Vaillant GA100CS SERIES Installation And Service Manual

Page 1
GA100CS Series Combination Gas
Fired Cast Iron Boiler and Indirect
Water Heater
Vaillant ......
Installation and Service Manual
Table of Contents
Page
Number
2
1. Boiler Dimensions & Specifications
2. Rules for Safe Installation 3 & Operation
3. Locating the Unit 3
4. Combustion Air Requirements 3
5. Vent Pipe Connections 4
6. System Piping Boiler 5
7. Gas Supply Piping 5
8. Electrical Wiring 7
9. Flame Roll-Out 7
10. Blocked Vent System 9 11, Checkout Procedures 9
12. Maintenance Requirements 10
®
PRICE $5.00
Vaillant
Vaillant Corp.
2607 River Road Cinnaminson, NJ 08077
(609) 786-2000
Fax (609) 786-8465
All of our appliances should be installed by qualified fitters only, who will be responsible for the observance of all existing national and/or local installation inStructionsand code regulations. On installation please hand this pamphlet to your customer.
o)
T--
"T
o
z
Page 2
1. Boiler Dimensions & Specifications
I*-- 3o'/,"--÷1
SideView
Fig. 1 - GA100 CS Series Boiler
,-8
-IBI--
.=
t"------" 221/4" --'-*1
FrontView
with Door Off
[__._]A ---*
i°
16
t
RearView
ModM A B
" GAt00CS-6 10_/1" 5"
GAI00CS_ 11_11" 5" GAI00CS-10 12_4" 6'
]
1. High Limit Control (Tank)
2. Combination Control
3. Transformer Relay
4. Intermittent Ignition Control
5. Combination Pressure Temp. Gauge
6. Damper Actuator
7. Combination Gas Valve
8. Circulator
9. Wet Leg Drain Tappings
10. Pilot Inspection Door
11. Tank Inspection Plate
12. Water Storage Tank
13. Temperature Sensor Well
14. Air Scoop
15. Vent Valve
16. DivertingValve
17. Expansion Tank
18. Boiler drain _' NPT
19. Return 1" NPT
20. Supply 1" NPT
21. Domestic Water Out (Hot) ¾"
22. Domestic Water In (Cold) ¾"
23. Gas line ½" NPT
24. Draft Diverter
25. 30 PSI A.S.M.E. Relief Valve
26. Tank Drain
27.125 PSI A.S.M.E. T&P Relief Valve
BOILER " " "- HEATING I-B-R NET
INPUT WBGHT
MODEL BTU/HR CAPACITY RATING I.BS.
NO. BTU/HR B'I'U/HR
GA100CS -6 60,000 ,50,000 43,000 340 GA100CS -8 80,000 67,000 58,000 360
GA100CS -10 100,000 85,000 74,000 390
Page 3
2. Rules for Safe Installation &
Operation
1. Read this manual and the Owner's Manual carefully.
Failure to follow the rules for
safe operation and the instruc- tions could cause a malfunction
of the boiler and result in death, serious injury, and/or property
damage.
2. Check your local codes and
utility requirements before installation. The installation must be in accordance with
their directives.
3. Before servicing, allow boiler to
cool and always shut off any
electricity and gas to boiler
when working on it. This will
prevent any electrical shocks or burns.
4. Never test for leaks with open
flame. Use soap suds to check
all connections. This will avoid any possibilityof fire or explo-
sion.
5. Be certain boiler isequipped for type of gas (natural or propane) to be used. Over-firing will result
in premature failure of the boiler sections and cause dangerous operation.
6. Never vent this boiler into an enclosed space. Always con-
nect the boiler to the outside. Never vent to another room or
inside a building.
7. Be sure there is adequate air supply for complete combus-
tion.
8. Follow a regular service and
maintenance schedule for effi- cient and safe operation.
