Rated voltage
- Heating circuit/Compressor
- Control circuit
- Auxiliary heating Fuse, slow-blow
- Unblocked mains supply Alternative operation (as-delivered
condition 4 kW) Parallel operation A
dual-circuit supply, heat pump tariff
- Compressor, single
- Auxiliary heating 2/4 kW, single Dual-circuit supply, special tariff
- Alternative operation (as-delivered status 4kW) Parallel operation
- Pumps and controllers Start-up current
- Without start-up current limiter
- With start-up current limiter Rated output
- Min. for B-5W35
- Max. for B20W60
- Auxiliary heating
does not affect the ozone layer. Never­theless, servicing work on the cooling circuit should only be carried out by au­thorised specialists.
mm mm mm mm
kg kg kg
kg kg
-
A
A A
A
A A
A A
kW kW kW
1930
600 650 840
231 216
402
100 106
16/20 25/25 25/35 35/50
16
16/20
16/20 25/25 25/25 25/35
4
58
< 45
1.4
2.8 2/4
239 224
411
100
114
1/N/PE 230 V 50 Hz 1/N/PE 230 V 50 Hz 1/N/PE 230 V 50 Hz
25
16/20
35/50
4
76
< 45
1.9
4.0
2/4
242
227 415
100
117
25
16/20
35/50
4
97
< 45
2.4
4.9
2/4
EN 60529 level of protection - IP 20 Hydraulic connections
- Heating circuit flow and return
- Heat source flow and return
- Cold/hot water
Table 7.1 Technical data
mm mm mm
G 1 1/4", Ø 28 G 1 1/4", Ø 28
R 3/4"
29Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 30
7 Appendix
Description Unit VWS 63/2 230 V VWS 83/2 230 V VWS 103/2 230 V
Integrated domestic hot water cylinder
- Contents
- Max. operating pressure
- Max. temperature with heat pump
- Max. temp. with heat pump and auxiliary heating
Heat source circuit (brine circuit)
- Brine type
- Max. operating pressure
- Min. inlet temperature
- Max. inlet temperature
- Nominal flow rate dT 3K
- Residual head dT 3K
- Nominal flow rate dT 4K
- Residual head dT 4K
- Electrical power consumption - pump
CH circuit
- Max. operating pressure
- Min. flow temperature
- Max. flow temperature
- Nominal flow rate dT 5K
- Residual head dT 5K
- Nominal flow rate dT 10K
- Residual head dT 10K
- Electrical power consumption - pump
Refrigerant Circuit
- Coolant type - R 407 C
- Quantity
- Number of revolutions EX valve
- Permissible operating overpressure
- Compressor type
- Oil
- Oil filling quantity
DHW circuit Expansion vessel bar 4 4 4 Expansion valve setting bar 6 6 6 Maximum water supply pressure bar 10 10 10 Pressure reducing valve bar 3.5 3.5 3.5 Temperature and pressure relief valve
setting Heat up time min 113 98 86
Recovery time min 88 74 60 Heat pump performance data
B0W35 dT5
- Heating output
- Power consumption
- Performance figure/COP
B5W55
- Heating output
- Power consumption
- Performance figure/COP
Maximum passive cooling output under the following conditions: heating flow VL = 18 °C and heating return RL = 22 °C! Sound output dbA 48 49 50
Conforms to safety regulations - CE mark
l MPa (bar) °C °C
­MPa (bar) °C °C l/h mbar l/h mbar W
MPa (bar) °C °C l/h mbar l/h mbar W
kg
­MPa (bar)
-
­l
ba r 7 7 7 ºC 95 95 95
kW kW
-
kW kW
­kW 3.8 5.0 6.2
1453
335
1090
433
132
1061 386
517
490
93
1.9
9.0
1.3 1,45 1,45
6.0
1.4
4.2
6.3
2.1
3.0
Low Voltage Directive 73/23/EWG EMC Directive 89/336/EWG EN 60335 ISO 5149
Ethylene glycol 30 %
175
1 (10)
55 75
0.3 (3)
-10 20
1936
277
1452
397
132
0.3 (3) 25 62
1375
324 697
460
93
2.2
9.0
2.9 (29) Scroll
Ester
8,1
1.9
4.2
8.6
2.8
3.0
2530
216
1898
398
195
1803
399 848 580
132
2.05
9.0
10.5
2.5
4.2
10.8
3.5
3.1
Table 7.1 Technical data (cont.)
Operating Manual geoTHERM exclusive VWS 0020071929_0030
Page 31
Appendix 7
7.2 Identification plate
An identification plate is attached to the baseplate on the inside of the geoTHERM exclusive heat pump. The type designation is located at the top of the front clad­ding (see Fig. 4.3, Item 2).
Vaillant GmbH Remscheid / Germany
Serial-No. 21054500100028300006000001N1
VWS 63/2 230 V
IT FR NO LV LT EE ES UK
IP 20
1/N/PE 230V 50Hz
1/N/PE 230V 50Hz
1/N/PE 230V 50Hz
6,8 kW
2,8 kW
2 / 4 kW
16 A
COP B0/W35 COP B5/W55
B0/W35 B5/W55
21054500100028300006000001N4
< 45 A
175 I
1 (10) MPa (bar)
R407 C 1,9 kg 2,9 (29) MPa (bar)
4,2
3,0
6,0 kW
6,3 kW
Explanation of the symbols on the identification plate
Rated voltage - compressor
Rated voltage - pumps + controller
Rated voltage - auxiliary heating
Rated maximum power
Rated power - compressor, pumps and controller
Rated power - auxiliary heating
Start-up current without start-up current limiter
16 A
COP B0/W35
COP B5/W55
B0/W35
B5/W55
Start-up current with start-up current limiter
Service water tank capacity Permissible rated overpressure Coolant type Filling quantity Permissible rated overpressure
Performance figure at a brine temperature of 0 °C and a heating flow temperature of 35 °C
Performance figure at a brine temperature of 5 °C and a heating flow temperature of 55 °C
Thermal output with a brine temperature of 0 °C and a heating flow temperature of 35 °C
Thermal output with a brine temperature of 5 °C and a heating flow temperature of 55 °C
Fig. 7.1 Example of an identification plate
CE mark
VDE/GS mark
Read the Operating and Installation Manual!
Humidity protection class
Ensure proper disposal at the end of its useful life (not household waste)
21054500100028300006000001N4
Serial Number
Table 7.2 Explanation of symbols
31Operating Manual geoTHERM exclusive VWS 0020071929_00
Page 32
0020071929_00 GB 102008
Loading...