WHEN YOUR BOILER ARRIVES
BE SURE TO SAVE AND REFER
TO INSTRUCTION .S_"-
First, inspect each item received for visible damage or shortage. If any parts are damaged, report this to the freight company immediately, and request them to cell and make an inspection before you make any
installation. Have the Inspector prepare a signed report. Send
Vaillant a copy of this report and we will send replacements for the
damaged parts. But, we must have the signed inspection report ofthe freight company to prove their liability.
Examine all packaging material
carefully for loose parts before discarding.
Also, store all parts received where they will not be lost or damaged.
If you have had to unpack the boiler outside, you may also have to dis- assemble itto carry itto the installa-
tion area. In this case, use the Parts List drawings hereinto guide you.
NOTE: The GA1 O0CS Series of boilers were evaluated by the
American Gas Association to certify that they meet all of the safety crite-
ria of ANSI standard 7_21.13a-Latest Edition "Gas Fired Low Pressure Steam and Hot Water Boilers." Safe
lightingand other performance crite- ria were met with the gas manifold and control assembly provided on
the boiler when the boiler underwent tests specified in this standard. The following steps are all neces-
sary for proper installation and safe operation of the boiler.
1. Locating the boiler.
2. Fresh air for combustion.
3. Chimney & vent pipe connection.
4. System piping.
5. Gas supply piping.
6. Electrical wiring.
7. Check out and adjust.
8. Maintenance.
3, Locating the Unit
If unit is to be part of an existing
system, it is usually best to put it where the old one was. If you plan to change location, you will need
additional material as well as an adequate base. The following rules
apply not only to replacement boil- ers, they also applyto new installa-
tions:
1. The unit must be level.
2. Use a raised base if floor can
become wet or damp.
3. The vent pipe connection should be short. The center ofthe chim-
ney opening must be high enough to allow a '/,"per ft. upward slope in vent from unit to chimney opening
4. Maintain clearances for fire safety
as well as servicing. The room must have a total cubic
foot volume notless than 16
times that of the boiler.
5. Fresh air for combustionmust be available at the front ofthe boiler.
6. While this boiler may be installed on combustibleflooring, it must
not be installed on carpeting.
7. The installation mustconform to the requirements of the authority
having jurisdictionor, in the absence of such requirements, to
the national Fuel Gas Code. ANSI Z223.1-Latest Edition.
8. Where required by the authority having jurisdiction,the installation
must conform to American Society of Mechanical Engineers
Safety Code for Controls and Safety Devices for Automatically
Fired Boilers,No. CSD-I.
Clearance from Combustible
Materials
The following minimumclearances
are required between boiler and combustible construction:
Top ............................... 12 inches
Right Side....................... 6 inches
Left Side ......................... 6 inches
Rear................................ 6 inches
Flue Connector ............... 6 inches
Hot Water Pipe ................... 1 inch
Flue and stackmust be at least 6"
from combustible surfaces.
If hotwater pipe passes through
combustible floors,walls, or ceil-
ings, clearance must be not less
than ½"capped with a non-com-
bustible plate (see NFPA bulletin 89M, heating equipment clearance).
Servicing requirements may require larger clearances than those
required forfire safety.
As the electrical and piping connec- tions are at the rear of the unit,
there should be space to permit
access to the rear of the unit for ser-
vice.
Page 4
4. Combustion Air
Requirements
WARNING
Be Sure to Provide Enough Fresh
Air for Combustion
You must providefor enough fresh air to assure proper combustion.
The fire in the unit uses oxygen. The air in a house contains only
enough oxygen to supply the bumer for a short time. Outside air must
enter the house to replace that used bythe burner. Study the following
examples to determine your fresh air requirements.
EXAMPLE 1: UNIT LOCATION IN UNCONFINED SPACE
Ifyour unit is in an open area in a
conventional house, the air that leaks through the cracks around the
door and windows will usually be adequate to provide air for combus- tion. The doors should notfit tightly.
Do not caulk the cracks around the
windows.
EXAMPLE 2: UNIT LOCATED IN A HOUSE HAVING TIGHT CON- STRUCTION
If the house is of tight construction with weathemtripped windows, not enough outside air will enter for safe combustion. Installa duct orpipe
from a point near the burner to a ventilated attic or crawl space orthe
outside where fresh air is freely available. Vertical ducts should
have a net free area of 1 square inchfor each 4,000 BTU per hour input of all gas appliances and for
each 2,000 BTUihr. if horizontal ducts are used. Screen the open-
ings to keep animals and birdsfrom
entering. This is also required ifthe boiler is installed near an exhaust
fan orclothes dryer. Provisions for combustion and venti-
lation air in accordance with section
5.3, Air for CombustTon'_nd Ventilation, of the National Fuel Gas
Cede, ANSI Z223.1-Latest Edition, or applicable provisions of the local
building codes.
5. Vent Pipe
Connections
Check Your Chlmney
This is a very important part of your
heating system. It must be clean,
the dght size, propedy con_ed
and in good condition. No boiler can
function properly with a bad chim-
ney. If your chimney isjust big enough for your new boiler, it will not have extra capacity forother gas appliances.
When two or more appliances are vented into the same chimney, the
cress-section area inside the chim- ney must be at least equal to the
area ofthe largest vent PLUS ½the area of each additional vent.
For example, if your boiler vent has a diameter of 5 inches (area 19.6 square inches), the water heater vent, a diameter of 4 inches (12.6 square inches), the minimum chim- ney area must be 19.6+ ½ of 12.6 or
25.9 square inches. They will require a 6" diameter round chim-
ney.
When removing a boiler from a
common venting system the venting system is likely to be too large:for
proper venting of the remaining appliances connected to it.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the com-
mon venting system placed in oper-
ation, while the other appliances
remaining connected to the com- mon venting system are not in oper-
ation.
(a) Seal any unused openings in
the common venting system.
(b) Visually inspect the venting
system for proper size and hori- zontal pitch and determine there
isno blockage or restriction, leak- age, corrosion and other deficien-
cies which could cause an unsafe condition.
(c) Insofar as is practical, close all buildingdoors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryer and any appliance
not connected to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom exhausts,
4
so they will operate at maximum speed. Do not operate a summer
exhaust fan. (d) Place in operationthe appli-
ance being inspected. Followthe lighting instructions.Adjust ther- mostat so appliance will operate continuously.
(e) Test for spillage at the draft hoed relief opening after 5 min-
utes of main burner operation. Use the flame of a match or can-
dle, or smoke from a cigarette, cigar or pipe.
(f) After it has been determined that each appliance remaining
connected to the common vent- ing system propedy vents when
tested as outlined above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning appliance to their
previous conditionsof use. (g) Any improperoperation of the
common venting system should be corrected so the installation
conforms with the National Fuel Gas Code, ANSI Z223.1-Latest
Edition. When resizing any por- tion of the common venting sys- tem, the common venting system should be resized to approach
the minimum size as determined using the appropriate tables in
Appendix G in the National Fuel Gas Code, ANSI Z223.1-Latest
Edition
Connect the Vent Pipe
WARNING
NEVERINSTALLA MANUALLY OPERATED DAMPER IN THE VENT PIPE OFANY GAS APPLI- ANCE.
1. Do not modify draft diverter fur-
nished with the boiler.
2. Vent pipe must be same size as outlet collar on draft diverter.
3. Slope pipe up from b_ler'to chim- ney not less than ¼"per foot.
4. Run pipe as directly as possible with as few elbows as possible.
5. Do notconnect to fireplace flue.
6. The sections ofvent pipeshould be fastened with sheet metal screws
to make the piping rigid. Use stovepipe wires to support the pipe
from above.
Page 5
MinimumVentPipeClearance
fftheventpipemustgothrougha
crawlspace,doublewallventpipe
shouldbeused.Whereventpipe passesthroughacombustiblewail orpartition,Useaventilatedmetal
thimble.Thethimble should be 4
inches larger in diameter than the vent pipe. If boiler is installed with a
single wall galvanized type vent, it
must have 6" clearance between its surface and any combustible materi-
al. If Underwriters Laboratories list- ed type B (insulated vent pipe) is
used, clearance between it and combustible material to be as listed.
In lieu of thimble protection, all com- bustible material in the wall shall be
cut away from the vent pipe a suffi- cient distance to provide the clear- ance required from vent pipe to combustible material. Any material used to close up such opening shall
be non-combustible. For boilers for connection to gas
vents or chimneys, vent installations shall be in accordance with Part 7,
Venting of Equipment, of the National Fuel Gas Cede, ANSI Z223.1--Latest Edition, or applica- ble provisions of the local building
codes.
Automatic Vent Damper The GA100 Series of boilers are fit-
ted with an integral vent damper which is operated by an actuator
mounted on the front panel (See Fig. 1).
The stack damper should be
checked for alignment and freedom of operation priorto installation and
during subsequent routine service.
6. System Piping
Boiler Place the boiler in a selected loca-
tion (as near chimne_yyas possible). Your boiler is shipped assembled.
You need onlyto install a ¾"relief
valve drain line. Run a pipe from the relief valve outlet to an open drain, tub or sink, or other suitable drainage point not subject to freez-
ing. Failure to do so may cause
water damage or injuryshould the
relief valve open. Pipe must be _'ame size as outlet and open end
must not be threaded. Connect supply and returnlines to
boiler. The connections may require
certain additional fittings and parts
as shown on Fig. 2.
If you are replacing an old boiler
with this new one, possiblyallyou will need to do is to connect the
existing pipingto your boiler.
Ifyou are installing an entire new
heating system, firstinstall all of your radiation units (panels, radia- tors, or cabinets) and the supply
and return mains--then make the
connection to the boiler.
When connecting the cold water
supply tothe water valve, make
sure that a clean water supplyis
available. When the water supplyis
from a well or a pump, a sand
strainer should be installed at the
pump.
When boiler is used in connection
with refrigeration systems, it shall be
installed so that the chilled water is piped in parallel with the heating
boiler with appropriate valves to pre- vent the chilledwater from entering the heating system boiler.
The boiler piping system of a hot water heating boiler connected to
heating coils located inair handling
unitswhere they may be exposed to refrigerated air circulation must be
equipped with flow controlvalves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
NOTE: A hotwater boiler installed above radiation level must be pro-
vided with a low water cutoff device at the time of boiler Installation.
It is recommended that the boiler be installed with gate valves on the
supply and return lines so that it
may be removed for service without draining the entire system. The gate
valve on the supply pipe must not
be located between the boiler and the relief valve or expansion tank.
Water Heater The relief valve and drain valve for
the flow and for the hot water tank
(Fig. 2) are packed in separate boxes and mount directly to the flow and return.
If the selected temperature at the temperature control (Fig. 1, No. 1) is in excess of 125°F a mixing valve
should be installed to minimize the danger of scalding.
7. Gas Supply Piping
INSTALL GAS PIPING AS OUT- LINED IN THE AMERICAN
NA't'IONAL STANDARD ANSI Z223.1-1984-- NATIONAL GAS FUEL CODE FOR U.S.A. INSTAL- LATIONS
The gas pipe to your boiler should
run direct from the gas meter (or propane regulator). It should supply only the boiler. It must be the cor-
rect size for the length of the run and the boiler rating. See Fig. 3 for
the proper size. Be sure your gas
line complies withlocal codes and the gas company requirements.
Connecting the Gas Piping
Refer to Fig. 1 for the general layout
at the boiler. It shows the basic fit- tings you will need. The gas line
enters the boilerfrom the back. The
following rules apply:
1. Use new, properlycleaned
black iron piping and fittings,
free from chips.
2. Apply good quality pipe dope to pipe only, leaving 2 end threads
bare.
3. Install a sediment trap to trap dirt and moisture before it can
enter the boiler.
4. Install a manual shut-off valve in vertical pipe about 5 feet above,
floor (not supplied by Vaillant).
5. Tighten all joints securely.
6. Propane gas connections
should only be made by a licensed propane installer.
7. The boiler and its individual
shut-off valve must be discon-
nected from the gas supply pip- ing system during any.pressure
testing of that system at test
pressures in excess of ½psig.
8. The boiler must be isolated from the gas supplypiping system by
closing its individual manual shutoff valve during any pres-
sure testing of the gas supply
piping system at test pressure equal to or tess than ½psig
(3.5KPa).
Page 6
ZONE VALVE
IIIIIII1
HEATING cl_curr GATE
DRAIN VALVES
CIRCUITS VALVES
* ZONE VALVE
© __
III1[1111
t
vE_, _
VALVE
EXPANSION TANK
AIR SCOOP
ASME PRESS.
_-_ REUEF VALVE
I
BOILER
t
t
'._ to.,_._.
TO FAUCETS
&SHOWERS
ASMET&P
REUEFVALVE
DOMESTIC "-_ COLD WATER . - ..-
vALVE
DR/UN VALVE
t
STORAGE TANK
* NOTE:- Zone valves
should be located in the supply side of the
heating circuit as close as is possible to the three way valve. This
will minimize the chance of waterhammePoocuring.
CAUTION: When storage tank is above 125°F a mixing valve should be installed to minimize the chance ofscalding.
F,ig. 2 - Typical Piping Arrangements
Page 7
Checking the Gas Piping Upon completion of piping, chock
right away for gas leaks. Open the manual shut-off valve. Test for leaks
by applying soap suds (or a liquid detergent) to each joint. Bubbles
foaming indicate a leak.
CORRECT EVEN THE SMALLEST LEAK AT ONCE.
WARNING
NEVER USE A MATCH OR OPEN FLAME TO CHECK FOR LEAKS.
LENGTH OF PiPE
-FT.
NATURAL GAS
PiPE CAPACITY
CUBIC FEET/HOUR
_" ¾" 1" 1_"
20 74 150 280 580
40 50 100 195 400
60 40 84 155 320
80 34 72 135 275
Fig. 3 - Gas Pipe Capacities
MODEL GA100 CS -60 -80 -100
Elevation Sea level to 2,000 ft. 38 42 38 2,000 to 5,000 ft. 40 43 41
5,000 to 7,000 ft. 41 44 42 7,000 to 9,000 ft. 42 46 43
9,000 to 10,000 ft. 43 47 44
Fig. 4 - Orifice Size for Natural Gas
MODEL GA100 CS -60 -80 -100 Elevation
Sea level to 2,000 ft. 52 53 52 2,000 to 5,000 ft. 53 55 53
5,000 to 7,000 ft. 53 55 53 7,000 to 9,000 ft. 55 56 54
9,000 to 10,000 ft. 55 56 54
Fig. 5 - Orifice Sizefor Propane (LPG)
Orifice Sizing
All Vaillant GA100 CS series units
are factory equipped with orifices sized for installation at elevations
ranging from sea level up to 2,000
feet. For higher elevations, smaller
orifices are required to assure safe operation. Order the proper orifices
e
from your supplier and install them
before turning boiler on. See Figs. 4 &5.
8. Electrical Wiring
Install Your Thermostat.
The thermostat location has an
important effect on the operation of your boiler system. BE SURE TO
FOLLOW THE INSTRUCTIONS INCLUDED WITH YOUR THERMO- STAT.
Locate the thermostat about five
feet above the floor on an inside
wall. It may be mounted vertically on
the wall or on a vertically mounted
outlet box. It should sense average room temperature, so avoid the fol- lowing:
Dead Spots:
1. Behind doors
2. Corners and alcoves
Hot Spots:
1. Concealed pipes
2. Fireplaces
3. TV sets
4. Radios
5. Lamps
6. Direct sunlight
7. Kitchens
Cold Spots:
1. Concealed piping or ducts
2. Stairwell drafts
3. Door drafts
4. Unheated rooms on other side of wall
Control Wiring Diagrams Field Wiring and Wire Replacement in the following wiring diagrams
dashed lines .... represent fac-
tory wiring 24V; dashed lines
represent field wiring 24V;
solid lines -- represent factory
wiring 120V; solid lines _ rep-
resent field wiring 120V. Field wiring, whether for a new
installation or to replace damaged
field or factory installed widng, must
be the type listed below, and must be installed in accordance with the National Electric Code and all other
codes and standards covering the boiler installation.
120-Volt Wiring All new and replacement wiring
must be U.L. listedand 14-gauge size (minimum). Installwire in approved conduit. All terminals and splices must be in a listed covered
box.
If an external electrical source is uti- lized, the boiler, when installed,
must be electrically ground in accor- dance with the requirements ofthe authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code,
ANSI/NFPA No. 70-Latest Edition. 24-Volt (Low Voltage) Wiring
Use listed low-voltage cable. All junctions must be clean, joined firm- ly, and suitably covered with electri- cal tape or approved wire connec-
tors.
9. Flame Roll Out
The GA100 CS Series is equipped with a Flame Roll-Out Safety Shut-
Off System. The system is designed to shut offthe boiler if a blockage
occurs in the heat exchanger that causes flames to roll-outthe bottom
of the burner tray. Temperature acti- vated switch is located on a bracket
next to the pilot or ignitoron the underside of the burner tray.
When corrective action has been taken to eliminate the restriction
the pre-set switch has to be
replaced with a Vaillant supplied replacement.
10. Blocked Vent
System
The GA100 CS Series is equipped with a =BlockedVent Shut-Off
System'. This system relies on a temperature sensitive-6witch located
on the side ofthe draft hood. Ifthe vent pipe or chimney should
become obstructed to the point of not completely evacuating the flue
gases, the switch will break and close down the unit.
When the vent or chimney restric- tion has been removed, the switch
can be reset.
Page 8
I
I" I I
I !
i I
.......... °
fill
OUT I
llll
I I i LREO=_ I I I I
I L_ WHITE I I II
I GREEN I
GOLD
L8148E
© ®
BLUE BLUE
$8_0
i_ 24v TH
MV PV PV GiNID GND 24V -W
! ! I I
I
L .... _
BLUE
WHITE
_E
IMPORTANT:
F,_Wy W_V_ -_V
S_d Lira Rm_er_ Fmo,y W_) -_20V AAAAAAAA'*AAAAA ;'_'* *. FieklW_ng -120V
eI.ACK WHITE
I
I ....... .e.._m__K. __
! I
t_ -. __R___. i i L°
I IE I IT
t c B
I _-I
II YELLO_ 1 r-e--- -_ I "-f-
! -- I I --
', , [ , ' [
C°l Y I I v
! I J I
[
,-I i I=""='"_ _ i
;"_L _'- _'" '_' '
-_l f %1 " •, '
I f ,,,-,'r,'_l I I l
, R_ I \ ..... 11 , ,
...... ..,, ..T_/ •, ',
"n4REEWAYL _St.ACK __, I
I I
I-r.. I,,'.._ •; ', "-
I_,;_ I--- "b- e
Ik._,i_d,,_ _, ,
I I..... -_- ....
I I
#
DAMP IGN
glv-1
Fig. 6 - 24 Volt Intermittent Pilot System - Field Wiring Diagram
8
Page 9
11. Checkout Procedures
Test for Any Gas Leaks
Inspect carefully all gas connections
for gas leaks before lighting bumer.
Do not check for leaks with an open flame.
Test for leaks with a soap solution made of 2 tablespoons of flake, granular, orliquid soap mixed well with _ cup ofwarm water and spread generously on connection in question, using a brush or cloth.
For Your Safety Read Before Operating
WARNING
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACT- LY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
A. This appliance is equipped with
an ignition device which automati- cally lightsthe burners. Do not try to light the pilot by hand.
B. Before operating smell all around
the appliance area forgas. Be sure to smell next to the floor
because some gas is heavier
than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch;
do not use any phone inyour building.
Immediately call your gas sup- plier from a neighbor's phone, follow the gas supplier's instruc-
tions.
If you cannot.r.ea_,byour gas supplier, call the Fire
Department.
C. Use only your hand to push in or
turn the gas control knob, never
use tools. If the knob will not push in or turn by hand, don't try to
repair it, call a qualified service technician. Force or attempted
repair may result in a fire or explosion.
Operating Instructions
1. STOP! READ THE SAFETY INFORMATION.
2. Set room thermostat to lowest
temperature.
3. Turn off electric power.
4. Turn gas cock knob clockwise and turnto OFF. Wait five min- utes, then turn knob to latch position at ON.
5. Turn on electric switch. Burner should turn on when thermostat is
set above room temperature.
Reset Ignition System
1. Turn the thermostat to the low
end of itstemperature range.
2. Turn the electric switch to the OFF position.
3. Wait 5 minutes, then turn the system switch to ON position set
the thermostat at least 4°F
(2.2°C) above room temperature.
The boiler should start. Ifthe
above steps do not start the pilot and main burner, call your gas appliance service technician, do not attempt to light manually.
To Turn Off Gas To Appliance
1. Set the thermostat to lowest setting.
2. To shutoff burner manually, turn gas cock knob clockwise F'_ and turn to OFF position.
3. Turn off electric switch.
Adjustment of Gas Input--Natural
Gas
To check for proper flow of gas into
combustion chamber, determine the BTU/hr. input from the instruction
plate on the jacket. Divide this input by the BTU per cubic foot of avail- able gas to get the required number of cubic feet of gas per hour.
ELECTRONIC IGNITION
II_'T "_ OUTLET
GROUND
TERM_kt_L
B
VR8440
ELECTRONIC IGNmON
_CO_I ROUND
TERMINAL
INLET _
L g-J_B
VR8204A
HOT SURFACE IGNmON
GAS..>.
INLET
GAS CONTROL KNOB
36E03
- SIEP FEATURE
Determine flow of gas through the gas meter for 2 minutes and multiply
by 30 to get the hourly flow rate.
Turn off all other gas equipment
connected to meter when making this test.
Manifold pressure should be set to
about 4" W.C. for natural gas. Small variations in gas flow may be made
by means of the gas pressure regu- lator adjustment. However, the final manifold pressure setting should not
vary more than plus oTmlhus 0.3" from the 4" valve. Any necessary
major changes in the flowshould be made by changing the size of the
burner orifice.
Page 10
Safety Check of Controls After boiler has been hooked upand
is ready foroperation, a few simple checks should be made to be sure
all controls are functioning properly.
1. Thermostat--Turn thermostat to
highest setting. This shouldturn on the main burner. Adjust heat
anticipator to proper current draw.
2. Thermocouple--The pilot lights
the main burner on demand and provides a safety feature through
either a singlecouple thermocou- pie or multiple couple thermocou-
pie which is placed in the pilot flame. These thermocouples gen- erate a small amount of electricity which permits the valve to open only when the pilot is burning. To check the thermocouple for safe operation, ignite the main burner, then disconnect the thermocouple
lead. The main burner should shut off.
3. Limit--The limitturns off the
burner when the boiler water tem- perature reaches the temperature
setting of the limit. To check this, set the limitat a lowest setting
and let the burner run untilthe limitturns it off. Raise tempera-
ture setting of limit.This should turn on burner.
Relief Valve
You have a safety relief valve on
your boiler. It will automatically open at 30 psig pressure. This will relieve
the strain on the boiler and system.
Run apipe from the relief valve out-
let (pipe must be same size as out- let and open end must not be
threaded) to an open drain, tub or
sink, or other suitable drainage point not subject to freezing. Failure to do
so may cause water ci_mage or injuryshould Relief Valve release.
Main Burner The main burner flame can be
observed through the inspection door (Fig. 7). The flame should be
translucent and blue in color. The
presence of any yellow streaking would indicatethe presence of dust or lack of primary air. A vacuum
cleaning of the burner tray and com- bustion area is indicated.
DOOR _
Fkj.7
Checks for Electronic Ignition The probe lead connections to
sensing probe and controlterminal must be secure. Electrodes should
have a spark gap of '/a".If the pilot burner does notignite, check to see that all connections are proper.
Observe presence of spark. If spark is not present, determine if power is available to the control. The ignition controlshould be replaced if, with power applied and spark gap prop- erly set at _", sparking does not occur. If pilotgas does not light even though a spark is present, gas is not available at the pilot burner or
the gas pressure istoo low or high. If pilotignites, but burner does not,
check probe lead connections to the sensing probe and control.Do not attempt to field repair the control. Replace defective controls.
12. Maintenance Requirements
CLEANING MUST INCLUDE PERI- ODIC EXAMINATION OF VENTING
SYSTEMS. ALL FLUE GAS PAS- SAGEWAYS FROM BOILER TO CHIMNEY AND THE CHIMNEY
ITSELF SHOULD BE INSPECTED
AND CLEANED IF NECESSARY. THIS SHOULD BE PERFORMED
AT LEAST ONCE A YEAR, PRIOR TO THE STARTING OF THE
HEATING SEASON.
1. Brush entire surface of all flues using a long handled wire brush.
Remove all soot, rust and scale
found. Inspect with a flashlight to
see that all flueways are com- pletely open. Remove soot and
dirt from bottom of boiler.
2. Inspect the flue cover, draft
diverter, and smokepipe and replace unserviceable parts,
clean all soot, rust or scale from these parts and from chimney.
Clean the burners; use a soap solution if necessary.
CAUTION: If it becomes necessary
to remove the draft diverter, it must be rasealed to the casting using
new sealant to be sure no fumes
can escape.
3. Reassemble all parts and start the boiler following the installation instructions. Carefully inspect fire
above each burner for a stable and blue flame. Carbon monoxide
poisoning can be caused by yel- lowish unstable (wavy) flame.
10
Page 11
;urnerCleaning urnersshouldbeinspectedafter
achboilercleaning.Slots(ports) anbebrushedfreeofdirtandlint
,itha stiffbristle brush. Do not amage metal at ports. The pilot
nd thermocouple or pilot generator
should be brushed free of dirt. Take care notto damage pilot, bend it out of position, or to plug pilotgas port.
Maintained Inspection
The homeowner and service per-
sonnel must, at all times, be alerted
for these items:
1. Gas odor.
a) Open the windows. b) Do not touch any electrical
switch.
c) Extinguish any open flame,
ifpossible. d) Shut off the main gas valve. e) Call the gas supplier.
2. Excessive heat, odors, smoke, unusual noise. Shut off gas to
all appliances and call gas sup-
plier or Fire Department and service organization.
3. Keep area around the boiler clean and free from combustible
materials, gasoline and other flammable vapors and liquids.
4. Make allowances and maintain free flow of combustion and
ventilating air.
Freeze Protection If the boiler is taken out of service
during potentially freezing weather,
always DRAIN IT COMPLETELY since any water left inthe boiler or pipes can freeze and cause dam- age. Be sure to open drain cocks on
the wet legs of the left and right castings, see Fig. 1.
Pilot and Burner Check for proper pilotflame as
explained in "Checkout Procedures' on page 9.
BurnerPorts
and Slots 4- 3/..
-..-,/.. ±'/."
PilotBracketMounted
on BurnerPanel
ForUse withNatural
& PropaneGas
Pilot and Burner Assembly - GA100 -60 Thru GA100 -100 E.I.
Fig. 9 - Electronic Ignition
11
Page 12
Vaillant
Vaillant Corp. 2605-07 River Road
Cinnaminson, NJ 08077 (609) 786-2000
m
Booklet No.:2180-0113
Loading...